~NEW~
 
Model: ET-7060
ET-7060
6-channel Power Relay Output and 6-channel Isolation Digital Input
 
         












 

 
 
 
 

The ET-7060, a web-based Ethernet I/O module, features a built-in web server, which allows configuration, I/O monitoring and I/O control by simply using a regular web browser. Besides, with the web HMI function, no more programming or HTML skills are needed; creating dynamic and attractive web pages for I/O monitoring and I/O control would be fun to engineers ever after. The ET-7060 offers easily and safely access for users from anytime and anywhere! In addition, the ET-7060 also supports Modbus/TCP protocol that makes perfect integration for ET-7060 to SCADA software.

The ET-7060 provides 6 power relay (form A) output and 6 isolated wet contact (sink, source type) digital input channels. Each power relay supports contact rating as 5A@250Vac or 5A@30Vdc and each digital input channel supports counter input (32 bits and 500Hz max.).more...

 
     
  back  
     
 
 
 
CPU
CPU 80186 CPU (80MHz)
SRAM 512K Bytes
Flash Memory 512K Bytes
EEPROM 16K Bytes
Dual Watchdog Yes
Communication
Ethernet Port 10 / 100 Base TX (With Link, Activity LED Indicator)
Automatic MDI/MDI-X Crossover
Relay Output
Output Channels 6
Output Type Power Relay, Form A (SPST N.O.)
Operating Voltage Range

250 Vac / 30Vdc

Max. Load Current 5.0A/channel at 25 ¢XC
Operate Time 6ms
Release Time 3ms
Electrical Life ( Resistive load ) VDE: 5A 250Vac 30,000 ops (10 ops/minute) at 75¢XC.
  5A 30Vdc 70,000 ops (10 ops/minute) at 75¢XC.
UL: 5A 250Vac/30Vdc 6,000 ops.
  3A 250Vac/30Vdc 100,000 ops.
Mechanical Life 20,000,000 ops. at no load (300 ops./minute).
Digital Input
Input Channels 6
Input Type Wet Contact (Sink, Source)
On Voltage Level +10Vdc to 50Vdc
Off Voltage Level +4Vdc max.
Input Impedance 10K Ohms
Counters Max. Count: 4,294,967,285 (32 bits)
Max. Input Frequency : 500Hz
Min. Pulse Width: 1 ms
Over-Voltage Protection +70Vdc
2 Way Isolation
Ethernet 1500 Vrms
I/O DI 3750 Vrms
Relay Output 3000 Vrms
Mounting
Din Rail Mount Yes
Wall Mount Yes
Power Requirements
Protection Power reverse polarity protection
Required Supply Voltage +10Vdc to 30Vdc (non-regulated)
LED Indicator Yes
Power Consumption 0.12A/24Vdc Max.
Environment
Operating Temperature -25 ~ +75 ¢XC
Storage Temperature -30 ~ +80 ¢XC
Relative Humidity 5% to 90% Non-condensing
Certification CE, FCC
Dimensions
Dimensions( W x H x D) 123 mm x 72 mm x 33 mm
 
     
  back  
     
 
 
 
ET-7060 CR     6-channel Power Relay Output and 6-channel Isolation Digital Input (RoHS)
 
     
  back  
     
 
 
 
GPSU06U-6     24V/0.25A output power supply
MDR-20-24     24V/1A output power supply with DIN-Rail
NS-205 CR     Unmanaged 5-Port Industrial Ethernet Switch
 
     
  back  
     
Copyright© ICP DAS Co., Ltd. All Rights Reserved