I-87069W/I-87069PW
8-channel PhotoMOS Relay Output Module
 
                 ~ NEW ~  
  • 8 PhotoMos Relay Outputs
  • 4 kV ESD Protection
  • No Arcing, No Bounce, and No Switching Noise
  • Photocouple Isolation
  • Embedded Dual Watchdog
  • Configurable Power-on Value Settings
  • Configurable Safe Value Settings
  • Wide Operating Temperature Range: -25 ~ +75 °C
 
Model: I-87069W Model: I-87069PW  
 
Both the I-87069W and the I-87069PW features eight Form A PhotoMOS relay output channels. In comparison to electromechanical relays, the PhotoMOS relays provide a faster response time, greater electrical endurance, higher vibration and shock resistance. There are also no arcing, no bounce, and no switching noise for the PhotoMOS relay. There are options for configuring power-on and safe digital output values, and both the I-87069W and the I-87069PW each include eight LED indicators that are used to display channel status as well as providing 4 kV ESD protection.
 
  • All Types of On/Off Control
  • Industrial Automation
  • Industrial Machinery
  • Building Automation
  • Food and Beverage Systems
  • Semiconductor Fabrication
  • Control Systems
 
Models I-87069W I-87069PW
PhotoMOS Relay Output
Output Channels 8
Relay Type PhotoMOS Relay, Form A
Operating Load Voltage Range 350 V (AC peck or DC) 80 V (AC peck or DC)
Countinous Load Current 0.13 A 1 A
Peak Load Current 0.4 A 3 A
Output Off State Leakage Current 1 μA
Operating Time 2 ms (Max.) 5 ms (Max.)
Release Time 1 ms (Max.) 0.5 ms (Max.)
Electrical Endurance No Arcing, No Bounce, and No Switching Noise
Power-on Value Yes, Programmable
Safe Value Yes, Programmable
 
Models I-87069W I-87069PW
Communication
Interface RS-485
Format (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1)
Baud Rate 1200 ~ 115200 bps
Protocol DCON
Watchdog
Dual Watchdog Yes, Module (1.6 seconds), Communication (Programmable)
LED Indicators
1 LED as Power Indicator
8 LEDs as PhotoMOS Output Indicators
Isolation
Intra-module Isolation, Field-to-Logic 5000 VDC 2000 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal
±8 kV Air for Random Point
EFT (IEC 61000-4-4) ±4 kV for Power
Power
Power Consumption 0.3 W (Max.)
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +75 °C
Humidity 10 ~ 95% RH, Non-condensing
Dimensions
30 mm x 102 mm x 115 mm (W x L x H)
 
I-87069W-G CR 8-channel PhotoMOS Relay Output Module (RoHS)
I-87069PW-G CR 8-channel PhotoMOS Relay Output Module (RoHS)
 
Converters USB, RS-232, Fiber Optical to RS-485 Converters and Repeaters
Power Supply 24 VDC Power Supply
Relay Module External Relay Modules for 87k DO Modules