DL-301-WF-IP65/DL-302-WF-IP65/DL-303-WF-IP65/
DL-304-WF-IP65/DL-305-WF-IP65/DL-306-WF-IP65/
DL-307-WF-IP65/DL-308-WF-IP65 *Asia Only
Remote CO/CO2/HCHO/TVOC/NH3/H2S/Temperature/
Humidity/Dew Point Data Logger Module |
|
|
|
 |
Model: |
DL-301-WF-IP65/DL-302-WF-IP65/DL-303-WF-IP65/
DL-304-WF-IP65/DL-305-WF-IP65/DL-306-WF-IP65/
DL-307-WF-IP65/DL-308-WF-IP65 |
|
|
|
 |
- Able to record CO, CO2, HCHO, TVOC, NH3, H2S, Temperature, Humidity, and Dew Point Measurements
- Non-dispersive Infrared (NDIR) CO2 Sensor
- 2.8" LCD Touch Screen
- Up to 450,000 Records with Date and Time Stamps
- Touch-screen and Web-based Configuration Interface
- Simple and Powerful Software Utility, iOS App and Android App Included
- Able to Display Multilingual Messages on the Screen
- Supports the DCON, Modbus RTU and Modbus TCP Protocols
- Supports the MQTT Protocol for Ethernet Interface
- Includes RS-485/Ethernet/Wi-Fi Communication Interfaces
- Includes Redundant Power Inputs: PoE (IEEE 802.3af, Class 1) and DC Input
- Compatible with IEEE802.11b/g/n Standards
- Support Infrastructure and Limit-AP Modes for Wireless Networks
- Relay Output for Audible/Visual Alarm or Device Control
- Web-based configuration interface and firmware update via Ethernet
- IP 65 Protection Approval
|
|
|
|
|
|
 |
The DL-300-WF-IP65 series is a gas detector monitoring module with Wi-Fi, Ethernet and RS-485 interfaces. It provides a WLAN connection which complies with the IEEE802.11b/g/n standards. With the popularity of 802.11 network infrastructure, the modules make an easy way to incorporate wireless connectivity into monitoring and control systems. The DL-300-WF-IP65 series of Data Logger devices can be used to record CO, CO2, HCHO, TVOC, NH3, H2S, Temperature, Humidity and Dew Point information, including date and time stamps, and are able to store up to 450,000 downloadable records. Real-time data can be accessed from the DL-300-WF-IP65 series Data Logger from anywhere and at any time using the free Windows software, the iOS App or the Android App, as long as they are connected to the same local network as the data Logger. Support is provided for popular industrial protocols such as DCON, Modbus RTU, and Modbus TCP. For Ethernet interface, It also support the emerging machine-to-machine (M2M)/IoT (Internet of Things) connectivity protocol - MQTT. The DL-300-WF-IP65 series Data Logger can be connected via widely used communication interfaces including RS-485, Ethernet, PoE and Wi-Fi, meaning that the device can be easily integrated into existing HMI or SCADA systems, and is easy to be maintained in a distributed control system. The IP65 version of DL-300-WF-IP65 series is designed for industrial applications in harsh environments that provides IP65 grade protection approval. The rugged RJ-45 ensures tight, robust connections, and guarantees reliable operation, even for applications that are subject to high vibration and shock. |
|
|
|
Large 2.8" LCD Touch Screen, with clear Color Chart to indicate the CO/CO2 Level |
|
Supports the MQTT Protocol for IoT Applications |
 |
|
 |
|
|
|
Simple and powerful utility
|
The DL300 Utility can be used to configure the modules, monitor real-time
data, group DL-300 modules so that the status of distribution groups can be viewed and managed. The utility also allows the log data to be downloaded
and exported to a .CSV file that can then be imported into any industrystandard software or spread sheet for analysis. |
 |
|
Multi-platform Remote Access Software
Real-time data from the DL-300 Data Logger can be accessed from anywhere and at any time using the DL300 Utility, the iOS or Android App, or via a regular web browser, as long as they are connected to the same local network as the Data Logger. |
|
 |
|
|
|
Display Messages in Multiple Languages |
|
 |
The display-message-on-screen function supports
multiple language character sets based on UTF-8 encoding. Either pre-configured messages or dynamic messages can be remotely displayed using Modbus commands, or a dynamic message can be sent via the web-based interface. |
|
|
|
|
Real-time data from the DL-300-WF series can be accessed from anywhere and at any time using the WF-IIOT-Utility and iOS App. |
|
 |
|
|
|
|
 |
Mushroom Farm
Mushroom growth yield requires long time to monitor the environment of CO2 concentration, temperature and humidity values, and its growth environment is
high humidity condition. The general equipment cannot work in such environment, but the DL-302-WF-IP65 can be used to record CO2, temperature, humidity
and dew point information with date and time stamps in the operating temperature from -20˚C to +50˚C, and are able to store up to 450,000 downloadable
records . The WISE-5231-3GWA features timer and schedule functions. It allows user to schedule specific date or time for control logic execution, or perform
specific tasks such as time delay. With calendar user interface provided, schedule setting can be more efficient and flexible. This does not require programming,
only some simple settings will be able to achieve the farm production control and quality control, production resume ... and so on. |
|
 |
|
Pig Farm
Ammonia and Hydrogen sulfide are two of the most harmful gases in animal farming environment. They will directly affect animals’ growth and immunity. Pig farm requires long-term immediate monitoring the environment of NH3 concentration, temperature and humidity values. The general equipment cannot work in such environment, but the DL-305-IP65 can be used to record NH3, temperature, humidity and dew point information with date and time stamps in the operating temperature from -20°C to +50°C, and are able to store up to 450,000 downloadable records. The WISE-5231-3GWA features timer and schedule functions. It allows user to schedule specific date or time for control logic execution, or perform specific tasks such as time delay. With calendar user interface provided, schedule setting can be more efficient and flexible. This does not require programming, only some simple settings will be able to achieve the farm production control and quality control, production resume ... and so on. |
|
 |
|
 |
Models |
DL-301-WF-IP65 |
DL-302-WF-IP65 |
DL-303-WF-IP65 |
DL-304-WF-IP65 |
DL-305-WF-IP65 |
DL-306-WF-IP65 |
DL-307-WF-IP65 |
DL-308-WF-IP65 |
System |
CO Alarm |
Yes |
– |
Yes |
– |
CO2 Alarm |
– |
Yes |
Yes |
– |
HCHO Alarm |
– |
Yes |
– |
Yes |
– |
TVOC Alarm |
– |
Yes |
– |
Yes |
NH3 Alarm |
– |
Yes |
– |
H2S Alarm |
– |
Yes |
– |
RH/Temperature Alarm |
Yes |
Real Time Clock |
Yes |
Data Logger |
Yes, up to 450,000 records |
Relay Output |
PhotoMos Relay × 4, 100 VDC @ 1 A |
Communication |
RS-485 Port |
Baud Rate = 1200 ~ 115200 bps |
Ethernet Port |
10/100 Base-TX, 8-Pin RJ-45 x1(Auto-negotiating, Auto-MDI/MDIX, LED indicators) |
Security |
IP filter (whitelist) and Password (web) |
Protocol |
Modbus/RTU (RS-485), Modbus TCP (Ethernet, Wi-Fi) and MQTT (Ethernet) |
Dual Watchdog |
Yes, Module (2.3 sec), Communication (Programmable) |
Wi-Fi Interface |
Antenna |
Antenna = 1 dBi (PCB Antenna) |
Output Power |
18 dBm @ 1 DSSS, 14.5 dBm @ 54 OFDM |
Receive Sensitivity |
-95.7 dBm @ 1 DSSS, -74.0 dBm @ 54 OFDM |
Standard Supported |
IEEE 802.11 b/g/n |
Wireless Mode |
Infrastructure & Limited AP |
Encryption |
WEP, WPA and WPA2 |
Transmission Range |
50 meters (LOS) |
LED Indicators |
PWR |
Green for normal operation |
Link |
Green for the Ethernet-linked |
S1 ~ S4 |
Red for an alarm condition |
Main Machine Interface |
LCD |
2.8 TFT (Resolution 240 x 320 x 16), Defective Pixels <= 3 |
Backlight Life |
20,000 hours |
Brightness |
160 cd/m2 |
Touch Panel |
Yes |
Electrical |
Powered from Terminal Block |
+12 to +48 VDC |
Powered from PoE |
IEEE 802.3af, Class 1 (48 V) |
Power Consumption |
PoE |
3.4 W (Max.) |
3.5 W (Max.) |
3.5 W (Max.) |
2.0 W (Max.) |
2.9 W (Max.) |
2.9 W (Max.) |
2.1 W (Max.) |
2.0 W (Max.) |
Non-PoE |
3.1 W (Max.) |
3.1 W (Max.) |
3.2 W (Max.) |
2.0 W (Max.) |
3.0 W (Max.) |
3.0 W (Max.) |
2.1 W (Max.) |
2.0 W (Max.) |
Mechanical |
Installation |
DIN-Rail or Wall Mounting |
Dimensions (L x W x H) |
170 mm x 117 mm x 60 mm |
Environment |
Operating Temperature |
-20 to +50°C |
Storage Temperature |
-30 to +75°C |
Humidity |
10 to 90% RH, Non-condensing |
Protection Class |
IP65 |
|
|
 |
Models |
DL-301-WF-IP65 |
DL-302-WF-IP65 |
DL-303-WF-IP65 |
DL-304-WF-IP65 |
DL-305-WF-IP65 |
DL-306-WF-IP65 |
DL-307-WF-IP65 |
DL-308-WF-IP65 |
CO Measurement |
Range |
0 to 1000 ppm
(Electrochemical) |
– |
0 to 1000 ppm
(Electrochemical) |
– |
Resolution |
1 ppm |
– |
1 ppm |
– |
Accuracy |
±5% of
measured value |
– |
±5% of
measured value |
– |
Response Time |
30 sec |
– |
30 sec |
– |
Warm-up Time |
300 sec |
– |
300 sec |
– |
CO2 Measurement |
Range |
– |
0 to 9999 ppm (NDIR) |
– |
Resolution |
– |
1 ppm |
– |
Accuracy |
– |
±30 ppm ±3% of measured value |
– |
Response Time |
– |
20 sec |
– |
Warm-up Time |
– |
60 sec |
– |
HCHO Measurement |
Range |
– |
0 ppb to 2000 ppb
(Electrochemical) |
– |
0 ppb to 2000 ppb (Electrochemical) |
– |
Resolution |
– |
1 ppb |
– |
1 ppb |
– |
Accuracy |
– |
0 ~ 300ppb :
±30ppb >
300ppb : ±10% |
– |
0 ~ 300ppb :
±30ppb >
300ppb : ±10% |
– |
Response Time |
– |
≤60 sec |
– |
≤60 sec |
– |
Warm-up Time |
– |
180 sec |
– |
180 sec |
– |
TVOC Measurement |
Range |
– |
0 ppb to 60000
ppb (MEMS
Metal Oxide) |
– |
0 ppb to 60000
ppb (MEMS
Metal Oxide) |
Resolution |
– |
1 ppb |
– |
1 ppb |
Accuracy |
– |
±15% |
– |
±15% |
Response Time |
– |
60 sec |
– |
60 sec |
Warm-up Time |
– |
180 sec |
– |
180 sec |
NH3 Measurement |
Range |
– |
0 to 100 ppm
(Electrochemical) |
– |
Resolution |
– |
1 ppm |
– |
Accuracy |
– |
±5% of
measured value |
– |
Response Time |
– |
< 40 Sec |
– |
Warm-up Time |
– |
60 Sec |
– |
H2S Measurement |
Range |
– |
0 to 100 ppm
(Electrochemical) |
– |
Resolution |
– |
1 ppm |
– |
Accuracy |
– |
±5% of
measured value |
– |
Response Time |
– |
< 30 Sec |
– |
Warm-up Time |
– |
60 Sec |
– |
Temperature Measurement |
Range |
-20 to +50°C |
Resolution |
0.1°C |
Accuracy |
±0.6°C |
Relative Humidity Measurement |
Range |
0 to 100% RH, Non-condensing |
Resolution |
0.1% RH, Non-condensing |
Accuracy |
±5% RH, Non-condensing |
Dew Point |
Range |
Calculated using temperature and relative humidity |
Resolution |
0.1°C |
|
|
 |
DL-301-WF-IP65 CR ~ NEW ~ |
Remote CO/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi and PoE (RoHS) |
DL-302-WF-IP65 CR ~ NEW ~ |
Remote CO2/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi and PoE (RoHS) |
DL-303-WF-IP65 CR ~ NEW ~ |
Remote CO/CO2/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi and PoE (RoHS) |
DL-304-WF-IP65 CR ~ Available soon ~ |
Remote HCHO/TVOC/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi and PoE (RoHS) |
DL-305-WF-IP65 CR ~ Available soon ~ |
Remote NH3/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi and PoE (RoHS) |
DL-306-WF-IP65 CR ~ Available soon ~ |
Remote H2S/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi and PoE (RoHS) |
DL-307-WF-IP65 CR ~ Available soon ~ |
Remote HCHO/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi and PoE (RoHS) |
DL-308-WF-IP65 CR ~ Available soon ~ |
Remote TVOC/Temperature/Humidity/Dew Point Data Logger with Ethernet/RS-485/Wi-Fi and PoE (RoHS) |
|
|
 |
NS-205-IP67 CR |
Industrial 5-port unmanaged IP67 Ethernet switch
Includes IP67 RJ45 Plug x 5, IP67 Power Plug x 1, Cap with Tether x 5 (RoHS) |
NS-205PSE-IP67 CR |
Industrial 5-port unmanaged IP67 Ethernet switch with PoE
Includes IP67 RJ45 Plug x 5, IP67 Power Plug x 1, Cap with Tether x 5 (RoHS) |
NS-208PSE-IP67 CR |
Industrial 8-port unmanaged IP67 Ethernet switch with PoE
Includes IP67 RJ-45 Plug x 8, IP67 Power Plug x 1, Cap with Tether x 8 (RoHS) |
NS-208-IP67 CR |
Industrial 8-port unmanaged IP67 Ethernet switch
Includes IP67 RJ-45 Plug x 8, IP67 Power Plug x 1, Cap with Tether x 8 (RoHS) |
MDR-60-48 CR |
48 V/1.25 A, 60 W Power Supply with DIN-Rail Mounting (RoHS) |
DIN-KA52F-48 |
48 V/0.52 A, 25 W Power Supply with DIN-Rail Mounting |
DR-120-48 |
48 V/2.5 A,120 W Power Supply with DIN-Rail Mounting |
|
 |
 |
 |
4SASO-0001 |
4SIO1K0000013 |