Isolation Voltage : 3000V DC
Communication :
- Asynchronous half-duplex 2-wire RS-485 network
- Max. distance without repeater=4000 feet(1.2Km)
- Speed=1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
- A maximum of 256 Modules can be connected in a single RS-485 bus without using a repeater
- Multiple baud rates and multiple data formats can share the same RS-485 bus(I-7520/7510)
- Different baud rates and the same module address can share the same RS-485 bus
- Connecting 256*8=2048 modules max. in one RS-485 bus with repeater.
- I-7000 series data format = 1 start + 8 data + 1 stop + no parity = 10-bit
- Two extra checksum bytes can be enabled/disabled
- Built-in transient voltage suppresser and PTC protector
- Sharing the same RS-485 bus with a RS-485 or RS-232 device that communicates in multiple data format
not 10-bit) and multiple baud rate. (Use I-7520 to convert from RS-232 to RS-485)
Power :
- +10V ~ +30V DC
- Power reverse protection, over-voltage brown-out protection
System :
- Internal daul watchdog , power-on start value and safe value for host failure
- Operating temperature : -25 to 75¢J
- Storage temperature : -40 to 85¢J
- Humidity : 5 to 95%, non-condensing
|
|
|
|
|
|
|