這個頁面上的內容需要較新版本的 Adobe Flash Player。

取得 Adobe Flash Player

home > product> solutions > remote i/o modules/units > I-8K & I-87K > I-87019ZW
 
I-87019ZW
10-channel Universal Analog Input Module with High Overvoltage Protection
 
 
~ NEW ~    
  • 10-channel Analog Input
  • Individual Channel Configuration
  • Open Thermocouple Detection
  • Temperature Output Consistency
  • Stable Temperature Output in the Field
  • 240 Vrms Overvoltage Protection
  • Jumper Selectable Voltage or Current Input
  • 4 kV ESD Protection
  • Dual Watchdog
  • 3000 VDC Intra-module Isolation, Field-to-Logic
  • Wide Operating Temperature Range: -25 °C ~ +75 °C
  • RoHS Compliant
   
Model: I-87019ZW    
 
The I-87019ZW is a 10-channel universal analog input module with an RS-485 interface that is a specially designed for extremely accurate thermocouple measurement and features automatic cold-junction compensation for each channel to ensure temperature output consistency and stable temperature output in the field. The innovative design of the enhanced model ensures that thermocouple measurement is more accurate than with the earlier design. Besides the thermocouple inputs, the I-87019ZW also supports voltage and current inputs. The voltage input range can be form +/-15 mV to +/-10 V, and the current input range can be either 4 ~ 20 mA, 0 ~ 20 mA, or +/- 20 mA. Up to 10 analog inputs of different types can be connected to a single module. Overvoltage protection of up to 240 Vrms is provided. The module also features per-channel open wire detection for thermocouple and 4 ~ 20 mA inputs.
 
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment.
 
Analog Input
Input Channels 10 Differential
Input Type +/-15 mV, +/-50 mV, +/-100 mV, +/-150 mV
+/-500 mV, +/-1 V, +/-2.5 V, +/-5 V,+/-10 V
-20 mA ~ +20 mA, 0 ~ 20 mA, 4 ~ 20 mA (Jumper Selectable)
Thermocouple Type: (J, K, T, E. R. S, B, N, C, L, M, and LDIN43710)
Resolution 16-bit
Sampling Rate 10 Samples/Second (Total)
Accuracy +/- 0.1%
Zero Drift +/- 20 μV/°C
Span Drift +/- 25 ppm/°C
Common Mode Rejection 86 dB
Normal Mode Rejection 100 dB
Input Impedance Voltage Input: >400 k[, Current Input: 125 Ω
Individual Channel Configuration Yes
Overvoltage Protection 240 Vrms
Open Thermocouple Detection Yes, (Software Selectable)
ESD Protection +/- 4 kV, Contact for Each Terminal
Intra-module Isolation, Field-to-Logic 3000 VDC
 
Interface
Interface RS-485
Format N, 8, 1; N, 8, 2; E, 8, 1; O, 8, 1
Baud Rate 1200 ~ 115200 bps
Watchdog
Dual Watchdog Yes, Module (1.6 seconds) and Communication (Programable)
LED Display
1 LED as Power/Communication Indicator
Power
Power Consumption Maximum : 1.4 W
Environment
Operating Temperature -25 °C ~ +75 °C
Storage Temperature -40 °C ~ +85 °C
Humidity 10 ~ 90% RH, Non-condensing
Dimensions
I-87019ZW 30 mm x 86 mm x 114 mm (W x L x H)
DB-1820 22 mm x 78 mm x 65 mm (W x L X H)
DN-1822 27 mm x 96 mm x 103 mm (W x L x H)
 
Type Code
Type
Temperature Range °C
0E
J
-210 ~ +760
0F
K
-270 ~ +1372
10
T
-270 ~ +400
11
E
-270 ~ +1000
12
R
0 ~ +1768
13
S
0 ~ +1768
14
B
0 ~ +1820
15
N
-270 ~ +1300
16
C
0 ~ +2320
17
L
-200 ~ +800
18
M
-200 ~ +100
19
LDIN43710
-200 ~ +900
 
I-87019ZW-G/S CR 10-channel Universal Analog Input Module (Gray Cover) (RoHS), Includes the I-87019ZW Module and a DB-1820 Daughter Board
I-87019ZW-G/S2 CR 10-channel Universal Analog Input Module (Gray Cover) (RoHS), Includes the I-87019ZW Module, a DN-1822 Daughter Board and a 1.8 m Cable
   
I-87019ZW-G/S CR = I-87019ZW Connects DB-1820 Directly
I-87019ZW-G/S2 CR = I-87019ZW Connect DN-1822 Directly
 
CD-2518D 25F-25M 1.8m cable with DIN-Rail Mounting for the DB-1820 (RoHs)
 
Converters USB, RS-232, Fiber Optical to RS-485 Converters and Repeaters
Power Supply 24 VDC Power Supply
Relay Module External Relay Modules for 87000 DO Modules
Application Books Application Books Designed for Our Products
Data Logger Software User Friendly Data Logger Software (free)
 
TOP | HOME
 

這個頁面上的內容需要較新版本的 Adobe Flash Player。