Model: VP-25W7, VP-23W7
  VP-25W7/VP-23W7
    ISaGRAF ViewPAC (Windows CE 5.0 inside)
   
   
 
     
     
 
 
 
ViewPAC combines PAC (Programmable Automation Controller), color graphic display and keypad in one unit (PAC + HMI).
It is equipped with a PXA270 CPU (520 MHz) running Windows CE .NET 5.0 operating system, a 3.5"/5.7" TFT LCD, a rubber keypad, 3 I/O slots and various connectivity including USB, Ethernet and RS-232/485. Its operating system, Windows CE .NET 5.0, has many advantages, includes hard real-time capability, small core size, fast boot speed, interrupt handling at a deeper level and achievable deterministic control. Running Windows CE .NET 5.0 in the ViewPAC gives it the ability to run ISaGRAF and PC-based control software such as Visual Basic .NET, Visual C#, Visual C++, SCADA software, etc.
 
     
     
 
 
Windows CE.NET 5.0
ISaGRAF Ver.3 SoftLogic Inside
Support IEC 61131-3 Standard
Support Web HMI function
Accepts max. 1 MB ISaGRAF code size
 
 
     
     
 
 
PXA270 CPU (32-bit & 520 MHz) Audio with Microphone-In and Earphone-Out
128 MB SDRAM & 96 MB Flash 3 I/O Expansion Slots (support High Profile I/O Modules)
IP65 Compliant Front Panel 10/100M Ethernet Port (Default: One)
Rubber Keypad 2 Serial Ports (RS-232, RS-485)
3.5"/5.7" TFT LCD (5.7" LCD is with Touch Panel)  
 
 
     
 
Top
 
     
 
 
 
Soft-GRAF: Create A Colorful HMI ISaGRAF PAC connects the Smart Meter Stress Monitoring Application of Constructions
 
 
Redundant Communication System Modbus RTU/TCP Slave Ports
eLogger HMI Application Modbus RTU/ASCII Master Ports
Remote I/O Modules and Expansion module/board Modbus TCP/IP Master
ZigBee Wireless Solution SMS: Short Message Service
GPS Applications: ISaGRAF PAC plus I-87211W or GPS-721 Multiple Web HMI - Monitor & Control Everywhere!
Integrate with CAN/CANopen Devices and Sensors Motion Control
Send Email with One Attached File Data Recorder and Data Logger
An Easy Way to Program the Fast FRnet Remote I/O Modules Data Exchange: Fbus or Ebus
Data Acquisition Auto-Report System Detect Hot-Swap I-87K (High Profile) I/O Status
Hot-Swap and Redundant System VIP Communication Security
   
   
for "Applications Supporting List" & all applications
 
 
     
 
Top
 
 
 
Spec
 
 
Models VP-23W7 VP-25W7
System Software  
OS Windows CE 5.0
.NET Compact Framework 2.0
Embedded Service FTP Server, Web Server
Development Software  
ISaGRAF Software ISaGRAF Version 3 : IEC 61131-3 standard. Languages: LD, ST, FBD, SFC, IL & FC
It supports Soft-GRAF HMI in the XP-8xx7-CE6, WP-8xx7 and VP-2xW7 PAC.
Max. Code Size Accepts max. 1 MB ISaGRAF code size (Appli.x8m must < 1 MB)
Non-ISaGRAF Options: Microsoft EVC++4.0 or VS .NET 2003/2005/2008 (VB .NET 2003/2005/2008, C# .NET 2003/2005/2008)
Web Service  
Web HMI Support Web HMI function, PC running Internet Explorer can access to the VP-2xW7 via Local Ethernet or Internet or dial Modem, monitoring and control.
Security Web HMI supports three-level user name and password protection
Power Supply  
Input Range +10 ~ +30 VDC
Isolated 1 kV
Capacity 2.5 A, 5 V supply to I/O expansion slots
Power Consumption 7.2W (0.3A @ 24 VDC)
General Environment  
Temperature Operating: -20 ~ +70 °C,
Storage : -30 ~ +80 °C
Humidity 10 ~ 90 % RH (non-condensing )
System  
CPU PXA270 (32-bit, 520 MHz) or compatible
Dual Watchdog Timers Yes
RTC (Real Time Clock) Provide second, minute, hour, date, day of week, month, year
SDRAM 128 MB
Dual Battery Backup SRAM 512 KB (for 5 years data retention while power off)
FLASH 96 MB (64 MB for OS image, 31 MB for built-in Flash disk, 1 MB for registry)
Expansion Flash Memory microSD socket with 1 GB microSD card (can support up to 16 GB compatible microSDHC card)
EEPROM 16 KB, Data retention: 40 years. 1,000,000 erase/write cycles
Rotary Switch Yes (0~9)
NET ID From 1 ~ 255, User-assigned by software
Serial Number Yes,64-bit hardware unique serial number
Communication Interface  
First Ethernet RJ-45 x 1, 10/100 Base-TX (Auto-negotiating, LED indicators)
Please use NS-205/NS-208 Industrial Ethernet Switch.
Second Ethernet The default VP-25W7/VP-23W7 has only one Ethernet port. They can add one optional I-8135W card in its slot 0 ~ 2 to expands the second Ethernet port.
USB Port one USB 1.1 Host ports for USB-mouse, keyboard or USB drive
COM0 Internal communication with the I-87K High Profile modules in slot 0 ~ 2
COM2 RS-485 (D2+, D2- ; self-tuner ASIC inside); Speed: 115200 bps max. ; 2500 VDC isolated
COM3 RS-232 (RxD, TxD, CTS, RTS, DSR, DTR, CD, RI and GND);
Non-Isolated; Speed: 115200 bps max.
I/O Expansion Slots  
Slot Number VP-25W7/VP-23W7: 3 slots (slot 0 ~ slot 2)
* Accept only High Profile I-8K Parallel & High Profile I-87K Serial I/O boards
Hot Swap * For High Profile I-87K I/O modules in slot 0 ~ 2 only
MMI (Man Machine Interface)
LCD Monitor 3.5" TFT (Resolution 320 x 240) 5.7" TFT (Resolution 640 x 480)
Touch Panel - Yes
Rubber Keypad 24 keys 6 keys
Audio Microphone-In and Earphone-Out
LED Indicators 3 Dual-Color LEDs (PWR, RUN, LAN1, L1, L2, L3; L1~L3 For User Programmable)
Mechanical
Dimensions (W x L x H) 182 mm x 158 mm x 125 mm
Ingress Protection Front panel: IP65
Motion  
Motion Control One I-8091W (2-axis) or two I-8091W (4-axis) can do motion control, only one I-8091W can do X-Y dependent motion.
PWM Output  
High Speed PWM Module I-7088, I-8088W, I-87088W:
8-ch. PWM outputs, software support 1 Hz ~ 100 KHz (non-continuous), duty: 0.1 ~ 99.9%
DO Module as PWM 8-ch. max. 250 Hz max. For Off=2 & On=2 ms . Output square wave: Off: 2 ~ 32766 ms, On: 2 ~ 32766 ms.
Optional DO Boards: I-8037W, 8041W, 8041AW, 8042W, 8050W, 8054W, 8055W, 8056W, 8057W, 8060W, 8063W, 8064W, 8068W, 8069W. (Relay Output boards cannot generate fast square wave)
Counter, Encoder, Frequency
Parallel DI Counter 8-ch. max. For 1 controller. Counter val: 32-bit. 250 Hz max. Min. ON & OFF width must > 2 ms. Optional DI boards: I-8040W, 8040PW, 8042W, 8046W, 8048W, 8050W, 8051W, 8052W, 8053W, 8053PW, 8054W, 8055W, 8058W, 8063W.
Serial DI Counter Counter input: 100 Hz max. Counter value: 0 ~ 65535 (16-bit)
Optional serial I-87K DI boards: I-87040W, 87046W, 87051W, 87052W, 87053W, 87053W-A5, 87054W, 87055W, 87058W, 87059W, 87063W.
Remote DI Counter All remote I-7000 & I-87K DI modules support counters. 100 Hz max. value: 0 ~ 65535
High Speed Counter I-87082W: 100 kHz max. 32 bit;
I-8084W: 250 kHz max. 32 bit
Encoder I-8093W: 3-axis Encoder Module, max. 1M Hz for quadrant input mode, max. 4M Hz for
              pulse/direction and cw/ccw input mode. (FAQ-112)
I-8084W: 250 kHz max., 4-ch encoder, can be pulse/direction, or Up/Down or A/B phase
              (Quad. mode); Not support Encoder Z-index. (FAQ-100)
Frequency I-87082W: 2-ch, 1 Hz ~ 100 kHz; I-87088W: 8-ch, 0.1 Hz ~ 500 kHz;
I-8084W: 8-ch, 1 Hz ~ 250 kHz;
Protocols  
Modbus RTU/ASCII Master
Protocol
Up to 10 COM Ports (COM2 ~ 3 and COM5 ~ COM14 if multi-serial port boards are plugged in) can support multi-ports of Modbus RTU/ASCII Master protocol to connect to other Modbus Slave devices.
Modbus TCP/IP Master
Protocol
Link to max. 100 devices that support Standard Modbus TCP/IP Slave protocol (FAQ-113)
Modbus RTU Slave
Protocol
Up to 5 COM Ports (one of COM2/3 and COM5 ~ COM8) can support Modbus RTU Slave protocol for connecting ISaGRAF, PC/HMI/OPC Server & HMI panels.
Modbus TCP/IP Slave
Protocol
Ethernet Ports all support Modbus TCP/IP Slave protocol for connecting ISaGRAF & PC/HMI. LAN1 and optional 2nd Ethernet Port in I-8135W support total up to 32 connections. When one Ethernet port is broken, the other one can still connect to PC/HMI.
Web HMI Ethernet ports for connecting PC running Internet Explorer.
I-7000 & I-87K
RS-485 Remote I/O
One of COM2, COM3 supports I-7000 I/O modules, I-87K base + I-87K Serial I/O boards and
RU-87P1/2/4/8 + I-87K High Profile I/O boards
as Remote I/O. Max. 255 pcs. of I-7000/87K Remote I/O modules for one controller.
M-7000 Series Modbus I/O Max. 10 RS-485 ports COM2 ~ 3 & COM5 ~ COM14 if multi-serial port boards are plugged in) can support M-7000 series Modbus I/O. Each port can connect up to 32 M-7000 Modules.
(with optional I-7510 repeater connected can connect up to more than 32 M-7000 Modules)
Modbus TCP/IP I/O Supports ICP DAS Ethernet I/O : I-8KE4-MTCP and I-8KE8-MTCP listed at oldweb.icpdas.com > FAQ > Software > ISaGRAF Ver.3 (English) FAQ-042.
If LAN1 is broken, it will switch to the 2nd Ethernet port (in optional I-8135W card) automatically to continuously work. (This need LAN1 & the 2nd Ethernet's IP are set in the same IP domain)
FRnet I/O Support max 3 pcs. I-8172W boards in slot 0 ~ 2 to connect to FRnet I/O modules, like FR-2053,
FR-2057, FR-32R, FR-32P, at oldweb.icpdas.com > FAQ > Software > ISaGRAF Ver.3 (English) FAQ-048. Each I-8172W board can connect up to 256 DI plus 256 DO channels.
Send Email Supports "mail_snd" and "mail_set" functions to send email with one attached file via Ethernet port.
Ebus To exchange data between ICP DAS's ISaGRAF Ethernet controllers via Ethernet port.
(LAN1 Port only)
SMS:
Short Message Service
One of COM3 (or COM5 if multi-serial port board is plugged in) can link to a GSM Modem to support SMS. User can request data/control the controller by cellular phone. The controller can also send data & alarms to user's cellular phone. Optional GSM Modems: GTM-201-RS232 (850/900/1800/1900 GSM/GPRS External Modem)
User-defined Protocol User can write his own protocol applied at COM2 ~ COM3 & COM5 ~ COM14 (if multi-serial port boards are plugged in) by Serial communication function blocks.
MMICON/LCD COM3 or COM5 (if I-8112W/8114W is found) supports ICP DAS's MMICON. The MMICON is featured with a 240 x 64 dot LCD & a 4 x 4 Keyboard to display picture, string, integer, float, & input a char, string, integer & float.
UDP Server & UDP Client
(Exchange Message &
Auto-Report)
LAN1 or 2nd Ethernet port (in optional I-8135W card) support UDP Server and UDP/IP Client protocol to send/receive message to/from PC/HMI or other devices. For example, to automatically report data to InduSoft's RXTX driver.
TCP Client
(Exchange Message &
Auto-Report)
LAN1 or 2nd Ethernet port (in optional I-8135W card) support TCP Client protocol to send/receive message to/from PC/HMI or other devices which support TCP Server protocol. For example, to automatically report data to InduSoft's RXTX driver, or to connect a local camera.
New Hot-Swap and
Redundant System
Must enable the 2nd Ethernet port in the optional I-8135W card. This redundant system has setup two "Active IP" address point to the active VP-25W7/VP-23W7's LAN1 and 2nd Ethernet ports always. One or two or more PC/HMI/SCADA can communicate with this redundant system via one of the two given active IP.

So the PC/HMI/SCADA can access to the system easily without any notice about which VP-25W7/
VP-23W7 is currently active. Moreover, the new redundant system can integrate with the RU-87P4 and RU-87P8 expansion unit plus the I-87K high-profile I/O cards to support the hot-swap application.

If the I/O card is damaged, the maintenance person just takes one good-card with same model number to hot-swap the damaged one without stopping this redundant system. Please refer to oldweb.icpdas.com > FAQ > Software > ISaGRAF Ver.3 (English) FAQ-093.
CAN/CANopen VP-25W7/VP-23W7 can use its COM3 or COM5 ~ COM14 resides at the I-8112iW/8114W/8114iW
RS-232 expansion board
to connect one I-7530 : the RS-232 to CAN converter to support CAN and CANopen devices and sensors. One VP-25W7/VP-23W7 supports max. Ten RS-232 ports to connect max. Ten I-7530. Please refer to oldweb.icpdas.com > FAQ > Software > ISaGRAF Ver.3 (English)
FAQ-086.
 
     
 
Top
 
     
 
 
VP-23W7-EN CR ISaGRAF based ViewPAC with 3.5" LCD (OS: English) (RoHS)
VP-25W7-EN CR ISaGRAF based ViewPAC with 5.7" LCD (OS: English) (RoHS)
VP-23W7-TC CR ISaGRAF based ViewPAC with 3.5" LCD (OS: Traditional Chinese) (RoHS)
VP-25W7-TC CR ISaGRAF based ViewPAC with 5.7" LCD (OS: Traditional Chinese) (RoHS)
VP-23W7-SC CR ISaGRAF based ViewPAC with 3.5" LCD (OS: Simplified Chinese) (RoHS)
VP-25W7-SC CR ISaGRAF based ViewPAC with 5.7" LCD (OS: Simplified Chinese) (RoHS)
VP-GUP-17000 Upgrade the VP-2xW1 to become VP-2xW7 (or Upgrade the VP-2xW9 to become VP-2xW6)
 
     
     
 
     
   
     
     
 
     
   
     
     
 