home > product> solutions > pac > I/O Expansion Unit > ET-87P4-MTCP/ET-87P8-MTCP
 
ET-87P4-MTCP/ET-87P8-MTCP
ET-8KP4-MTCP/ET-8KP8-MTCP
 
 
~ NEW ~ ~ NEW ~
Model: ET-87P4-MTCP
Model: ET-87P8-MTCP
~ Available soon ~ ~ NEW ~
Model: ET-8KP4-MTCP
Model: ET-8KP8-MTCP
 
  • Two Ethernet Ports for Daisy-Chain Topology
  • Supports Modbus TCP
  • Supports Modbus RTU/ASCII
  • Supports Modbus TCP to RTU Gateway
  • Auto Configuration
  • 4/8 I/O Slots for I-87K Series Modules (ET-87P4-MTCP/ET-87P8-MTCP)
  • 4/8 I/O Slots for I-87K/I-8K Series Modules (ET-8KP4-MTCP/ET-8KP8-MTCP)
  • Operating Temperature: -25 ~ +75 °C
 
ET-87Pn-MTCP series is a Modbus TCP I/O expansion unit to expand I-87K series I/O modules over the Ethernet for industrial monitoring and controlling applications. It offers two Ethernet switch ports for daisy-chain topology. The daisy-chain feature allows ET-87Pn to connect in series to each other or other Ethernet devices. Users can easily simplify the cabling and save installation space with the feature.

It is designed to be used in harsh and noisy environment, so the hardware is manufactured with wide power input range (10 ~ 30 VDC), isolated power input and can operate under wide temperature (-25 ~ +75°C). There are more than 50 I/O modules supported with the unit, including analog input/output, digital input/output, DI counter modules. To simplify installation and maintenance of I/O modules, it provides many useful features, such as: auto configuration, LED indicators for fault detection, dual watchdog to keep alive, programmable power on and safe values for safety.

Modbus is a very wide known protocol in the industrial manufacturing and environment monitoring fields. Many SCADA software, HMI and PLC has builtin driver to support Modbus devices. Besides, we also provide SDK on different platforms, such as Windows XP, Window CE 5.0/6.0, Linux, MiniOS7. Therefore, it is very easy to integrate remote I/O to customer’s applications.
 
Daiy Chain ethernet cabling pic of ET-87Pn-MTCP, ET-8KPn-MTCP
 
Models ET-87P4-MTCP ET-87P8-MTCP ET-8KP4-MTCP ET-8KP8-MTCP
Communication Ports
Protocol Modbus TCP Slave
Modbus RTU/ASCII Slave
Modbus TCP to RTU Gateway
Ethernet RJ-45 x 2, 10/100 Base-TX (Auto negotiating, Auto MDI/MDI-X, LED indicators)
COM 1 RS-232 (to update firmware) (RxD, TxD and GND); non-isolated
SMMI
LED Display Yes, 5-Digit LED Display
Push Buttons 4
I/O Expansion Slots
Slot Number 4 8 4 8
Note: For High Profile I-87K Modules Only For High Profile I-87K/I-8K Modules
Hot Swap Yes No
Mechanical
Dimensions (W x L x H) 188 mm x 132 mm x 111 mm 312 mm x 132 mm x 111 mm 188 mm x 132 mm x 111 mm 312 mm x 132 mm x 111 mm
Installation DIN-Rail or Wall Mounting
Environmental
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +75 °C
Ambient Relative Humidity 10 ~ 90% RH (non-condensing)
Power
Input Range +10 ~ +30 VDC
Isolation 1 kV
Redundant Power Inputs Yes
Capacity 30 W
Consumption 2 W 2.4 W 2 W 2.4 W
 
ET-87P4-MTCP 4 slots I/O Expansion Unit with Modbus TCP protocol
ET-87P8-MTCP 8 slots I/O Expansion Unit with Modbus TCP protocol
ET-8KP4-MTCP 4 slots I/O Expansion Unit with Modbus TCP protocol
ET-8KP8-MTCP 8 slots I/O Expansion Unit with Modbus TCP protocol
 
DP-660 24 VDC/2.5 A, 60 W and 5 VDC/0.5 A, 2.5 W Power Supply with DIN-Rail Mounting
DP-665 24 VDC/2.7 A, 65 W Power Supply with DIN-Rail Mounting
 
TOP | HOME
 