Model: I-8KE4-MTCP-G |
|
|
 |
Model: I-8KE8-MTCP-G |
|
|
|
I-8KE4-MTCP-G
I-8KE8-MTCP-G
Modbus/TCP I/O Unit
(Ethernet enables Modbus commands to run over TCP/IP)
|
|
|
|
|
 |
|
|
|
|
|
|
I-8KE4-MTCP-G and I-8KE8-MTCP-G
are Modbus/TCP I/O units with Modbus communication protocol.
They support most of 8K and 87K series I/O modules, such
as DI, DO, DIO, AI, AO, etc.. Most SCADA software support
Modbus communication protocol, thus users can easily and
quickly integrate remote I/Os to the SCADA software as data
acquisition and monitor to apply to environment monitoring,
power management, factory automation, etc.
|
|
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
Supports IPv4 |
|
Supports Modbus/TCP communication
protocol at Ethernet port. |
|
Supports Modbus/RTU communication protocol
at RS-232 port. |
|
Supports 8K and 87K series DI/DO/AI/AO/Counter/Frequency
modules |
|
I/O configurable via the Ethernet
(Using the Modbus Utility) |
|
I/O scan engine |
|
The
engine can automatically scan I/O modules plug in slots and
range I/O registers address to continuous |
to
have high-data-density registers to get best communication
efficiency. |
|
Support power on value and safe value for analog/digital output module. |
|
Detection of I/O module communication
status (online/offline). |
|
The SMMI of the panel can be
used to |
|
1.
Configure the network setting (IP, Mask, Gateway) |
|
2.Set
the offset value of AI/AO module |
|
Allowed a maximum
of 8 host PCs access simultaneously |
|
Firmware updateable (via the
RS-232 port) |
|
Firmware programmable |
|
We
provide the Modbus SDK allowing users customized the Modbus
firmware. |
|
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
The Modbus Utility package
is for Windows 98/SE/2K/XP. It includes
|
Modbus Utility |
1.On-line configuration via Ethernet
2.TO memorize the I/O setting in EEPROM
3.Automatically generate register mapping tables
4.Configuration export/import
5.COM Port setting(Modbus/RTU gateway, VxComm, UpLink,
Programming, Debug)
6.show I/O value by 3 modes(Value, Dec, Hex)
7.Analog output, digital output control
8.Plot trend line
9.I/O value datalog (.txt file)
10.Power on value, safe value, WDT setting
|
 |
|
MBRTU |
Modbus/RTU client
(with source code in VB6) to diagnostic Modbus/RTU slave
devices. |
|
MBTCP |
Modbus/TCP client (with source
code in VB6) to diagnostic Modbus/TCP slave devices. |
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
CPU
module |
CPU |
CPU:80186-80
or compatible (16-bit and 80MHz) |
SRAM |
512KBytes |
Flash |
512KBytes |
EEPROM |
2KBytes |
NVRAM |
- |
RTC (real time clock) |
- |
Hardware Serial Number |
- |
Built-in Watchdog Timer |
Yes |
Communicate
Interface |
COM
0 |
Internal
communication with the 87K modules |
COM 1 |
RS-232
(to update firmware) |
COM
2 |
- |
COM
3 |
- |
COM 4 |
- |
Ethernet Port |
10BaseT
NE2000 compatible |
SMMI |
5 - Digit LED
Display |
Yes |
3 - Programmable
LED Indicators |
Yes |
4 - Push Buttons |
Yes |
I/O
expansion slots |
I-8KE4-MTCP |
4
Slots |
I-8KE8-MTCP |
8
Slots |
Dimensions |
I-8KE4-MTCP |
230mm
x 110mm x 75.5mm |
I-8KE8-MTCP |
354mm
x 110mm x 75.5mm |
Operating
Environment |
Operating Temperature |
-25°C
to +75°C |
Storage Temperature |
-30°C
to +85°C |
Humidity |
5
~ 95%,non-condensing |
Power |
Protection |
Power
reverse polarity protection |
3KV power isolation |
Yes |
Power requirement |
10
~ 30 V/DC |
Power supply |
20W |
Power
consumption |
I-8KE4-MTCP:
3.9 W |
I-8KE8-MTCP
: 5.1 W |
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
I-8KE4-MTCP-G |
4-slots Ethernet I/O unit (Gray color) |
I-8KE8-MTCP-G |
8-slots
Ethernet I/O unit (Gray color) |
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
KA-52F |
AC100~250V
input, DC 24V/1A output, flat type power supply |
DIN-KA52F |
KA-52F
with DIN-Rail mount |
DP-665 |
AC
85 ~ 270 V input, DC 24V/1.7A and 5V/0.5A output power supply |
DP-660 |
24V/1.7A
5V/0.5A Power Supply |
DP-1200 |
24V/5A
Power Supply |
|
|
|
|
|
|
|
|
|
back |
|
|
|