CAN-2054C
 
Applications
Hardware Specifications
Ordering Information
Related Products
 
 
  • 繁體中文
  • English
  • CAN-2054C

    CANopen Slave Module of 8-Channel Isolated Digital Input and 8-Channel Isolated Digital Output

     

    CANopen is one kind of the network protocols based on the CAN bus and mainly used for embedded network of machine control, such as industrial machine control , aircraft engines monitoring, factory automation, medical equipment control, remote data acquisition, environmental monitoring, and packaging machines control, etc.

    CAN-2054C module follows the CiA DS-301 version 4.02 and DSP-401 version 2.1. You can access the digital I/O status and set the configuration by using standard CANopen protocol. CAN-2054C has passed the validation of the CiA CANopen conformance test tool. Therefore, you can use it with standard CANopen master easily by applying the EDS file. CAN-2054C has isolated sink/source input 8 channel and isolated sink output 8 channel, It can be used to various applications, such as PNP, NPN, TTL, relay contact and so forth. By owing to the CANopen masters of ICP DAS, you can quickly build a CANopen network to approach your requirements. For more information about the CANopen master interfaces and other CANopen products, please refer to the following web site.

    http://oldweb.icpdas.com/root/product/solutions/industrial_communication/fieldbus/fieldbus_selection_guide.html#2

     
     
    Applications  


     
     
    Hardware Specifications  
    CANopen Interface
    NMT
    Slave
    Error Control
    Node Guarding protocol or Heartbeat Producer
    No. of PDOs
    10Rx , 10Tx
    PDO Modes
    Event Triggered, Remotely requested, Cyclic and acyclic SYNC
    PDO Mapping
    Available
    No. of SDOs
    1 server, 0 client
    Emergency Message
    Yes
    CANopen Version
    DS-301 v4.02
    Device Profile
    DSP-401 v2.1
    Specification
    ISO 11898-2, CAN 2.0A
    Baud Rate (bps)
    Setting by Rotary Switch
    10 k, 20 k, 50 k, 125 k, 250 k, 500 k, 800 k, and 1 M
    Node ID
    Setting by Rotary Switch
    1 ~ 99
    Terminal Resistor
    Switch of 120 Ω terminal resistor
    Connector
    5-pin screwed terminal block (CAN_GND, CAN_L, CAN_SHLD, CAN_H, CAN_V+)
    EDS file
    Yes
    Digital Input
    Channels
    8 (Sink/Source)
    On Voltage Level
    +3.5 ~ +30 VDC
    Off Voltage Level
    +1 VDC Max.
    Input Impedance
    3 kΩ, 0.3 W
    Response Time
    250 us
    Intra-module Isolation
    3750 Vrms
    ESD Protection
    4 kV Contact for each channel
    Digital Output
    Channels
    8 (Sink)
    Load Voltage
    +5 ~ +30 VDC
    Output Max Load Current
    700 mA per channel
    Output Type
    Open-collector
    Reaction Time
    200 us
    Intra-module Isolation
    3750 Vrms
    ESD Protection
    4 kV Contact for each channel
    LED
    CANopen Status
    3 LEDs to PWR, RUN and ERR
    Terminal Resister
    1 LED to terminal resister indicators
    DI LED
    8 LEDs to digital input indicators
    DO LED
    8 LEDs to digital output indicators
    Power
    Power Supply
    Unregulated +10 ~ +30 VDC
    Power Consumption
    1.5 W
    Mechanism
    Installation
    DIN-Rail
    Dimensions
    32.3 mm x 99 mm x 77.5 mm ( W x L x H ) Detail
    Environment
    Operating Temp.
    -25 ~ +75 ℃
    Storage Temp.
    -30 ~ +80 ℃
    Humidity
    10 ~ 90% RH, non-condensing
     
     
    Ordering Information  
    CAN-2054C
    CANopen module of 8-channel DI and DO
     
     
    Related Products  
    PISO-CAN200/200U 2-Port Isolated Protection CAN Communication Board
    PISO-CAN400/400U 4-Port Isolated Protection CAN Communication Board
    PEX-CAN200i
    (PISO-CAN200E)
    PCI Express CAN Communication Card
    PISO-CM100U One Standalone Intelligent CAN Communication Card
    PISO-CPM100U One Standalone Intelligent CANopen Communication Card
    I-7565-CPM USB/CANopen Master Converter Module
    I-8123W 1 Port High Performance CANopen Master Slot Module
    I-87123 1 Port CANopen Master Slot Module
     
       
    TOP  
       
       

    這個頁面上的內容需要較新版本的 Adobe Flash Player。

    取得 Adobe Flash Player