Isolation Voltage : 3000V DC
Communication :

  • Asynchronous half-duplex 2-wire RS-485 network
  • Max. distance without repeater=4000 feet(1.2Km)
  • Speed=1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
  • A maximum of 256 Modules can be connected in a single RS-485 bus without using a repeater
  • Multiple baud rates and multiple data formats can share the same RS-485 bus(I-7520/7510)
  • Different baud rates and the same module address can share the same RS-485 bus
  • Connecting 256*8=2048 modules max. in one RS-485 bus with repeater.
  • I-7000 series data format = 1 start + 8 data + 1 stop + no parity = 10-bit
  • Two extra checksum bytes can be enabled/disabled
  • Built-in transient voltage suppresser and PTC protector
  • Sharing the same RS-485 bus with a RS-485 or RS-232 device that communicates in multiple data format
    not 10-bit) and multiple baud rate. (Use I-7520 to convert from RS-232 to RS-485)

Power :

  • +10V ~ +30V DC
  • Power reverse protection, over-voltage brown-out protection

System :

  • Internal daul watchdog , power-on start value and safe value for host failure
  • Operating temperature : -25 to 75¢J
  • Storage temperature : -40 to 85¢J
  • Humidity : 5 to 95%, non-condensing
 
 


 