home > product> solutions > industrial communication> Fieldbus > PROFIBUS
 
GW-7553
GW-7553-M
 
Applications
Features
Web-based Administration
Modules Support
Hardware Specifications
Ordering Information
 
 
GW-7553
GW-7553-M
  • 繁體中文
  • English
  •  

    PROFIBUS/Modbus TCP Gateway

     
     

    The GW-7553 Gateway is specially designed for the slave device of PROFIBUS DP protocol. It allows the PROFIBUS master to access the Modbus TCP devices. These Modbus devices may be a PLC, a sensor, the ICPDAS I-8KE4-MTCP module and so forth. In addition, the GW-7553 module built-in web server, the user can set the module by web browser. By using this module, users can put their Modbus TCP devices into PROFIBUS network very easily.

     
     
    Applications  
    • Industrial Automation
    • Factory Automation
    • Process Automation
    • Etc…
     
     
    Features  
    Protocol & Hierarchy
    DP-V0 & DP-V1 Slave
    Supports PROFIBUS Transmission Rate (kbps)
    9.6, 19.2, 45.45, 93.75, 187.5, 500, 1500, 3000, 6000, 12000
    Transmission Rate Setting
    detected automatically
    Max Input Data Length
    240 Bytes
    Max Output Data Length
    240 Bytes
    Address Setting
    0~126 set by DIP switch or EEPROM
    Supports Modbus Mode
    Master/Slave
    Supports Modbus Format
    RTU/ASCII/TCP
    Ethernet
    10/100 Base-TX
    Supports COM 1 Baudrate (kbps)
    2.4, 4.8, 9.6, 19.2, 38.4, 57.6, 115.2
    Supports COM 1 Data Format
    7/8 data bits, No/Odd/Even parity, 1/2 stop bit
    Indicators
    PWR, ERR, and RUN LEDs
    Network Isolation Protection
    2500 Vrms High Speed iCoupler
    DC Isolation Protection
    3000 VDC on PROFIBUS side
     
     
    Web-based Administration  
    • Provide safe value setting
    • Provide network configuration
    • Show diagnostic messages and device information
    • Show communication log between GW-7553 and Modbus devices

     
     
    Modules Support  
    Only the following Modbus commands are supported by the gateway.
    Code
    Name
    Description
    01
    Read Coil Status
    Read the ON/OFF status of discrete outputs in the slave
    02
    Read Input Status
    Read the ON/OFF status of discrete inputs in the slave
    03
    Read Holding Registers
    Read the binary contents of holding registers in the slave
    04
    Read Input Registers
    Read the binary contents of input registers in the slave
    05
    Force Single Coil
    Write a single output to either ON or OFF in the slave
    06
    Preset Single Register
    Write an integer value into a single register in the slave
    15
    Force Multi. Coils
    Write each coil in the sequence of coils to either ON or OFF in the slave
    16
    Preset Multi. Registers
    Write a block of contiguous registers in the slave
     
     
    Hardware Specifications  
    Hardware
    CPU
    80186, 80 MHz or compatible
    SRAM/Flash/EEPROM
    512 KB / 512 KB / 16 KB
    Watchdog
    Watchdog IC
    CPU built-in
    ESD Protection
    4 kV class A
    PROFIBUS Interface
    Controller
    Profichip VPC3+C
    Transceiver
    ADI ADM2486
    Connector
    9-pin female D-Sub
    Baud Rate (bps)
    9.6 k, 19.2 k, 45.45 k, 93.75 k, 187.5 k, 500 k, 1.5 M, 3 M, 6 M, 12 M
    Transmission Distance (m)
    Depend on baud rate (for example, max. 1200 m at 9.6 kbps )
    Isolation
    3000 VDC for DC-to-DC, 2500 Vrms for bus-to-logic
    Protocol
    DP-V0 & DP-V1
    UART Interface
    COM
    RS-232 (For updating firmware and configuration)
    COM Connector
    5-pin screwed terminal block (TxD, RxD, RTS, CTS, GND )
    Baud Rate (bps)
    2400, 4800, 9600, 19200, 38400, 57600, 115200
    Data bit
    7, 8
    Stop bit
    1, 2
    Parity
    None, Even, Odd
    Ethernet Interface
    Controller
    10/100Base-TX Ethernet Controller (Auto-negotiating, Auto_MDIX)
    Connector
    RJ-45 with LED indicator
    LED
    Round LED
    PWR LED, RUN LED, ERR LED
    Power
    Power supply
    Unregulated +10 ~ +30 VDC
    Protection
    Power reverse polarity protection, Over-voltage brown-out protection
    Power Consumption
    2.5 W
    Mechanism
    Installation
    DIN-Rail
    Dimensions
    72mm x 33mm x 119mm (W x L x H)
    Environment
    Operating Temp.
    -25 ~ 75 ℃
    Storage Temp.
    -30 ~ 85℃
    Humidity
    5 ~ 95% RH, non-condensing
     
     
    Ordering Information  
    GW-7553-B CR
    PROFIBUS/Modbus TCP Gateway (RoHS)
    GW-7553-M CR
    PROFIBUS/Modbus TCP Gateway (RoHS) (Metal casing)
     
       
    TOP  
       
       

    這個頁面上的內容需要較新版本的 Adobe Flash Player。

    取得 Adobe Flash Player