| PM-3112 | PM-3114 | PM-3112-MTCP | PM-3114-MTCP | |
| No. of Measurement circuit | 2 single phase circuits | 4 single phase circuits | 2 single phase circuits | 4 single phase circuits |
| No. of Input Voltage | 2 | 2 | 2 | 2 |
| No. of Input Current | 2 | 4 | 2 | 4 |
| Input Voltage | 10 - 300 V | |||
| Input Current | Wired clip-on CT,CT Φ10 mm ( 60 A), CT Φ16 mm (100 A), CT Φ24 mm (200 A) | |||
| Frequency | 50 / 60 Hz | |||
| Wiring diagram | 1P2W | 1P4W | 1P2W | 1P4W |
| Power Parameters Measures | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency | |||
| W Accuracy | better than 0.5% (PF=1) | |||
| Communication | RS485 / Modbus RTU | Ethernet / Modubs TCP | ||
| Relays | Form A (Normal Open) x 2; Relay Contact Voltage Range : 5 A @ 250 VAC (47 ~ 63Hz), 5 A @ 30 VDC | |||
| PM-3033 | PM-3133 | PM-3133-RCT | PM-3033-MTCP | PM-3133-MTCP | PM-3133-RCT-MTCP | |
| No. of Measurement circuit | 1 three phase circuits | 1 three phase circuits | 1 three phase circuits | 1 three phase circuits | 1 three phase circuits | 1 three phase circuits |
| No. of Input Voltage | 1 | 1 | 1 | 1 | 1 | 1 |
| No. of Input Current | 3 | 3 | 3 | 3 | 3 | 3 |
| Input Voltage | 10 - 500 V | |||||
| Input Current | 1A or 5A | External type CT, CTØ10 mm (60 A); CTØ16 mm (100 A); CTØ24 mm (200 A); CTØ36 mm (300 A); CTØ36 mm (400 A) |
Rogowski Coil CT, CTØ55 mm (500 A); CTØ80 mm (1000 A); CTØ105 mm (2000 A); |
1A or 5A | External type CT, CTØ10 mm (60 A); CTØ16 mm (100 A); CTØ24 mm (200 A); CTØ36 mm (300 A); CTØ36 mm (400 A) |
Rogowski Coil CT, CTØ55 mm (500 A); CTØ80 mm (1000 A); CTØ105 mm (2000 A); |
| Frequency | 50 / 60 Hz | |||||
| Wiring | 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT | |||||
| Power Parameters Measures | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency | |||||
| W Accuracy | better than 0.5% (PF=1) | Better than 1% (PF=1; Input Current >50 A) |
better than 0.5% (PF=1) | Better than 1% (PF=1; Input Current >50 A) |
||
| Communication | RS485 / Modbus RTU | Ethernet / Modubs TCP | ||||
| Relays | - | Form A (Normal Open) x 2; Relay Contact Voltage Range : 5 A @ 250 VAC (47 ~ 63Hz), 5 A @ 30 VDC |
- | Form A (Normal Open) x 2; Relay Contact Voltage Range : 5 A @ 250 VAC (47 ~ 63Hz), 5 A @ 30 VDC |
||
| PM-2133D | PM-2133D-MTCP | PM-5133 | |
| No. of Measurement circuit | 1 three phase circuits | ||
| No. of Input Voltage | 1 | ||
| No. of Input Current | 3 | ||
| Input Voltage | 10 - 500 V | ||
| Input Current |
PM-2133D-005P: CTØ10 mm (0.05 A ~ 5 A) PM-2133D-100P: CTØ10 mm (0.05 A ~ 60 A) PM-2133D-160P: CTØ16 mm (0.1 A ~ 100 A) PM-2133D-240P: CTØ24 mm (0.15 A ~ 200 A) PM-2133D-360P: CTØ36 mm (0.3 A ~ 300 A) PM-2133D-400P: CTØ36 mm (0.3 A ~ 400 A) |
PM-5133-005P: CTØ10 mm (0.05 A ~ 5 A) PM-5133-100P: CTØ10 mm (0.05 A ~ 60 A) PM-5133-160P: CTØ16 mm (0.1 A ~ 100 A) PM-5133-240P: CTØ24 mm (0.15 A ~ 200 A) PM-5133-360P: CTØ36 mm (0.3 A ~ 300 A) PM-5133-400P: CTØ36 mm (0.3 A ~ 400 A) |
|
| Frequency | 50 / 60 Hz | ||
| Wiring | 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT | ||
| Power Parameters Measures | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency | ||
| W Accuracy | better than 0.5% (PF=1) | ||
| Communication | RS485 / Modbus RTU | Ethernet / Modubs TCP | RS485 / Modbus RTU |
| PM-4324 | PM-4324A | PM-4324-MTCP | PM-4324A-MTCP | |
| No. of Measurement circuit | 8 three phase circuits or 24 single phase circuits | |||
| No. of Input Voltage | 1 | 2 | 1 | 2 |
| No. of Input Current | 24 | 24 | 24 | 24 |
| Input Voltage | 10 - 500 V | |||
| Input Current | External type CT, CTØ10 mm (60 A); CTØ16 mm (100 A); CTØ24 mm (200 A); CTØ36 mm (300 A); CTØ36 mm (400 A) |
|||
| Frequency | 50 / 60 Hz | |||
| Wiring | 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT | |||
| Power Parameters Measures | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency | |||
| W Accuracy | better than 0.5% (PF=1) | |||
| Communication | RS485 / Modbus RTU | Ethernet / Modubs TCP | ||
| Relays | Form A (Normal Open) x 2; Relay Contact Voltage Range : 5 A @ 250 VAC (47 ~ 63Hz), 5 A @ 30 VDC |
|||
| iWSN-9603-1P / iWSN-9603-3P | ||||||||||||
| No. of Measurement circuit | 2 three phase circuits or 4 single phase circuits | |||||||||||
| No. of Input Voltage | 1 | |||||||||||
| No. of Input Current | 4(Single Phase) / 2(Three Phase) | |||||||||||
| Input Voltage | Three phase 4 wire x1, 100 - 480 VAC (58 - 277 VAC single phase) | |||||||||||
| Input Current |
|
|||||||||||
| Frequency | 50 / 60 Hz | |||||||||||
| Wiring | 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT | |||||||||||
| Power Parameters Measures | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Power Factor (PF) | |||||||||||
| W Accuracy | better than 1% (PF=1) | |||||||||||
| RF | ||||||||||||
| Channels | 0 ~ 15 | |||||||||||
| Group ID | 0 ~ 3 | |||||||||||
| Radio Frequency | 433.1000 ~ 434.6000 MHz | |||||||||||
| Transmission Power | 9±1dBm (PA Off) / 18±1dBm (PA On) | |||||||||||
| Transmission Distance (LoS) | 100 m | |||||||||||
| Node ID | 1 ~ 31 | |||||||||||
| Working Duty | 1, 10, 30, or 60 Seconds | |||||||||||