Models |
I-7188EG(D) |
System Software |
OS |
MiniOS7 (DOS-like embedded operating system) |
Development Software |
ISaGRAF
Software |
ISaGRAF Ver. 3 |
IEC 61131-3 standard |
Languages |
LD, ST, FBD, SFC, IL & FC |
Max. Code Size |
64 KB |
Scan Time |
5 ~ 100 ms for normal program
25 ~ 500 ms (or more) for complex or large program |
CPU Module |
CPU |
80188, 40 MHz |
SRAM |
512 KB |
Flash |
512 KB |
EEPROM |
2 KB |
NVRAM |
31 Bytes (battery backup, data valid up to 10 years) |
RTC (Real Time Clock) |
Provides seconds, minutes, hours, date, day of week, month, year |
64-bit Hardware Serial Number |
Yes, for Software Copy Protection |
Watchdog Timers |
Yes (0.8 second) |
Communication Ports |
Ethernet |
RJ-45 x 1, 10 Base-T |
COM1 |
RS-232 (TxD, RxD, RTS, CTS, GND), non-isolated |
COM2 |
RS-485 (Data+, Data-) with internal self-tuner ASIC; non-isolated |
LED Indicator |
System LED |
Yes |
LED Display |
5-digit 7-segment LED display for (D) version |
Hardware Expansion |
I/O Expansion Bus |
Yes, 1 (14 Pins) |
Mechanical |
Dimensions (W x L x H) |
72 mm x 123 mm x 33 mm |
Environmental |
Operating Temperature |
-25 ~ +75 °C |
Storage Temperature |
-30 ~ +80 °C |
Ambient Relative Humidity |
10 ~ 90 % RH (non-condensing) |
Power |
Input Range |
+10 ~ +30 VDC |
Protection |
Power reverse polarity protection |
Power Consumption |
2 W; 3 W for (D) version |
Protocols (Note that certain protocols require optional devices) |
NET ID |
1 ~ 255, User-assigned by software |
Modbus RTU/ASCII Master
Protocol |
A max. of 2 ports: COM1 ~ COM3 (*).
(To connect to other Modbus Slave devices)
A max. of Max. Mbus_xxx
Function Block amount for 2 ports: 64. |
Modbus RTU Slave
Protocol |
A max. of 2 ports: COM1, one of COM2 or COM3 (*).
(For connecting ISaGRAF, PC/HMI/OPC Server and HMI panels.) |
Modbus TCP/IP Slave
Protocol |
Ethernet port supports Modbus TCP/IP Slave protocol for connecting ISaGRAF & PC/HM up to 4 connections. |
User-defined Protocol |
Custom protocols can be applied at COM1, COM2 & COM3 ~ COM8 (*) using Serial communication function blocks. |
Remote I/O |
One of COM2 or COM3: RS-485 (*) supports I-7000 I/O modules, I-87K base + I-87K Serial I/O boards, or RU-87Pn + I-87K High Profile I/O boards as remote I/O. A max. of 64 I-7000/87K remote I/O modules can connect to one PAC. |
Fbus |
Built-in COM2 Port to exchange data between ICP DAS's ISaGRAF PACs. |
Ebus |
Used to exchange data between ICP DAS ISaGRAF Ethernet PACs via the Ethernet port. |
SMS:
Short Message Service |
One COM port (one of COM1 or COM3 or COM4) (*) can link to a GSM modem to support SMS. The user can request data/control the controller via a cellular phone. The controller can also send data and alarms to the user’s cellular phone. Optional GSM Modem: GTM-201-RS232 (850/900/1800/1900 GSM/GPRS External Modem) |
Modem Link |
Supports PC to remotely download & monitor the controller through COM4 of X504. (*) |
MMICON/LCD |
The COM3: RS-232 (*)supports the ICP DAS MMICON. The MMICON is featured with a 240 x 64 dot LCD and a 4 x 4 Keyboard. User can use it to display picture, string, integer, float, and input a character, string, integer and float. |
Optional I/O Functions (Refer to the ISaGRAF PAC I/O Selection Guide for I/O Module list) |
PWM Output |
Pulse Width Modulation Output |
All X-board series DO boards support PWM output.
Support max. 8-ch for one PAC; Max. frequency:
500 Hz max. for OFF = 1 & ON = 1 ms
Output square wave: OFF: 1 ~ 32767 ms, ON: 1 ~ 32767 ms |
Counters |
Parallel DI Counter |
All X-board series DI boards support DI counter.
Support max. 8-ch for one PAC ; Max. count/frequency: 32-bit, 500 Hz ; Min. pulse width > 1 ms |
Remote DI Counter |
All remote I-7000 & I-87K DI modules support counters.
Max. count/frequency: 16-bit (0~65535), 100 Hz |
Remote High Speed Counter |
Max. count/frequency for I-87082: 32-bit, 100 kHz |
SRAM Expansion |
Battery Backup SRAM |
With an X607/X608 plug in the only expansion I/O slot. Data can be stored in X607/X608, and then PC can load these data via COM1. PC can also download pre-defined data to the X607/X608. (for retain variables) Optional: X607: 128 KB, X608: 512 KB |
* Note: The COM3 ~ COM8 are located in the optional X-board series if it is installed inside the I-7188EG(D).
* ISaGRAF FAQ: oldweb.icpdas.com > Support > FAQ > ISaGRAF Soft-Logic PAC |