Model: I-8417/8817(-G) ; I-8437-80/8837-80(G)
  I-8x37-80, I-8x17
    I-8x37-80: Faster CPU (80 MHz) Ethernet ISaGRAF PAC
  I-8x17: 40 MHz ISaGRAF PAC
   
   
 
     
     
 
 
 
The I-8437-80/8837-80, I-8417/8817 is an ISaGRAF PAC and includes ISaGRAF SoftLogic, ISaGRAF is a Windows programming tools and also provides powerful debugging tools including On-line Motoring and Control and also Off-line Simulation. There are more than 300 function blocks built-in the PAC for various Industrial Applications including PID, motion, remote IO, serial communication, SMS, retain variable, scaling, etc.

In hardware, I-8xx7 has 3 or 4 serial ports, support Modbus RTU slave protocol and it can easily communicate with PC/HMI/OPC Server and Touch panel. The I-8xx7 also supports up to 2 COM ports of Modbus RTU / ASCII master protocol to integrate with other Modbus devices. The I-8x37-80 has one 10M Ethernet port.

The I-8xx7 supports various High/Low profile I/O modules. The user can choose Local I/O modules:I-8K/I-87K I/O modules and RS-485 Remote I/O modules:I-7000 or expansion units (I-87Kn or RU-87Pn) plugged with I-87K serial I/O modules. Compared to I-8437/8837 (It has phased out), I-8x37-80 is 2 ~ 4 times faster!
 
     
     
 
 
MiniOS7 Embedded Operating System (DOS-like)
ISaGRAF Ver.3 SoftLogic Inside
Support IEC 61131-3 Standard
Accepts max. 64 KB ISaGRAF code size
 
 
     
     
 
 
80186 CPU (16-bit & 80 MHz) (for I-8x37-80)
80188 CPU (16-bit & 40 MHz) (for I-8x17)
512 KB SRAM & 512 KB Flash
4/8 I/O Expansion Slots (support High/Low Profile I/O Modules)
10M Ethernet Port (for I-8x37-80)
3 or 4 Serial Ports (RS-232, RS-485)
 
 
     
 
Top
 
     
 
 
 
ISaGRAF PAC connects the Smart Meter Stress Monitoring Application of Constructions ZigBee Wireless Solution
 
 
Data Acquisition Auto-Report System Motion Control
Modbus RTU/TCP Slave Ports Data Recorder and Data Logger
Modbus RTU/ASCII Master Ports Data Exchange: Fbus or Ebus
Remote I/O Modules and Expansion module/board Detect Hot-Swap I-87K (High Profile) I/O Status
SMS: Short Message Service VIP Communication Security
   
   
for "Applications Supporting List" & all applications
 
 
     
 
Top
 
     
Spec
 
 
System Software
OS MiniOS7
Development Software
ISaGRAF Version 3 IEC 61131-3 standard. Languages: LD, ST, FBD, SFC, IL & FC
Max. Code Size Accepts max. 64 KB ISaGRAF code size (Appli.x8m must < 64 KB)
Power Supply
Input Range +10 ~ +30 VDC, 20 W (when I/O slots are empty)
Protection Power reverse polarity protection
General Environment
Temperature Operating: -25 ~ +75 °C,
Storage : -30 ~ +80 °C
Humidity 10 ~ 90 % RH (non-condensing )
System
CPU I-8417/8817/8437/8837: 80188, 40 MHz or compatible
I-8437-80/8837-80: 80186, 80 MHz or compatible
Watchdog Timer Yes
RTC (Real Time Clock) Provide second, minute, hour, date, day of week, month, year
SRAM 512 KB
FLASH Memory 512 KB, Erase unit is 64 KB, 100,000 erase/write cycles
NVRAM 31 bytes, battery backup, data valid up to 10 years
EEPROM 2048 bytes, retention > 100 years. 1,000,000 erase/write cycles
SMMI 5-Digit 7-Seg. LED, four push buttons & three LED on the front panel. It can display message, value, simulate input & output.
NET ID 8-pin DIP switch to set NET ID as 1 ~ 255
Communication Interface
COM1 RS-232: TxD, RxD, GND, Speed: 115200 bps max. Programs download port.
COM2 (for I-8417/8817) RS-485: D+, D-, 115200 bps max. Self-tuner ASIC inside, Programs download port.
Ethernet (for I-8x37-80) 10 Mbps, NE2000 compatible, 10 Base-T, Programs download port.
COM3 It can be configured as RS-232 or RS-485, Speed: 115200 bps max.
RS-232: TxD, RxD, RTS, CTS, GND, RS-485: DATA+, DATA-
COM4 RS-232: Full modem signals, 115200 bps max.
TxD, RxD, RTS, CTS, DSR, DTR, CD, RI, GND.
I/O Expansion Slots
Slot Number I-84x7: 4 Slots
I-88x7: 8 Slots
Accept I-8K Series (parallel) & I-87K Series (serial) I/O boards.
Mechanical
Dimensions I-84x7: 230 mm x 110 mm x 75.5 mm
I-88x7: 354 mm x 110 mm x 75.5 mm
Motion
Motion Control I-8417/8817/8437-80/8837-80 can integrate with one I-8091 (2-axis) or two I-8091 (4-axis) to do motion control. When doing motion control, I-8437-80/8837-80's Ethernet communication is not available. (Please update to motion driver to support it.)
PWM Output
Pulse Width Modulation
Output
8-ch max. for one controller. 500 HZ max. for Off = 1 & On = 1 ms
Output square wave: Off: 1 ~ 32767 ms, On: 1 ~ 32767 ms
Optional DO boards: I-8037, 8041, 8042, 8054, 8055, 8056, 8057,8060, 8063, 8064, 8065, 8066, 8068, 8069. (Relay Output boards cannot generate fast square wave )
Counters
Parallel DI Counter 8-ch. max. for 1 controller. Counter value: 32-bit. 500 HZ max. Min. pulse width > 1 ms
Optional DI boards: I-8040, 8042, 8051, 8052, 8053, 8054, 8055, 8058, 8063, 8077
Serial DI Counter Counter input: 100 Hz max. Counter value: 0 ~ 65535 (16-bit)
Optional serial I-87k DI boards: I-87040, 87051, 87052, 87053, 87054, 87055, 87058, 87063
Remote DI Counter All remote I-7000 & I-87K DI modules support counters. 100Hz max. value: 0 ~ 65535
High Speed Counter I-87082: 100 kHz max. 32-bit, I-8080:450 kHz max. 32-bit
Protocols
Modbus RTU/ASCII Master
Protocol
Up to 2 COM Ports, COM1 or COM3 or COM4 ( or COM5 if multi-serial port boards are plugged) supports Modbus Master protocol to connect to other Modbus Slave devices.
Modbus RTU Slave
Protocol
Up to 2 COM Ports, COM1/3 for I-8x37-80 (& COM1/2 for I-8417/8817) default supports Modbus RTU Slave protocol for connecting ISaGRAF, PC/HMI/OPC Server & MMI panels.
Modbus TCP/IP Slave
Protocol (for I-8x37-80)
Ethernet port support Modbus TCP/IP Slave protocol for connecting ISaGRAF & PC/HMI.
Remote I/O One of COM3 or COM4 supports I-7000 I/O modules & (I-87K base + I-87K serial I/O boards or
RU-87P1/2/4/8 + I-87K High Profile I/O cards) as Remote I/O. Max. 64 Remote I/O module for one controller.
Fbus Built-in COM3 Port to exchange data between ICP DAS's ISaGRAF PACs.
Ebus (for I-8x37-80) To exchange data between ICP DAS's ISaGRAF Ethernet PACs via Ethernet port.
SMS:
Short Message Service
One of COM4 or COM5 can link to a GSM modem to support SMS. User can request data/controller by cellular phone. The controller can also send data & alarms to user's cellular phone.
Optional GSM modems: GTM-201-RS232 (850/900/1800/1900 GSM/GPRS External Modem).
User-defined Protocol User can write his own protocol applied at COM1, COM3, COM4 (& COM5 ~ COM20 if multi-serial port boards are plugged) by serial communication function blocks.
Modem Link Supports PC to remotely download & monitor the controller through a normal modem.
MMICON/LCD One of COM3 or COM4 supports ICP DAS's MMICON. The is featured with a 240x 64 dot LCD and a
4 x 4 Keyboard. User can use it to display picture, string, integer, float, and input a character, string, integer and float.
Redundant Bus7000 Two ISaGRAF PACs can link to remote I-7000 & I-87K I/O modules at the same time. Only one controller is active to control these Remote I/Os. If one is dead, the other one will take over the control of Remote I/Os.
Battery Backup SRAM
I-8417/8817/8437-80/8837-80 can support up to 1024 retain variables with a S256/S512 plug in the socket of the back-plane. Data can also be stored in the S256/S512, and then PC can load these data via COM1 (or COM2 of I-8417/8817, or Ethernet of I-8437-80/8837-80). PC can also download pre-defined data to the S256/S512. Optional: S256: 256 KB, S512: 512 KB.
 
     
 
Top
 
     
 
 
I-8437-80 CR (blue) 4 slots Faster CPU (80 MHz) Ethernet ISaGRAF PAC (RoHS)
80186, 80 MHz, 10 Base-T
I-8437-80G CR (gray)
I-8837-80 CR (blue) 8 slots Faster CPU (80 MHz) Ethernet ISaGRAF PAC (RoHS)
80186, 80 MHz, 10 Base-T
I-8837-80G CR (gray)
I-8417 CR (blue) 4 slots ISaGRAF PAC (RoHS)
80188, 40 MHz
I-8417-G CR (gray)
I-8817 CR (blue) 8 slots ISaGRAF PAC (RoHS)
80188, 40 MHz
I-8817-G CR (gray)
 
     
     
 
     