Model: DP-1200
DP-1200
24V/5A Power supply
 
 
     
 
 
 
  •  With built in PFC
  •  90% efficiency
  • 60% power boost ability
  • 23V to 28V adjustable range
  •  
         
       
     
     
     
    Input voltage : 85Vac to 264Vac
    Input current : <1.6A @ 115Vac, <0.8A @230Vac
    Input frequency : 47Hz to 63Hz
    Inrush current (cold start)
    < 15A at 115Vac
    < 30A at 230Vac
    Outputs
    MODEL NO. DP-1200
    OUTPUT RAIL +24V
    LOAD

    MIN.

    0A

    RATED

    5A

    MAX.

    6A

    VOLTAGE ACCURACY ¡Ó2%
    RIPPLE NOISE <50mVpp
    LINE REG. !O0.1%
    LOAD REG. !O0.5%
    Efficiency : 90% typical at 230Vac
    Hold up time : longer than 20ms at 115Vac
    Over voltage protection : latch off
    Over load protection : auto recovery
    Short circuit protection : auto recovery
    Cooling : free air convection
    EMI standard : FCC docket 20780 curve "B" EN55022 "B", EN61000-3-2 class D
    Safety : UL 1950, UL 508 CSA 22.2 No. 950-M90 EN 60 950
    Power on indicator : Green light on the panel
    Connectors: AC & DC Connector : Terminal blocks (suitable wire 26~10AWG)
    Hook : For standard symmetrical 35mm DIN-rail
     
         
       
     
     
     
  • Operating temperature : -10¢XC to +70¢XC (derating: typ. 3W/K > 60¢XC)
  • Storage temperature : -25¢XC to +85¢XC
  • Dimensions : 65mm x 125mm x 103mm
  •  
         
       
     
     
     
    1.Each output can provide up to max. load separately when the power supply starts up. To exceed the max. output power    continuously is not allowed.
    2.At factory,in 60%rated load condition,each output is checked to be within voltage accuracy.
    3.Line regulation is defined by changing +-10% of input voltage from nominal line at rated load.
    4.Load regulation is defined by changing +-40% of measured output load from 60%rated load at another output set to 60%rated load.
    5.Ripple &noise is measured by using 15MHz bandwidth limited oscilloscope and terminated each output with a 0.47uF capacitor at    rated load and nominal line.
    6.Hold up time is measured from the end of the last charging pulse to the time which the main output drops down to low  limit of main    output at rated load and nominal line.
    7. Efficiency is measured at rated load and nominal line.
     
         
       
     
     
     