home > product> solutions > industrial communication> Fieldbus > CANopen
 
CAN-2018C
 
Applications
Hardware Specifications
Thermocouple Type
Ordering Information
Related Products
 
 
  • 繁體中文
  • English
  • CAN-2018C

    CANopen Slave Module of 8-channel Thermocouple Input

     
     

    CAN-2018C module follows the DS-301 version 4.02 and DSP-401 version 2.1. You can access the thermocouple input status and set the configuration by using standard CANopen protocol. CAN-2018C has passed the validation of the CiA CANopen Conformance Test tool. Therefore, you can use it with standard CANopen master easily by applying the EDS file. CAN-2018C has 8-channel thermocouple input. It can be used to various applications. By owing to the CANopen masters of ICP DAS, you can quickly build a CANopen network to approach your requirements. For more information about the CANopen master interfaces and other CANopen products, please refer to the following web site, please refer to the following web site.

    http://oldweb.icpdas.com/root/product/solutions/industrial_communication/fieldbus/fieldbus_selection_guide.html#2.

     
     
    Applications  



     
     
    Hardware Specifications  
    CANopen Interface
    NMT
    Slave
    Error Control
    Node Guarding protocol / Heartbeat Producer
    No. of PDOs
    10Rx , 10Tx
    PDO Modes
    Event Triggered, Remotely requested, Cyclic and acyclic SYNC
    PDO Mapping
    Available
    No. of SDOs
    1 server, 0 client
    Emergency Message
    Yes
    CANopen Version
    DS-301 v4.02
    Device Profile
    DSP-401 v2.1
    Specification
    ISO-11898-2, CAN 2.0A
    Baud Rate (bps)
    Setting by Rotary Switch
    10 k, 20 k, 50 k, 125 k, 250 k, 500 k, 800 k, and 1 M
    Node ID
    Setting by Rotary Switch
    1 ~ 99
    Terminal Resistor
    Switch for 120 Ω terminal resistor
    Connector
    5-pin screwed terminal block (CAN_GND, CAN_L, CAN_SHLD, CAN_H, CAN_V+)
    EDS file
    Yes
    Analog Input
    Channels
    8
    Input Type
    +/- 15mV, +/- 50mV, +/- 100mV, +/- 500mV, +/- 1V, +/- 2.5V
    +/-20mA,(Requires Optional External 125 Ohm Resistor)
    Thermocouple (J, K, T, E, R, S, B, N, C)
    Resolution
    16-bit
    Sampling Rate
    10 Samples/Sec. (Total)
    Accuracy
    +/-0.1% FSR
    Zero Drift
    +/- 10 μV/ °C
    Span Drift
    +/- 25 ppm/ °C
    Common Mode Rejection
    86 dB
    Normal Mode Rejection
    100 dB
    Input Impedance
    >400 kΩ
    Individual Channel Configuration
    Yes
    Open Thermocouple Detection
    Yes
    Over voltage Protection
    240 Vrms
    ESD Protection
    +/-4kV, Contact for each terminal.
    Intra-module Isolation, Field to Logic
    3000 VDC
    LED
    Power
    PWR, red
    CANopen Status
    RUN/ERR, green/orange
    Power
    Power Supply
    Unregulated +10 ~ +30 VDC
    Power Consumption
    1.5 W
    Mechanism
    Installation
    DIN-Rail
    Dimensions
    32.3 mm x 99 mm x 77.5 mm ( W x L x H )
    Environment
    Operating Temp.
    -25 ~ 75 ℃
    Storage Temp.
    -30 ~ 80 ℃
    Humidity
    10 ~ 90% RH, non-condensing
     
     
    Thermocouple Type  
    Type Code
    Temperature Range (°C)
    J
    -210 °C ~ +1200 °C
    K
    -270 °C ~ +1372 °C
    T
    -270 °C ~ +400 °C
    E
    -270 °C ~ +1000 °C
    R
    -50 °C ~ +1765 °C
    S
    -50 °C ~ +1765 °C
    B
    0 °C ~ +1820 °C
    N
    -270 °C ~ +1300 °C
    C
    0 °C ~ +2320 °C
     
     
    Ordering Information  
    CAN-2018C/S
    CANopen Slave Module of 8-channel Thermocouple Input
    Include CAN-2018C module and a CN-1824 daughter board
     
     
    Related Products  
    PISO-CAN200/200U 2-Port Isolated Protection CAN Communication Board
    PISO-CAN400/400U 4-Port Isolated Protection CAN Communication Board
    PEX-CAN200i
    (PISO-CAN200E)
    PCI Express CAN Communication Card
    PISO-CM100U One Standalone Intelligent CAN Communication Card
    PISO-CPM100U One Standalone Intelligent CANopen Communication Card
    I-7565-CPM USB/CANopen Master Converter Module
    I-8123W 1 Port High Performance CANopen Master Slot Module
    I-87123 1 Port CANopen Master Slot Module
    CA-252518D 25pin Male-Female D-Sub 1.8M flat cable ( 180°)
     
       
    TOP  
       
       

    這個頁面上的內容需要較新版本的 Adobe Flash Player。

    取得 Adobe Flash Player