SG-3000 series signal conditioning modules are used to accept wide range of input signals, such as voltage, current, temperature (Thermocouple and RTD) and provide 0 ~ 10 VDC, 0 ~ 20 mA, 4 ~ 20 mA output signals. It gives following good features for industrial applications:
  • 3-way (power/input/output) isolation (1000 VDC)
  • Wide operating temperature (-25 ~ +75°C)
  • DIN-Rail mounting
  • Input and output connectors on the opposite side
  • Signal range configurable by switch
SG-3000 Series
Model Input Output
Channel Signal Bandwidth Channel Voltage Current
SG-3011-G 1 Thermocouple 10 Hz 1 0 ~ 10 VDC 0 ~ 20 mA
SG-3011H-G 500 Hz/10 Hz
SG-3013-G 1 RTD - 1 0 ~ 5 VDC
0 ~ 10 VDC
0 ~ 20 mA
4 ~ 20 mA
SG-3016-G 1 Strain Gauge 600 Hz 1 ±5 VDC, ±10 VDC, 0 ~ 5 VDC, 0 ~ 10 VDC 0 ~ 20 mA
SG-3016-80-G 80 Hz
SG-3071-G 1 Voltage
(±5 VDC, ±10 VDC)
1 kHz 1 ±5 VDC, ±10 VDC 0 ~ 20 mA, 4 ~ 20 mA
SG-3081-G 1 Current
(0 ~ 20 mA, 4 ~ 20 mA)
1 kHz 1 0 ~ 5 VDC, 0 ~ 10 VDC 0 ~ 20 mA, 4 ~ 20 mA
SG-3383 1 4 ~ 20 mA 2.5 kHz 3 - 4 ~ 20 mA
 
 
SG-3000 Series
Model Input for Accelerometer Output
Channel Signal Excitation Bandwidth Supported
Accelerometer
Channel Signal
SG-3037-G 3 Voltage
(0 ~ 24 VDC)
24 VDC 50 kHz iSN-703-BALT-F1-L015
(3-axis)
3 ±10 VDC
SG-3227 2 IEPE
(0 ~ 28 VDC)
2/4/6/10 mA x1, x10 Gain: 80 kHz
x100 Gain: 50 kHz
iSN-701-BALT-F15-L030
(1-axis)
2 ±10 VDC
 
 
SG-3000 Series
Model Input DO
Channel Signal Channel Type
SG-3784M 4 4 ~ 20 mA 4 PWM, Open Collector
tSG-3781B 1 4 ~ 20 mA 1 PWM, Open Collector
tSG-3781L 1 4 ~ 20 mA 1 PWM, Open Collector