CAN Bus
    I-7532
 
 
 
 
 
    CAN Bus
 
 
    I-7000 Series
 
     

 
 
       
 


I-7532 ~ NEW ~
Two-channel CAN Bus Isolated Bridge

 
     
 

I-7532 is a local CAN bridge used to establish a connection between two CAN bus system in a CAN network.The I-7532 stands by itself connecting adjacent wiring segments together as in the case of a CAN repeater (I-7531).Not just like I-7531, I-7532 have three more important features. First one, the transmission distance limitation of the CAN bus system on each side of I-7532 are independent, which means the total network distance can be extended.

 
 
Second one, when the CAN bus system on one side of I-7532 happpens some error (e.g. bit error), the system on other side can still work on correctly. Last one, the baud of two channel on I-7532 can be different for highly flexibility.
 
     
 
 
 
     
 
• Control System• Building Automation• Factory Automation• Distributed data acquisition
 
     
 
 
 
     
 
  • Microprocessor inside with 72MHz
  • 82C250 CAN transceiver
  • 2500 VRMS photo coupler isolation on the CAN side
  • 3KV galvanic isolation among the power supply and 2 CAN channels
  • Support both CAN 2.0A and CAN 2.0B
  • Fully compatible with the ISO 11898-2 standard
  • Build-in jumper to select 120£[ terminal resistor
  • Watchdog inside
  • Up to 100 CAN nodes on each channel
  • Transmission distance up to 1 km on each CAN port
  • Removable terminal block, Mount easily on DIN-rail
  • 768 frame buffer for each CAN channel
  • The baud of each channel can be different for highly flexibility
 
     
 
 
 
     
 
Switch Value
0
1
2
3
Baud [bps]
N/A
5k
10k
20k
Switch Value
4
5
6
7
Baud [bps]
40k
50k
80k
100k
Switch Value
8
9
A
B
Baud [bps]
125k
200k
250k
400k
Switch Value
C
D
E
F
Baud [bps]
500k
600k
800k
1000k
 
     
 
 
 
     
 
CAN Interface
Controller
Microprocessor inside with 20MHz
Transceiver
NXP 82C250
Channel number
2
Connector
4-pin screwed terminal block (CAN_GND, CAN_L, CAN_SHLD, CAN_H)
Baud Rate (bps)
5 k, 10 k, 20 k, 50 k, 80 k, 100 k, 125 k, 200 k, 250 k, 400 k, 500 k, 600 k, 800 k, 1 M
Isolation
3000 VDC for DC-to-DC, 2500 Vrms for photo-couple
Terminator Resistor
Jumper for 120 £[ terminator resistor
Specification
ISO-11898-2, CAN 2.0A and CAN 2.0B
Power
Power supply
Unregulated +10 ~ +30 VDC
Protection
Power reverse polarity protection, Over-voltage brown-out protection
Power Consumption
2 W
Mechanism
Installation
DIN-Rail
Dimensions
72mm x 33mm x 122mm (W x L x H)
Environment
Operating Temp.
-25 ~ 75 ¢J
Storage Temp.
-40 ~ 80 ¢J
Humidity
5 ~ 95% RH, non-condensing
 
     
 
 
 
     
 
I-7532-G CR
Two-channel CAN Bus Isolated Bridge (RoHS)
 
     
   
Copyright© ICP DAS Co., Ltd. All Rights Reserved