Model: I-7017R
I-7017R
8-channel Analog Input Module with High Voltage Protection
 
   
 
     
 
 
 
Analog Input
Input Channels 8 differential
Input Type +/-500mV, +/-1V, +/-5V, +/-10V
+/-20mA (requires optional external 125ohm  resistor)
Resolution 16-bit (Normal Mode) / 12-bit (Fast Mode)
Sampling Rate 10 samples/ second (Normal Mode) / 60 samples/ second (Fast Mode) total 
Accuracy +/-0.1% (Normal Mode) / +/-0.5% (Fast Mode) or better
Band Width 15.7Hz (Normal Mode) / 78.7Hz (Fast Mode)
Zero drift +/-20uV/¢XC
Span drift +/-25ppm/¢XC
Input Impedance 2M Ohms
Common Mode Rejection 86dB min.
Normal Mode Rejection 100dB
Over Voltage Protection 240 Vrms
4KV ESD Protection Yes, Contact for each terminal.
Intra-module Isolation, Field to Logic 3000 VDC
Interface
Interface RS-485
Format N, 8, 1 (details)
Baud Rate 1200 ~ 115200bps
LED Display
1 LED as Power/Communication indicator
Power
Input +10 to +30 Vdc
Power Consumption 1.3W
Environment
Operating temperature -25 to 75¢XC
Storage temperature -40 to 85¢XC
Humidity 5 to 95% RH, non-condensing
 
     
  back  
     
 
 
 
I-7017R    8-channel Analog Input Module with High Voltage Protection
I-7017R CR    8-channel Analog Input Module with High Voltage Protection (RoHS)
 
     
  back  
     
 
 
 
DN-800    The daughter board can be measured high voltage(+/-80 VDC, +/-150 VDC, +/-600 VDC)
   and high current(+/-1A, +/-50A).
SG-770    7-channel Surge Protector
tM-SG4    The RS-485 Pull-high/Pull-low and Termination Resistors Module
Converters    USB, RS-232, Fiber Optical to RS-485 Converters and Repeaters
Power Supply    24V DC power supply
Relay Module    External relay modules for I-7000 DO module
Learning Kit    Learning kit
Application Books    Application books designed with our products
Data Logger Software    User friendly data logger software (free)
125Ohms, 0.1% DIP Resistors    use for current type of I-7011/I-7012/I-7017/I-7018 series
 
   
  back  
Copyright© ICP DAS Co., Ltd. All Rights Reserved