DeviceNet is one kind of the network protocols based on the CAN bus and mainly used for the embedded network of the machine control, such as industrial machine control , aircraft engines monitoring, factory automation, medical equipments control, remote data acquisition, environmental monitoring, and packaging machines control, etc.
The CAN-2018D follows DeviceNet specification Volume I/II, Release 2.0. User can access the thermocouple input status and set the configuration via DeviceNet EDS file. CAN-2018D has 8-channel thermocouple input and it can be used to various applications. By the DeviceNet masters of ICP DAS, you can quickly build a DeviceNet network to approach your requirements. For more information about the DeviceNet master interfaces and other DeviceNet products, please refer to the following web site.
|
|
|
|
Applications |
|
|
|


We have communicated with the following DeviceNet masters or gateways.
- Allen-Bradley(AB) 193-DNENCAT, 193-DNENCATR
- OMRON CJ1W-DRM21
- OMRON CS1W-DRM21-V1
- OMRON C200HW-DRM21-V1
- OMRON 3G8F7-DRM21-E
|
|
|
|
Hardware Specifications |
|
|
|
DeviceNet Interface |
DeviceNet Specification |
Volume I, Release 2.0 & Volume II, Release 2.0, Errata5 |
DeviceNet subscribe |
Group 2 Only Server |
Connection supported |
1 connection for Explicit Messaging
1 connection for Polled I/O
1 connection for Bit-Strobe I/O |
Baud Rate
Setting by Rotary Switch |
125 kbps, 250 kbps, 500 kbps |
Node ID
Setting by Rotary Switch |
0 ~ 63 |
Heartbeat message |
Yes |
Shutdown message |
Yes |
Terminal Resistor |
Switch for 120 Ω terminal resistor |
Connector |
5-pin screwed terminal block
(CAN_GND, CAN_L, CAN_SHLD, CAN_H, CAN_V+) |
EDS file |
Yes |
Analog Input |
Channels |
8 |
Input Type |
+/- 15mV, +/- 50mV, +/- 100mV, +/- 500mV, +/- 1V, +/- 2.5V
+/-20mA,(Requires Optional External 125 Ohm Resistor)
Thermocouple (J, K, T, E, R, S, B, N, C) |
Resolution |
16-bit |
Sampling Rate |
10 Samples/Sec. (Total) |
Accuracy |
+/-0.1% FSR |
Zero Drift |
+/- 10 μV/ °C |
Span Drift |
+/- 25 ppm/ °C |
Common Mode Rejection |
86 dB |
Normal Mode Rejection |
100 dB |
Input Impedance |
>400 kΩ |
Individual Channel Configuration |
Yes |
Open Thermocouple Detection |
Yes |
Over voltage Protection |
240 Vrms |
ESD Protection |
+/-4kV, Contact for each terminal. |
Intra-module Isolation, Field to Logic |
3000 VDC |
LED |
Power |
PWR, red |
DeviceNet Status |
NET/MOD, green/orange |
Power |
Power Supply |
Unregulated +10 ~ +30 VDC |
Power Consumption |
1.5 W |
Mechanism |
Installation |
DIN-Rail |
Dimensions |
33 mm x 99 mm x 78 mm (W x L x H) |
Environment |
Operating Temp. |
-25 ~ 75 ℃ |
Storage Temp. |
-30 ~ 80 ℃ |
Humidity |
10 ~ 90% RH, non-condensing |
|
|
|
|
Thermocouple Type |
|
|
|
Type Code |
Temperature Range (°C) |
J |
-210 °C ~ +1200 °C |
K |
-270 °C ~ +1372 °C |
T |
-270 °C ~ +400 °C |
E |
-270 °C ~ +1000 °C |
R |
-50 °C ~ +1765 °C |
S |
-50 °C ~ +1765 °C |
B |
0 °C ~ +1820 °C |
N |
-270 °C ~ +1300 °C |
C |
0 °C ~ +2320 °C |
|
|
|
|
Ordering Information |
|
|
|
|
DeviceNet Slave Module of 8-channel Thermocouple Input
Include CAN-2018D module and a CN-1824 daughter board |
|
|
|
|
Related Products |
|
|
|
DeivceNet Master Library |
Support PISO-CAN serials, PEX-CAN serials and PCM-CAN with DeviceNet master library |
PISO-DNM100U-D
PISO-DNM100U-T |
1 Port Intelligent DeviceNet Master Communication Board with DeviceNet Firmware Inside for universal PCI bus |
I-7565-DNM-G CR |
USB/DeviceNet Master communication Converter with D-sub 9-pin connector |
I-8124W |
1 Port DeviceNet Master Module with dual port RAM |
I-87124 |
1 Port High Performance DeviceNet Master Module |
CA-0910-C |
9-pin Female D-sub & 3-wire CAN bus cable (1M) |
|
|
|
|
TOP |
|
|
|
|
|
|