Analog Input |
Input Channels |
8 Differential |
Input Type |
+/- 15 mV, +/- 50 mV, +/- 100 mV, +/- 150 mV
+/- 500 mV, +/- 1 V, +/- 2.5 V, +/- 5 V,+/- 10 V
-20 mA ~ +20 mA, 4 ~ 20 mA, 0 ~ 20 mA (Jumper Selectable)
Thermocouple Type: (J, K, T, E. R. S, B, N, C, L, M, and LDIN43710) |
Resolution |
16-bit |
Sampling Rate |
8 Samples/ sec (Total) |
Accuracy |
0.1% of FSR |
Zero Drift |
+/- 20£gV/ ¢XC |
Span Drift |
+/-
25 £gV/ ¢XC |
Common Mode Rejection |
113dB |
Normal Mode Rejection |
100
dB |
Input Impedance |
Voltage Input: >2M ohm, Current Input: 125 Ohm |
Individual Channel Configurable |
Yes |
Open Thermocouple Detection |
Yes |
Overvoltage Protection |
240 Vrms |
4KV ESD Protection |
Yes, Contact for each terminal. |
Intra-module Isolation, Field
to Logic |
3000 VDC |
Watchdog |
Dual Watchdog |
Yes, Module(1.6 sec) and Communication(Programable) |
1 LED as Power/ Communication
Indicator |
16 LEDs as
High/ Low Alarm Signals |
Power |
Power Consumption |
Maximum : 1.1W |
Environment |
Operating Temperature |
-25
to 75 ¢XC |
Storage Temperature |
-30
to 75 ¢XC |
Humidity |
5 to 95% RH, non-condensing |
Dimensions |
30mm x 102mm x 115mm(W x L x H) Detail |
|
|
|
|
|
Note¡GWe recommend to choose I-87019PW or I-87019Z for accurate thermocouple measurement. |
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
Type Code |
Thermocouple Type
|
Temperature Range ¢XC
|
0E |
Type J |
-210 ~ +760 |
0F |
Type K |
-270 ~ +1372 |
10 |
Type T |
-270 ~ +400 |
11 |
Type E |
-270 ~ +1000 |
12 |
Type R |
0 ~ +1768 |
13 |
Type S |
0 ~ +1768 |
14 |
Type B |
0 ~ +1820 |
15 |
Type N |
-270 ~ +1300 |
16 |
Type C |
0 ~ +2320 |
17 |
TypeL |
-200 ~ +800 |
18 |
TypeM |
-200 ~ +100 |
19 |
Type L2 (DIN 43710) |
-200 ~ +900 |
|
|
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
I-87019RW-G CR |
8-channel Universal Analog Input Module with High Voltage Protection (Gray Cover) (RoHS) |
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|