~NEW~ |
|
|
|
|
|
|
|
|
|
|
|
|
|
The ZB-2000 series is a family of wireless Zigbee network data acquisition and control modules that support Modbus RTU and DCON protocols. With the Modbus RTU protocol, it can easily communicate with most popular SCADA/ HMI software and PLC. It has the same form factor as the I-7000 series. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
- ISM 2.4 GHz Operating Frequency
- Fully Compliant 2.4 G IEEE802.15.4/ZigBee Specifi cations
- Wireless Transmission Range up to 700 m (ZB-2550P/ZB-2570P)
- Wireless Transmission Range up to 100 m (ZB-2550/ZB-2570)
- GUI Configuration Software (Windows Version)
- 6 Digital Input & 4 Relay Ouutput
- Supports 16-bit Counters for Digital Inputs
- Surge and ESD Protection
- DIN-Rail Mount
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis, Testing Equipment. |
|
|
 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Digital Input |
Input Channel |
6 |
Input Type |
Isolated, Wet Contact (Sink/Source) |
Input level |
On Voltage Level: +3.5 VDC ~ +30 VDC |
Off Voltage Level: +1 VDC max. |
Input Impedance |
3 k£[, 0.33 W |
Counter |
Channels: 6 |
Max. Count: 16-bit (65535) |
Max. Input Frequency: 100 Hz |
Min. Pulse Width: 5 ms |
Relay Output |
Output Channels |
4 |
Output Type |
Power Relay, Form A |
Contact Rating |
5 A @ (250 VAC/30 VDC) |
Max. Contact voltage |
270 VAC/125 VDC |
Operate Time |
10 ms max. at rated voltage |
Release Time |
5 ms max. at rated voltage |
Endurance |
Electrically |
Resistive Load: 100,000 ops. min. (10 ops/minute) |
Mechanically |
At No Load: 20,000,000 ops. min. 300 ops/minute) |
Dielectric Strength |
Between Contacts |
750 VAC for 1 minute |
Between Coil to Contacts |
3,000 AC for 1 minute |
Insulation Resistance |
5,080 V (1.2/50 £gs) |
Surge Strength |
5 ms max. at rated voltage |
ESD Protection |
+/-4 kV (Contact for each channel) |
Communication Interface |
Wireless |
ZigBee, IEEE 802.15.4 Standard |
Antenna |
2.4 GHz-3 dBi Omni-Directional ante |
Protocols |
Supports DCON and Modbus RTU Protocols |
Hot Swap |
By Rotary and DIP switch |
LED Indicators |
Power |
1 LED, red |
ZigBee Communication |
1 LED, green |
Digital Input & Output |
10 LEDs, green |
Power |
Power Consumption |
1.2 W max. |
Mechanical |
Flammability |
Fire Retardant Materials (UL94-V0 Level) |
Dimensions (W x L x H) |
33 mm x 87 mm x 107 mm |
Installation |
DIN-Rail |
Environment |
Operating Temperature |
-25 ¢XC ~ +75 ¢XC |
Storage Temperature |
-30 ¢XC ~ +80 ¢XC |
Humidity |
10 ~ 90% RH, non-condensing |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RF channels |
16 |
Receive sensitivity |
-102 dBm |
Transmit power |
3.7 dBm |
Network Topology
support |
Star, Mesh and cluster tree |
Antenna (2.4 GHz) |
3 dBi Omni-Directional antenna |
Transmission range (LOS) |
100 m |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ZB-2060-T CR |
Wireless 6-ch Isolated Digital Input and 4-ch Relay Output Module (RoHS) |
Important Note : The ZigBee AIO modules need a ZB-2570 to coordinate the data transmission route, please remember to also order a ZB-2570 when you purchase the ZB DIO products. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|