The PROFI-5018 is specially designed for the slave device of PROFIBUS DP protocol. It supports up to 10-channel Thermocouple Input Module with High Voltage Protection. Users can easily to choose and configure it by using the GSD file in any PROFIBUS Configurator.

|
|
|
|
Applications |
|
|
|
- Industrial Automation
- Factory Automation
- Process Automation
- Etc…
|
 |
|
|
|
|
Features |
|
|
|
Protocol & Hierarchy |
DP-V0 Slave |
Supports PROFIBUS Transmission Rate (kbps) |
9.6, 19.2, 45.45, 93.75, 187.5, 500, 1500, 3000, 6000, 12000 |
Transmission Rate Setting |
detected automatically |
Address Setting |
Address 0~126 set by rotary switches or SSA Telegram |
Indicators |
PWR LED, RUN LED, ERR LED |
I/O modules Configuration |
Configured by GSD file |
Network Isolation Protection |
High Speed iCoupler |
4KV ESD Protection |
Contact for each terminal |
|
|
|
|
Thermocouple Type |
|
|
|
Thermocouple Type |
Temperature Range °C |
TYPE J |
-210 °C ~ +1200 °C |
TYPE K |
-270 °C ~ 1372 °C |
TYPE T |
-270 °C ~ 400 °C |
TYPE E |
-270 °C ~ 1000 °C |
TYPE R |
-50 °C ~ 1765 °C |
TYPE S |
-50 °C ~ 1765 °C |
TYPE B |
0 °C ~ 1820 °C |
TYPE N |
-270 °C ~ 1300 °C |
TYPE C |
0 °C ~ 2320 °C |
|
|
|
|
Hardware Specifications |
|
|
|
Hardware |
ESD Protection |
4 kV class B |
PROFIBUS Interface |
Controller |
Siemens SPC3 |
Transceiver |
ADI ADM2486 |
Connector |
9-pin female D-Sub |
Baud Rate (bps) |
9.6 k, 19.2 k, 45.45 k, 93.75 k, 187.5 k, 500 k, 1.5 M, 3 M, 6 M, 12 M |
Transmission Distance (m) |
Depend on baud rate (for example, max. 1200 m at 9.6 kbps ) |
Isolation |
3000 VDC for DC-to-DC, 2500 Vrms for bus-to-logic |
Protocol |
DP-V0 |
LED |
Round LED |
PWR LED, RUN LED, ERR LED |
POWER |
Power supply |
Unregulated +10 ~ +40 VDC |
Protection |
Reverse polarity protection, Over-voltage brown-out protection |
Power Consumption |
3.5 W |
I/O |
Analog Input |
10 channel differential thermocouple input, Isolation Voltage:2500Vrms |
Input Range |
+/-15mV, +/-50mV, +/-100mV, +/-500mV, +/-1V, +/-2.5V, +/-20mA, 0~20mA, 4~20mA
(requires optional external 125 Ohms resistor), Thermocouple Type: J, K, T, E, R, S, B, N, C |
Accuracy |
+/- 0.1 of FSR |
Mechanism |
Installation |
DIN-Rail |
Dimensions |
91 mm x 130 mm x 52 mm (W x L x H) |
Environment |
Operating Temp. |
-25 ~ 75℃ |
Storage Temp. |
-30 ~ 80℃ |
Humidity |
10~90% RH,non-condens |
|
|
|
|
Ordering Information |
|
|
|
PROFI-5018/S CR |
PROFIBUS Remote I/O Module (10-Channel Thermocouple input) (ROHS)
include PROFI-5018 module and a DB-1820 daughter board |
|
|
|
|
|
|
Optional Accessories |
|
|
|
CA-252518D |
25pin Male-Female D-Sub 1.8m flat cable ( 180°) |
CD-2518D |
25F-25M 1.8m cable with DIN-Rail Mount of DB-1820 |
|
|
|
|
TOP |
|
|
|
|
|
|