CAN Bus
    CAN-2055C
 
 
 
 
    CAN Bus
 
 
    I-8000 Series
 
     

 
 
         
 
CAN-2055C ~ NEW ~

CANopen Slave Module of 8-channel Isolated Digital Input and 8-channel Isolated Digital Output
 
   
 
     
 

CANopen is one kind of the network protocols based on the CAN bus and mainly used for embedded network of machine control, such as industrial machine control , aircraft engines monitoring, factory automation, medical equipments control, remote data acquisition, environmental monitoring, and packaging machines control, etc.

CAN-2055C module follows the CiA-301 version 4.02 and CiA-401 version 2.1. You can access the digital I/O status and set the configuration by using standard CANopen protocol. CAN-2055C has passed the validation of the CiA CANopen conformance test tool. Therefore, you can use it with standard CANopen master easily by applying the EDS file. CAN-2055C has 8 isolated sink/source input channels and 8 isolated source output channesl, It can be used to various applications, such as PNP, NPN, TTL, relay contact and so forth. By owing to the CANopen masters of ICP DAS, you can quickly build a CANopen network to approach your requirements. For more information about the CANopen master interfaces and other CANopen products, please refer to the following web site.

http://www.icpdas.com/products/Remote_IO/can_bus/can_list.htm#2

 
     
 
 
 
     
 



 
     
 
 
   
 
CANopen Interface
Connector 5-pin screwed terminal block (CAN_GND, CAN_L, CAN_SHLD, CAN_H, CAN_V+)
Baud Rate (bps) 10 k, 20 k, 50 k, 125 k, 250 k, 500 k, 800 k, 1 M, selected by rotary switch
Terminator Resistor DIP switch for the 120 £[ terminator resistor
Protocol CANopen CiA 301 ver4.02, CiA 401 ver2.1
Node ID 1~99 selected by rotary switch
NMT Slave
Error Control Node Guarding protocol / Heartbeat Producer
SDOs 1 server, 0 client
PDOs 10 RxPDO, 10 TxPDO (Supports dynamic PDO)
PDO Modes Event-triggered, remotely-requested, synchronous (cyclic), synchronous (acyclic)
Emergency Message Yes
EDS file Yes
Digital Input
Channels 8 (Sink/Source)
On Voltage Level 3.5 ~ 30 VDC
Off Voltage Level +1 VDC Max
Input Impedance 3k£[, 0.3W
Response Time 250 us
Intra-module Isolation 3750 Vrms
ESD Protection 4kV for each channel
Digital Output
Channels 8 (Source)
Load Voltage 10 ~ 30 VDC
Output Max. Load Current 700mA, each channel
Output Type Open emitter
Reaction Time 200 us
Intra-module Isolation 3750 Vrms
ESD Protection 4kV Contact for each channel
LED
CANopen Status 3 LEDs to PWR, RUN and ERR
Terminal Resister 1 LED to terminal resister indicator
DI LED 8 LEDs to digital input indicator
DO LED 8 LEDs to digital output indicator
Power
Power Supply Unregulated +10 ~ +30 VDC
Power Consumption 1.7 W
Mechanism
Installation DIN-Rail
Dimensions 33 mm x 99 mm x 78 mm ( W x L x H )
Environment
Operating Temp. -25 ~ 75 ¢J
Storage Temp. -30 ~ 80 ¢J
Humidity 10 ~ 90% RH, non-condensing
   
 
 
 
     
 
CAN-2055C
CANopen slave module of 8-channel DI and DO
 
     
 
 
 
     
 
2-Port Isolated Protection CAN Communication Board
4-Port Isolated Protection CAN Communication Board
One Standalone Intelligent CAN Communication Card
USB/CANopen Master Converter Module
1 Port High Performance CANopen Master Slot Module
1 Port CANopen Master Slot Module
 
     
   
Copyright© ICP DAS Co., Ltd. All Rights Reserved