CAN Bus
    CAN-2018C
 
 
 
 
 
    CAN Bus
 
 
    I-8000 Series
 
     

 
 
         
 
CAN-2018C
~ NEW ~
CANopen Slave Module of 8-channel Thermocouple Input
 
     
 
     
 

CAN-2018C module follows the DS-301 version 4.02 and DSP-401 version 2.1. You can access the thermocouple input status and set the configuration by using standard CANopen protocol. CAN-2018C has passed the validation of the CiA CANopen Conformance Test tool. Therefore, you can use it with standard CANopen master easily by applying the EDS file. CAN-2018C has 8-channel thermocouple input. It can be used to various applications. By owing to the CANopen masters of ICP DAS, you can quickly build a CANopen network to approach your requirements. For more information about the CANopen master interfaces and other CANopen products, please refer to the following web site.

http://www.icpdas.com/products/Remote_IO/can_bus/can_list.htm#2

 
     
 
 
 
     
 


 
     
 
 
   
 
CANopen Interface
NMT
Slave
Error Control
Node Guarding protocol / Heartbeat Producer
No. of PDOs
10Rx , 10Tx
PDO Modes
Event Triggered, Remotely requested, Cyclic and acyclic SYNC
PDO Mapping
Available
No. of SDOs
1 server, 0 client
Emergency Message
Yes
CANopen Version
DS-301 v4.02
Device Profile
DSP-401 v2.1
Specification
ISO-11898-2, CAN 2.0A and CAN 2.0B
Baud Rate (bps)
¡@Setting by Rotary Switch
10 k, 20 k, 50 k, 125 k, 250 k, 500 k, 800 k, and 1 M
Node ID
¡@Setting by Rotary Switch
1 ~ 99
Terminator Resistor
Switch for 120 £[ terminator resistor
Connector
5-pin screwed terminal block (CAN_GND, CAN_L, CAN_SHLD, CAN_H, CAN_V+)
EDS file
Yes
Analog Input
Channels
8
Input Type
+/- 15mV, +/- 50mV, +/- 100mV, +/- 500mV, +/- 1V, +/- 2.5V
+/-20mA,(Requires Optional External 125 Ohm Resistor)
Thermocouple (J, K, T, E, R, S, B, N, C)
Resolution
16-bit
Sampling Rate
10 Samples/Sec. (Total)
Accuracy
+/-0.1% FSR
Zero Drift
+/- 10 £gV/ ¢XC
Span Drift
+/- 25 ppm/ ¢XC
Common Mode Rejection
86 dB
Normal Mode Rejection
100 dB
Input Impedance
>400 k£[
Individual Channel Configuration
Yes
Open Thermocouple Detection
Yes
Over voltage Protection
240 Vrms
ESD Protection
+/-4kV, Contact for each terminal.
Intra-module Isolation, Field to Logic
3000 VDC
LED
Power
PWR, red
CANopen Status
RUN/ERR, green/orange
Power
Power Supply
Unregulated +10 ~ +30 VDC
Power Consumption
1.5 W
Mechanism
Installation
DIN-Rail
Dimensions
32.3 mm x 99 mm x 77.5 mm ( W x L x H )
Environment
Operating Temp.
-25 ~ 75 ¢J
Storage Temp.
-30 ~ 80 ¢J
Humidity
10 ~ 90% RH, non-condensing
   
 
 
 
     
 
Type Code
Temperature Range (¢XC)
J
-210 ¢XC ~ +1200 ¢XC
K
-270 ¢XC ~ +1372 ¢XC
T
-270 ¢XC ~ +400 ¢XC
E
-270 ¢XC ~ +1000 ¢XC
R
-50 ¢XC ~ +1765 ¢XC
S
-50 ¢XC ~ +1765 ¢XC
B
0 ¢XC ~ +1820 ¢XC
N
-270 ¢XC ~ +1300 ¢XC
C
0 ¢XC ~ +2320 ¢XC
 
     
 
 
 
     
 
CAN-2018C/S
CANopen Slave Module of 8-channel Thermocouple Input
Include CAN-2018C module and a CN-1824 daughter board
 
     
 
 
 
     
 
2-Port Isolated Protection CAN Communication Board
4-Port Isolated Protection CAN Communication Board
PCI Express CAN Communication Card
One Standalone Intelligent CAN Communication Card
One Standalone Intelligent CANopen Communication Card
USB/CANopen Master Converter Module
1 Port High Performance CANopen Master Slot Module
1 Port CANopen Master Slot Module
25pin Male-Female D-Sub 1.8M flat cable ( 180¢X)
 
     
   
Copyright© ICP DAS Co., Ltd. All Rights Reserved