CANopen is one kind of the network protocols based on the CAN bus and mainly used for embedded network of machine control, such as industrial machine control , aircraft engines monitoring, factory automation, medical equipments control, remote data acquisition, environmental monitoring, and packaging machines control, etc.
CAN-2084C module follows the CiA-301 version 4.02. CAN-2084C has passed the validation of the CiA CANopen conformance test tool. Therefore, you can use it with standard CANopen master easily by applying the EDS file. The CAN-2084C is a 4/8-channel Counter/Frequency module that provides “Up Counter”, "Frequency”, “Up/Down Counter”, “Dir/Pulse Counter” and “A/B Phase Counter” modes. It provides a variety of measurement applications, such as measuring a number of time-related quantities, counting events or totalizing and monitoring position with quadrature encoders. In addition, a digital filter is used to eliminate the effects of noise. By owing to the CANopen masters of ICP DAS, you can quickly build a CANopen network to approach your requirements. For more information about the CANopen master interfaces and other CANopen products, please refer to the following web site.
http://oldweb.icpdas.com/root/product/solutions/industrial_communication/fieldbus/canopen/canopen_selection_guide.html |
|
|
|
Applications |
|
|
|

|
|
|
|
Hardware Specifications |
|
|
|
CANopen Interface |
Connector |
5-pin screwed terminal block (CAN_GND, CAN_L, CAN_SHLD, CAN_H, CAN_V+) |
Baud Rate (bps) |
10 k, 20 k, 50 k, 125 k, 250 k, 500 k, 800 k, 1 M, selected by rotary switch |
Terminal Resistor |
DIP switch for the 120 Ω terminal resistor |
Protocol |
CANopen CiA 301 ver4.02, CiA 401 ver2.1 |
Node ID |
1~99 selected by rotary switch |
NMT |
Slave |
Error Control |
Node Guarding protocol / Heartbeat Producer |
SDOs |
1 server, 0 client |
PDOs |
10 RxPDO, 10 TxPDO (Supports dynamic PDO) |
PDO Modes |
Event-triggered, remotely-requested, synchronous (cyclic), synchronous (acyclic) |
Emergency Message |
Yes |
EDS file |
Yes |
Digital Input |
Channel |
4/8 |
Mode |
4-channel Up/Down Counter (Up/Down)
4-channel Dir/Pulse Counter (Bi-direction)
4-channel Quadrant Counting
8-channel Up Counter
8-channel Frequency
Programmable Digital Noise Filter: 1 to 32767 µs |
Isolated Input Level |
Logic Level 0: +1 V Max.
Logic Level 1: +4.5 to +30 V |
TTL Input Level |
Logic Level 0: 0 to +0.8 V
Logic Level 1: 2 to +5 V |
Minimum Pulse Width |
2μs |
Input Frequency |
1 Hz ~ (typically) 250 kHz for both counter and frequency mode, where 250 kHz is calculated as follows:
supposed that the duty cycle = 50%, by referring to the Minimum Pulse Duration of the High Level, the pulse period will be 2 μs x 2 = 4 μs, which is 250 kHz as a maximum.
Maximum Frequency:
Refer to the Minimum Pulse Duration of the High Level, the maximum frequency is highly affected by the duty cycle
Frequency Accuracy = ±0.4% |
EEPROM |
128KB |
Isolated Voltage |
1000Vrms |
Hardware |
ESD Protection |
2 kV (Contact for each Channel) |
LED |
CANopen Status |
3 LEDs to PWR, RUN and ERR |
Terminal Resister |
1 LED to terminal resister indicator |
Digital Input |
8 LEDs as Digital Input Indicators |
Power |
Power Supply |
Unregulated +10 ~ +30 VDC |
Power Consumption |
1.5 W |
Mechanism |
Dimensions |
33 mm x 99 mm x 78 mm ( W x L x H ) |
Environment |
Operating Temp. |
-25 ~ 75 ℃ |
Storage Temp. |
-30 ~ 80 ℃ |
Humidity |
10 ~ 90% RH, non-condensing |
|
|
|
|
Ordering Information |
|
|
|
|
4/8 channel Counter/Frequency CANopen Slave Module |
|
|
|
|
Related Products |
|
|
|
PISO-CAN200/200U |
2-Port Isolated Protection CAN Communication Board |
PISO-CAN400/400U |
4-Port Isolated Protection CAN Communication Board |
PISO-CM100U |
One Standalone Intelligent CAN Communication Card |
I-7565-CPM |
USB/CANopen Master Converter Module |
I-8123W |
1 Port High Performance CANopen Master Slot Module |
I-87123 |
1 Port CANopen Master Slot Module |
|
|
|
|
TOP |
|
|
|
|
|
|