Models |
WP-8137 |
WP-8147 |
WP-8437 |
WP-8447 |
WP-8837 |
WP-8847 |
System Software |
|
OS |
Windows CE 5.0 |
.NET Compact Framework |
2.0 |
Embedded Service |
FTP Server, Web Server |
Multilanguage Support |
English, German, French, Spanish, Russian, Italian, Simplified Chinese, Traditional Chinese
(OS version: WP-8x3x v1.2.0.1 or later version; WP-8x4x v1.5.0.2 or later version) |
Development Software |
|
ISaGRAF Software |
ISaGRAF Ver.3 |
IEC 61131-3 standard.
|
Languages |
LD, ST, FBD, SFC, IL & FC; It supports Soft-GRAF HMI in the XP-8xx7-CE6, WP-8xx7 and VP-2xW7 PAC. |
Max. Code Size |
1 MB |
Scan Time |
3 ~ 15 ms for normal program
15 ~ 50 ms for complex or large program |
Non-ISaGRAF |
Options: MS eVC++ 4.0 or VS.NET 2005/2008 (VB.NET, C#.NET) |
Web Service |
|
Web HMI |
PC running Internet Explorer can monitor/control PAC via Internet/modem |
Security |
Support three levels username and password protection. (high/middle/low) |
CPU Module |
|
CPU |
PXA270 (32-bit, 520 MHz) or compatible |
SDRAM |
128 MB |
Dual Battery Backup SRAM |
512 KB (for 5 years data retention while power off) |
FLASH |
Total size |
128 MB |
96 MB |
128 MB |
96 MB |
128 MB |
96 MB |
OS Image |
64 MB |
64 MB |
64 MB |
Built-in Flash Disk |
63 MB |
31 MB |
63 MB |
31 MB |
63 MB |
31 MB |
Registry |
1 MB |
1 MB |
1 MB |
EEPROM |
16 KB |
microSD |
microSD socket with one 2 GB microSD card (support up to 16 GB microSDHC card) |
RTC (Real Time Clock) |
Provide second, minute, hour, date, day of week, month, year |
64-bit Hardware Serial Number |
Yes, for Software Copy Protection |
Dual Watchdog Timers |
Yes |
Programmable LED Indicator |
1 |
Rotary Switch |
Yes (0~9) |
DIP Switch |
- |
Yes (8 bits) |
VGA & Communication Ports |
VGA Port |
Extra GPU |
Yes |
- |
Yes |
- |
Yes |
- |
Resolution |
WP-8x37 : 1024 x 768, 800 x 600, 640 x 480
WP-8x47 : 800 x 600, 640 x 480 |
Ethernet |
RJ-45 x 2, 10/100 Base-TX (Auto-negotiating, LED indicators)
Please use NS-205/NS-208 Industrial Ethernet Switch. |
USB 1.1 (Host) |
2 |
1 |
2 |
1 |
2 |
1 |
COM0 |
Internal communication with the high profi le I-87K series modules in slots |
COM1 |
RS-232 (to update fi rmware) (RxD, TxD and GND); non-isolated |
COM2 |
RS-485 |
D2+, D2- ; self-tuner ASIC inside |
Isolated |
2500 VDC |
3000 VDC |
COM3 |
- |
RS-232/RS-485 (RxD, TxD, CTS, RTS and GND for RS-232,
DATA+ and DATA- for RS-485);
non-Isolated |
COM4 |
- |
RS-232 (RxD, TxD, CTS, RTS, DSR, DTR, CD, RI and GND);
non-isolated |
I/O Expansion Slots |
|
Slot Number |
1 slot (slot 0 ) |
4 slots (slot 0 ~ 3) |
8 slots (slot 0 ~ 7) |
* For High Profi le I-8K and I-87K Modules Only |
Hot Swap * Will be available |
* For High Profile I-87K Modules Only |
Mechanical |
|
Dimensions (W x L x H) |
95 mm x 132 mm x 111 mm |
231 mm x 132 mm x 111 mm |
355 mm x 132 mm x 111 mm |
Installation |
DIN-Rail or Wall Mounting |
Environment |
|
Operating Temperature |
-25 ~
+75 °C |
Storage Temperature |
-30 ~
+80 °C |
Ambient Relative Humidity |
10 ~ 90 % RH (non-condensing ) |
Power |
|
Input Range |
+10 ~ +30 VDC |
Isolation |
1 kV |
Redundant Power Inputs |
Yes, with one power relay (1 A @ 24 VDC) for alarm |
Protection |
1.0 A, 5 V supply to CPU and backplane; 0.6 A, 5 V supply to I/O expansion slots,
total 8 W |
1.1 A, 5 V supply to CPU and backplane; 4.9 A, 5 V supply to I/O expansion slots,
30 W in total for WP-8447
25 W in total for WP-8437 |
1.2 A, 5 V supply to CPU and backplane; 4.8 A, 5 V supply to I/O expansion slots,
30 W in total for WP-8847
25 W in total for WP-8837 |
Power Consumption |
WP-81x7: 7.3 W
(0.3 A @ 24 VDC);
|
WP-84x7: 9.1 W
(0.38 A @ 24 VDC); |
WP-88x7: 9.6 W
(0.4 A @ 24 VDC); |
Protocols (some protocols need optional devices) |
NET ID |
1 ~ 255, User-assigned by software |
Modbus TCP/IP Master
Protocol |
Link to max. 100 devices that support Standard Modbus TCP/IP Slave protocol (FAQ-113) |
Modbus RTU/ASCII Master
Protocol |
Max. 10 ports: COM1 ~ 14 (To connect to other Modbus Slave devices). Support Multi-ports. (*) |
Modbus RTU Slave
Protocol |
Max. 5 ports: COM1, one of COM2/3, COM4 ~ 8 (For connecting ISaGRAF, PC/HMI/OPC Server & HMI panels). (*) |
Modbus TCP/IP Slave
Protocol |
Ethernet LAN1 & LAN2 support total up to 32 connections. (If WP-8xx7 uses 1 connection to connect each PC/HMI, it can connect up to 32 PC/HMI; If WP-8xx7 uses 2 connections to connect each PC/HMI, it can connect up to 16 PC/HMI; ...) When one Ethernet port is broken, the other one can still connect to PC/HMI. |
Web HMI Protocol |
Ethernet port for connecting PC running Internet Explorer. |
I-7000 & I-87K RS-485
Remote I/O |
One of COM2, COM3 supports I-7000 I/O modules, I-87K base + I-87K Serial I/O boards and
RU-87P1/2/4/8 + I-87K High Profile I/O boards as Remote I/O.Max. 255 modules for one controller. (*) |
M-7000 Series Modbus I/O |
Max. 10 RS-485 ports (COM1 ~ 14) can support M-7000 I/O. Each port can connect up to 32 M-7000 Modules. |
Modbus TCP/IP I/O |
LAN2 supports ICP DAS Ethernet I/O : I-8KE4-MTCP and I-8KE8-MTCP. listed at oldweb.icpdas.com > FAQ > Software > ISaGRAF Ver.3 (English) FAQ-042. If LAN2 is broken, it will switch to LAN1 automatically to continuously work. (This need LAN1 & LAN2's IP are set in the same IP domain) |
FRnet I/O |
Support max 8 pcs. I-8172W boards in slot 0 to 7 to connect to FRnet I/O modules, like FR-2053, FR-2057 FR-32R, FR-32P, at oldweb.icpdas.com > FAQ > Software > ISaGRAF Ver.3 (English) FAQ-048. Each I-8172W board can connect up to 256 DI plus 256 DO channels. |
Send Email |
Supports mail_snd and mail_set functions to send email with one attached file via Ethernet port. |
Ebus |
LAN2 to exchange data between ISaGRAF Ethernet PAC via Ethernet port. |
SMS:
Short Message Service |
WP-84x7/88x7's COM4/5 and WP-81x7's COM1/COM5 can link to a GSM Modem to support SMS. User can request data/control the controller by cellular phone. The controller can also send data & alarms to user's cellular phone. (*) Optional GSM Modems: GTM-201-RS232 (850/900/1800/1900 GSM/GPRS External Modem) |
User-defined Protocol |
COM1 ~ COM14 by Serial communication function blocks. (*) |
MMICON/LCD |
COM4 or COM5 and supports ICP DAS's MMICON. (*) |
UDP Server & UDP Client :
Exchange Message & Auto-Report |
LAN1 or LAN2 support UDP Server and UDP Client protocol to send/receive message to/from PC/HMI or other devices. For example, to automatically report data to InduSoft's RXTX driver. |
TCP Client :
Exchange Message & Auto-Report |
LAN1 or LAN2 (To send/receive message to/from PC/HMI or other devices which support TCP server protocol.)
Ex: automatically report data to InduSoft's RXTX driver, or to connect a location camera. |
SQL Client |
Supports SQL Client functions to write data to (or read data from) Microsoft SQL Servers (2000 SP3, 2005, 2008) |
New Hot-Swap and Redundant System |
This redundant system has setup two "Active IP" address point to the active WP-8xx7's LAN1 and LAN2 ports always. One or two or more PC/HMI/SCADA can communicate with this redundant system via one of the two given active IP. So the PC/HMI/SCADA can access to the system easily without any notice about which WP-8xx7 is currently active.
Moreover, the new redundant system can integrate with the RU-87P4 and RU-87P8 expansion unit plus the I-87K high-profile I/O cards to support the hot-swap application. If the I/O card is damaged, the maintenance person just takes one good-card with same model number to hot-swap the damaged one without stopping this redundant system. Please refer to oldweb.icpdas.com > FAQ > Software > ISaGRAF Ver.3 (English) FAQ-093. |
CAN/CANopen |
COM1, COM3 ~ COM14 can connect one I-7530 (converter: RS-232 to CAN) to support CAN/CANopen devices and sensors. One WP-8xx7 supports max.10 RS-232 ports to connect max.10 I-7530. (*) Please refer to oldweb.icpdas.com > FAQ > Software > ISaGRAF Ver.3 (English) FAQ-086. |
HART Solutions |
Support I-87H17W modules in slot 0 to 7 to communicate with other HART devices. |
Optional I/O Functions (Refer to ISaGRAF PAC I/O Selection Guide for I/O Module list) |
PWM Output |
|
High Speed PWM Module |
I-7088, I-8088W, I-87088W:
8-ch. PWM outputs, software support 1 Hz ~ 100 KHz (non-continuous), duty: 0.1 ~ 99.9% |
DO Module as PWM |
8-ch. max. 250 Hz max. For Off=2 & On=2 ms . Output square wave: Off: 2 ~ 32766 ms, On: 2 ~ 32766 ms.
Optional DO Boards: I-8037W, 8041W, 8041AW, 8042W, 8050W, 8054W, 8055W, 8056W, 8057W, 8060W, 8063W, 8064W, 8068W, 8069W. (Relay Output boards cannot generate fast square wave) |
Counter, Encoder, Frequency |
Parallel DI Counter |
8-ch. max. For 1 controller. Counter val: 32-bit. 250 Hz max. Min. ON & OFF width must > 2 ms.
Optional DI boards: I-8040W, 8040PW, 8042W, 8046W, 8048W, 8050W, 8051W, 8052W, 8053W, 8053PW, 8054W, 8055W, 8058W, 8063W. |
Serial DI Counter |
Counter input: 100 Hz max. Counter value: 0 ~ 65535 (16-bit)
Optional serial I-87K DI boards: I-87040W, 87046W, 87051W, 87052W, 87053W, 87053W-A5, 87054W, 87055W, 87058W, 87059W, 87063W. |
Remote DI Counter |
All remote I-7000 & I-87K DI modules support counters. 100 Hz max. value: 0 ~ 65535 |
High Speed Counter |
I-87082W: 100 kHz max. 32 bit;
I-8084W : 250 kHz max. 32 bit |
Encoder |
I-8093W: 3-axis Encoder Module, max. 1M Hz for quadrant input mode, max. 4M Hz for
pulse/direction and cw/ccw input mode. (FAQ-112)
I-8084W: 250 kHz max., 4-ch encoder, can be pulse/direction, or Up/Down or A/B phase
(Quad. mode); Not support Encoder Z-index. (FAQ-100) |
Frequency |
I-87082W: 2-ch, 1 Hz ~ 100 kHz;
I-8084W : 8-ch, 1 Hz ~ 250 kHz; |
Motion |
|
Motion Control |
WP-8xx7 integrate with one I-8091W (2-axis) or two I-8091W (4-axis). |
*Note: COM5 ~ COM14 are resided at the expansion boards if they are plugged on slot 0 ~7 of WP-8xx7.
WP-8137/8147 has no COM3 & COM4. |