Home > Products > Solutions > Soft PLC, Win-GRAF & eLogger HMI > Win-GRAF > XPAC-8000-CE6
 
XP-8000-CE6 Series (Win-GRAF based)
XP-8038-CE6, XP-8138-CE6, XP-8338-CE6, XP-8738-CE6
 
~ New ~
     
 
XP-8038-CE6
 
XP-8138-CE6
     
 
  x86 CPU, 1.0 GHz, dual-core
  Windows CE 6.0
  Embedded Win-GRAF SoftLogic (IEC 61131-3)
  Hard Real-Time Capability
  VGA Port Output
  Modbus RTU/TCP (Master, Slave)
  Support eLogger HMI
  Redundant Power Inputs
  Support Dual PAC Redundant System
  Operating Temperature: -25 ~ +75 °C
 
 
       
   
XP-8338-CE6   XP-8738-CE6  
 

The Win-GRAF XPAC-8000-CE6 Series (XP-8038-CE6/XP-8138-CE6/XP-8338-CE6/XP-8738-CE6) is the new generation WinCE 6.0 based Win-GRAF XPAC-CE6 (Programmable Automation Controller) from ICP DAS. Each is equipped with an x86 CPU (1 GHz) dual-core running a Windows CE 6.0 operating system, a variety of input/output ports (VGA, USB, Ethernet, RS-232/485), and a range of I/O slots (0/1/3/7) that can be used to integrate high performance parallel I/O modules (high profile I-8K Series) or serial I/O modules (high profile I-87K series)

The benefits of running Windows CE 6.0 on a XPAC device include hard real-time capability, achievable deterministic control and allowing PAC can have a PC-like window displays and operating environment. The PACs are capable of running Win-GRAF (IEC 61131-3 Standard) software to develop logic control applications, and also supporting M.S. VS 2008 software (VB .NET, C#) to develop HMI and data management applications that can exchange data with Win-GRAF applications. So the application's design is more convenient and more practical.

 

Win-GRAF is a powerful, PLC-like, softlogic development software.It is installed on PC with windows 7 or 8 (or later version). It supports the international PLC language standard - IEC 61131-3 - Ladder Diagram (LD), Function Block Diagram (FBD), Sequential Function Chart (SFC), Structured Text (ST), Instruction Set (IL), suitable to develop applications for the full range of Win-GRAF PACs from ICP DAS.

IEC 61131-3 Standard Open PLC Syntax (LD, FBD, SFC, ST, IL)
Using ST Syntax in the FBD or LD Program
Event Triggered Data Binding (Exchange Data between PACs)
Online Debugging/Control/Monitoring, Offline Simulation
On Line Change
Various Protocols:
    - Modbus TCP/UDP, Modbus RTU/ASCII Master
    - Modbus TCP, RTU Slave
    - DCON ...
Plenty of Functions, Function Blocks, I/O Boards
Redundancy (For XP-8x38-CE6 PAC only)
 
 
TOP | HOME
 Note: Except for specially noted items, all applications are applicable to the Win-GRAF PAC (i.e., WP-8xx8, WP-5xx8-CE7,
           WP-8xx8-CE7, WP-9xx8-CE7, VP-x2x8-CE7, XP-8x38-CE6 PAC).
  Redundant System   Schedule Control 
For XP-8x38-CE6 PAC only.
Only CPU is Redundant
Both CPU and I/O Modules are Redundant
  On Line Change Modbus Master Ports
Replace the current running project to a new modified one
   without stopping the project.
 



  eLogger HMI Modbus RTU/TCP Slave Ports



  Event Triggered Data Binding DCON Remote I/O
Exchange data between PACs.
  Intelligent Win-GRAF 3G Solution  
Only the WG-Communication Server (behavior like a Cloud Server) needs a public IP (support Domain Name).
   Other PACs and PCs that connect to this Server no need a public IP.
The user can monitor the remote PAC by using a 3G wireless network or an intranet.
The user can use the Win-GRAF Workbench to connect to a remote PAC to debug/update the Win-GRAF program or
   update the Win-GRAF PAC Driver.
The PAC can actively send a Log File to a PC (WG-Communication-Server).

  Support VS 2008 Development  
The Win-GRAF PACs support to use VS 2008 (VB.net, C#) to develop user own HMI and data management
   programs, and can exchange variables with the Win-GRAF control programs.

 
  Create Your Own Functions and Function Blocks
For some reason (like business protection, integration with your own product protocol, and etc.), you can develop your
   own functions and function blocks by VS 2008. Then, you can use these functions and function blocks in
   the Win-GRAF project.

  PID Control
Can Control more than 200 PID in one PAC.

 
 
 
TOP | HOME
Models XP-8038-CE6 XP-8138-CE6 XP-8338-CE6 XP-8738-CE6
System Software
OS Windows CE 6.0
.Net Compact Framework 3.5
Embedded Service FTP Server, ASP (Java Script, VB Script), SQL Compact Edition 3.5
SDK Provided Dll for Visual Studio .Net 2005/2008
Multilanguage Support English, German, French, Spanish, Russian, Italian, Japanese, Simplified Chinese, Traditional Chinese
Development Software
Win-GRAF
Software
Win-GRAF IEC 61131-3 standard
Languages LD, ST, FBD, SFC, IL
Max. Code Size 2 MB
Scan Time 3 ~ 15 ms for normal program
15 ~ 50 ms (or more) for complex or large program
Non-Win-GRAF Options: VS.NET 2008 (VB.NET, C#.NET, C)
CPU Module
CPU x86 CPU, 1.0 GHz, dual-core
System Memory 2 GB DDR3
Non-volatile Memory, MRAM 512 KB (retain memory without battery support)
Flash 32 GB
EEPROM 16 KB (Data Retention: 40 years; 1,000,000 erase/write cycles)
CF Card 8 GB (support up to 32 GB)
RTC (Real Time Clock) Provides seconds, minutes, hours, day of week, month, year
Programmable LED Indicator 2
64-bit Hardware Serial Number Yes, for Software Copy Protection
Dual Watchdog Timers Yes
Rotary Switch Yes (0 ~ 9)
DIP Switch - Yes (8 bits)
Audio Microphone-In and Earphone-Out
VGA & Communication Ports
VGA Yes, (resolution: 1024 x 768, 800 x 600, 640 x 480)
Ethernet RJ-45 x 2, 10/100/1000 Base-T (Auto-negotiating, Auto MDI/MDI-X, LED indicators)
USB 2.0 4
COM 1 RS-232 (RxD, TxD and GND); non-isolated Internal communication with the high profile I-87K series modules in slots
COM 2 RS-232 (RxD, TxD and GND); non-isolated
COM 3 RS-485 D2+, D2-; self-tuner ASIC inside
Isolation 3000 VDC
COM 4 RS-232/RS-485 (RxD, TxD, CTS, RTS and GND for RS-232, Data+ and Data- for RS-485);
non-isolated
COM 5 RS-232 (RxD, TxD, CTS, RTS, DSR, DTR, CD, RI and GND); non-isolated
I/O Expansion Slots
Slot Number 0 1 3 7
Note: For High Profile I-8K and I-87K Modules Only
Mechanical
Dimensions (W x L x H) 137 x 132 x 125 mm 169 x 132 x 125 mm 231 x 132 x 125 mm 355 x 132 x 125 mm
Installation DIN-Rail or Wall Mounting
Environmental
Operating Temperature -25 ~ +75°C
Storage Temperature -30 ~ +80°C
Ambient Relative Humidity 10 ~ 90% RH (non-condensing)
Power
Input Range +10 ~ +30 VDc
Isolation 1 kV
Redundant Power Inputs Yes, with one power relay (1 A @ 24 VDC) for alarm
Capacity 20 W 20 W 35 W 35 W
Consumption 12 W
(0.5 A @ 24 VDC)
16.6 W
(0.69 A @ 24 VDC)
16.8 W
(0.7 A @ 24 VDC)
18 W
(0.75 A @ 24 VDC)
 
TOP | HOME
Protocols (Note that certain protocols require optional devices)
NET ID 1 ~ 255, for Modbus TCP/RTU Slave, user-assigned.
Modbus TCP Master A max. of 200 IP links to access/control the devices supporting Standard Modbus TCP Slave protocol.
Modbus RTU/ASCII Master A max. of 32 ports: COM1 ~ 33 (*) to connect other Modbus Slave devices(Like M-7000).
Recommend connecting no more than 32 devices in each port for better scan rate.
Modbus RTU Slave A max. of 16 ports: COM1 ~ 33 (*) for connecting SCADA/HMI/OPC Server.
Modbus TCP Slave Two Ethernet ports (LAN1 & LAN2) support up to 64 connections. If the PAC uses 1 connection to connect each PC/HMI, it can connect up to 64 PCs/HMIs; If the PAC uses 2 connections to connect each PC/HMI, it can connect up to 32 PCs/HMIs; If one of the Ethernet port malfunctions, the other one can still be used to connect the PC/HMI.
User-defined Protocol Custom protocols can be applied at COM1 ~ 33 (*) by using Serial communication functions or function blocks.
DCON Remote I/O A max. of 16 RS-485 ports: COM1 ~ 33 (*). Each port can connect max. 50 nos I-7000 series modules or 50 nos I-87xxxW I/O modules in expansion units (I-87K4, I-87K8, I-87K9, RU-87P8, RU-87P4). Recommend connecting no more than 32 modules in each port for better scan rate.
Local I/O Modules Supports only high profile I/O modules. Slot 1 ~ 7 supports I-8xxxW parallel I/O modules and I-87xxxW serial I/O modules. (Refer Optional I/O List)
App Protection Using the unique 64-bit (8 bytes) PAC serial number to generate a protection password by your own algorithm to protect your Win-GRAF application. Then, if someone intend to copy your application in the PAC to another new PAC with the same PAC model, this application will not work properly in that new PAC.
Redundancy 2 XP-8x38-CE6 can set a redundant system, when one is damaged or crashes, the other can still take up and continue the work. The system offers 3-line communication redundancy, LAN1, LAN2 and Alive Port, as long as one of the three communication lines still connects normally, this redundant system can normally control the process. The redundant system provides a public IP address that allows SCADA/ HMI software to access it without needing to determine which one is the Active IP.
Data Binding Exchange data between ICP DAS Win-GRAF PAC via Ethernet ports (LAN1 and LAN2). The data transmission is event triggered. It is much efficient than polling way. Beside, user can setup the Redundant Binding in two ethernet ports by Software, then if one Ethernet port fail, it can switch to use the other port.
On Line Change For application field that not allowed to stop the Win-GRAF program and wish to run a new program modified a little from the original program.
Modbus RTU I/O When software enables Modbus RTU Master function, the PAC can connect ICP DAS M-7000 and tM series and LC series I/O modules which support Modbus RTU protocol.
Modbus TCP I/O When software enable Modbus TCP Master function, the PAC can connect ICP DAS I-8KE4/8-MTCP, PETL-7000, tPET/tET series I/O modules which support Modbus TCP protocol.
HART Master Support I-87H17W modules in slot 1 to 7 to communicate with other HART devices.
Schedule Control Supports the "Schedule-Control Utility" (free) to implement schedule control. Each PAC can control max. 10 Targets (devices) with different schedule settings in each day / holiday / special day / season / year.
Retain Variables Built-in the fast retain memory that can retain up to 12,000 Win-GRAF variables.
File Access and Data Log The Win-GRAF supports file operation functions to read/write files in the PAC's micro_SD or flash memory to do data log or file access.
eLogger HMI Support to run HMI program (developed by the eLogger) together with the Win-GRAF logic-control program in the same PAC.
Optional I/O List (Go to I-8K, I-87k Selection Guide)
Digital Input (DI) I-8040W, I-8040PW, I-8046W, I-8051W, I-8052W, I-8053W, I-8053PW, I-87040W, I-87040PW,
I-87046W, I-87051W, I-87052W, I-87053W, I-87053PW, I-87053W-A2, I-87053W-A5, I-87053W-E5
Digital Input/Output (DIO) I-8042W, I-8050W, I-8054W, I-8055W, I-87042W, I-87054W, I-87055W
Digital Output (DO) I-8037W, I-8041W, I-8041AW, I-8056W, I-8057W, I-87037W, I-87041W, I-87057W, I-87057PW
Relay Output I-8060W, I-8063W, I-8064W, I-8068W, I-8069W, I-87061W, I-87061PW, I-87063W, I-87064W,
I-87065W, I-87066W, I-87068W, I-87068W-2A, I-87069W, I-87069PW
AC Input I-8058W, I-87053W-AC1, I-87058W, I-87059W
Analog Input (AI) I-8017DW, I-8017HW, I-8017HCW, I-87017W, I-87017RW, I-87017RCW, I-87017DW, I-87017W-A5, I-87017ZW, I-87018W, I-87018RW, I-87018PW, I-87018ZW, I-87019PW, I-87019RW, I-87019ZW
Analog Output (AO) I-8024W, I-87024CW, I-87024UW, I-87024DW, I-87024RW, I-87024W, I-87028CW, I-87028UW,
I-87028VW, I-87028VW-20V
Multifunction (DIO, AIO) I-87026W
Temperature
Input
Thermistor I-87005W
RTD -87013W, I-87015W, I-87015PW
T/C I-87018W, I-87018RW, I-87018PW, I-87018ZW, I-87019PW, I-87019RW, I-87019ZW
Strain Gauge I-87016W
Counter/Frequency Input I-8084W, I-87082W, I-87084W
Encoder Input I-8093W
PWM Output I-8088W
HART I-87H17W
GPS GPS-721
Communication Module I-8112iW, I-8114W, I-8114iW, I-8142iW, I-8144iW
Temperature & Humidity Input DL-100T485, DL-100T485-W, DL-100T485P, DL-100T485P-W (DCON Protocol)
DL-100TM485, DL-100TM485-W, DL-100TM485P, DL-100TM485P-W (Modbus RTU Protocol)
* Note: COM6 ~ COM33 ports are located in the expansion boards (I-8142iW, I-8144iW, I-8112iW, I-8114W, I-8114iW)
             if they are installed in slot 1 ~ 7 of XP-8x38-CE6.
* The COM1 port on XP-8038-CE6 is RS-232;
   COM1 on other Win-GRAF XPAC is for internal communication with I-87K modules installed in slots only.
 
TOP | HOME
XP-8038-CE6 CR 0 I/O slot WinCE 6.0 Based Win-GRAF XPAC (OS: Multi-Language version) (RoHS)
XP-8138-CE6 CR 1 I/O slot WinCE 6.0 Based Win-GRAF XPAC (OS: Multi-Language version) (RoHS)
XP-8338-CE6 CR 3 I/O slots WinCE 6.0 Based Win-GRAF XPAC (OS: Multi-Language version) (RoHS)
XP-8738-CE6 CR 7 I/O slots WinCE 6.0 Based Win-GRAF XPAC (OS: Multi-Language version) (RoHS)
XPCE6-GUP-18000 Upgrade XP-8x31-CE6 to XP-8x38-CE6 to support Win-GRAF.
 
Win-GRAF Development Software
Win-GRAF Workbench Win-GRAF Workbench Software (Large I/O Tags) with one USB Dongle.
 
Power Supply 24 VDC Power Supply with DIN-Rail Mounting (RoHS)
Ethernet Switch 5 to 8 Ports Real-time Redundant Ring Ethernet Switch (RoHS)
5 to 16 Ports Unmanaged Industrial Ethernet Switch (RoHS)
Converter RS-232/422/485 Converter (RoHS)
USB to RS-232/422/485 Converter (RoHS)
TPM-4100 / TP-4100 10.4" (800 x 600) resistive touch panel monitor with RS-232 or USB interface
 