Models |
VP-23W7 |
VP-25W7 |
System Software |
|
OS |
Windows CE 5.0 |
.NET Compact Framework |
2.0 |
Embedded Service |
FTP Server, Web Server |
Development Software |
|
ISaGRAF Software |
ISaGRAF Version 3 : IEC 61131-3 standard. Languages: LD, ST, FBD, SFC, IL & FC
It supports Soft-GRAF HMI in the XP-8xx7-CE6, WP-8xx7 and VP-2xW7 PAC. |
Max. Code Size |
Accepts max. 1 MB ISaGRAF code size (Appli.x8m must < 1 MB) |
Non-ISaGRAF |
Options: Microsoft EVC++4.0 or VS .NET 2003/2005/2008 (VB .NET 2003/2005/2008, C# .NET 2003/2005/2008) |
Web Service |
|
Web HMI |
Support Web HMI function, PC running Internet Explorer can access to the VP-2xW7 via Local Ethernet or Internet or dial Modem, monitoring and control. |
Security |
Web HMI supports three-level user name and password protection |
Power Supply |
|
Input Range |
+10 ~ +30 VDC |
Isolated |
1 kV |
Capacity |
2.5 A, 5 V supply to I/O expansion slots |
Power Consumption |
7.2W (0.3A @ 24 VDC) |
General Environment |
|
Temperature |
Operating: -20 ~
+70 °C, Storage : -30 ~ +80 °C |
Humidity |
10 ~ 90 % RH (non-condensing ) |
System |
|
CPU |
PXA270 (32-bit, 520 MHz) or compatible |
Dual Watchdog Timers |
Yes |
RTC (Real Time Clock) |
Provide second, minute, hour, date, day of week, month, year |
SDRAM |
128 MB |
Dual Battery Backup SRAM |
512 KB (for 5 years data retention while power off) |
FLASH |
96 MB (64 MB for OS image, 31 MB for built-in Flash disk, 1 MB for registry) |
Expansion Flash Memory |
microSD socket with 1 GB microSD card (can support up to 16 GB compatible microSDHC card) |
EEPROM |
16 KB, Data retention: 40 years. 1,000,000 erase/write cycles |
Rotary Switch |
Yes (0~9) |
NET ID |
From 1 ~ 255, User-assigned by software |
Serial Number |
Yes,64-bit hardware unique serial number |
Communication Interface
| |
First Ethernet |
RJ-45 x 1, 10/100 Base-TX
(Auto-negotiating, LED indicators)
Please use NS-205/NS-208 Industrial Ethernet Switch. |
Second Ethernet |
The default VP-25W7/VP-23W7 has only one Ethernet port. They can add one optional I-8135W card in its slot 0 ~ 2 to expands the second Ethernet port. |
USB Port |
one USB 1.1 Host ports for USB-mouse, keyboard or USB drive |
COM0 |
Internal communication with the I-87K High Profile modules in slot 0 ~ 2 |
COM2 |
RS-485 (D2+, D2- ; self-tuner ASIC inside); Speed: 115200 bps max. ; 2500 VDC isolated |
COM3 |
RS-232 (RxD, TxD, CTS, RTS, DSR, DTR, CD, RI and GND);
Non-Isolated;
Speed: 115200 bps max. |
I/O Expansion Slots |
|
Slot Number |
VP-25W7/VP-23W7: 3 slots (slot 0 ~ slot 2) |
* Accept only High Profile I-8K Parallel & High Profile I-87K Serial I/O boards |
Hot Swap
|
* For High Profile I-87K I/O modules in slot 0 ~ 2 only |
MMI (Man Machine Interface) |
LCD Monitor |
3.5" TFT (Resolution 320 x 240) |
5.7" TFT
(Resolution 640 x 480) |
Touch Panel |
- |
Yes |
Rubber Keypad |
24 keys |
6 keys |
Audio |
Microphone-In and Earphone-Out |
LED Indicators |
3 Dual-Color LEDs (PWR, RUN, LAN1, L1, L2, L3; L1~L3 For User Programmable) |
Mechanical |
Dimensions (W x L x H) |
182 mm x 158 mm x 125 mm |
Ingress Protection |
Front panel: IP65 |
Motion |
|
Motion Control |
One I-8091W (2-axis) or two I-8091W (4-axis) can do motion control, only one I-8091W can do X-Y dependent motion. |
PWM Output |
|
High Speed PWM Module |
I-7088, I-8088W, I-87088W:
8-ch. PWM outputs, software support 1 Hz ~ 100 KHz (non-continuous), duty: 0.1 ~ 99.9% |
DO Module as PWM |
8-ch. max. 250 Hz max. For Off=2 & On=2 ms . Output square wave: Off: 2 ~ 32766 ms, On: 2 ~ 32766 ms.
Optional DO Boards: I-8037W, 8041W, 8041AW, 8042W, 8050W, 8054W, 8055W, 8056W, 8057W, 8060W, 8063W, 8064W, 8068W, 8069W. (Relay Output boards cannot generate fast square wave) |
Counter, Encoder, Frequency |
Parallel DI Counter |
8-ch. max. For 1 controller. Counter val: 32-bit. 250 Hz max. Min. ON & OFF width must > 2 ms. Optional DI boards:
I-8040W, 8040PW, 8042W, 8046W, 8048W, 8050W, 8051W, 8052W, 8053W, 8053PW, 8054W, 8055W, 8058W, 8063W. |
Serial DI Counter |
Counter input: 100 Hz max. Counter value: 0 ~ 65535 (16-bit)
Optional serial I-87K DI boards:
I-87040W, 87046W, 87051W, 87052W, 87053W, 87053W-A5, 87054W, 87055W, 87058W, 87059W, 87063W. |
Remote DI Counter |
All remote I-7000 & I-87K DI modules support counters. 100 Hz max. value: 0 ~ 65535 |
High Speed Counter |
I-87082W: 100 kHz max. 32 bit;
I-8084W: 250 kHz max. 32 bit |
Encoder |
I-8093W: 3-axis Encoder Module, max. 1M Hz for quadrant input mode, max. 4M Hz for
pulse/direction and cw/ccw input mode. (FAQ-112)
I-8084W: 250 kHz max., 4-ch encoder, can be pulse/direction, or Up/Down or A/B phase
(Quad. mode); Not support Encoder Z-index. (FAQ-100) |
Frequency |
I-87082W: 2-ch, 1 Hz ~ 100 kHz; I-87088W: 8-ch, 0.1 Hz ~ 500 kHz;
I-8084W: 8-ch, 1 Hz ~ 250 kHz; |
Protocols |
|
Modbus RTU/ASCII Master
Protocol |
Up to 10 COM Ports (COM2 ~ 3 and COM5 ~ COM14 if multi-serial port boards are plugged in) can support multi-ports of Modbus RTU/ASCII Master protocol to connect to other Modbus Slave devices. |
Modbus TCP/IP Master
Protocol |
Link to max. 100 devices that support Standard Modbus TCP/IP Slave protocol (FAQ-113) |
Modbus RTU Slave
Protocol |
Up to 5 COM Ports (one of COM2/3 and COM5 ~ COM8) can support Modbus RTU Slave protocol for connecting ISaGRAF, PC/HMI/OPC Server & HMI panels. |
Modbus TCP/IP Slave
Protocol |
Ethernet Ports all support Modbus TCP/IP Slave protocol for connecting ISaGRAF & PC/HMI. LAN1 and optional 2nd Ethernet Port in I-8135W support total up to 32 connections. When one Ethernet port is broken, the other one can still connect to PC/HMI. |
Web HMI |
Ethernet ports for connecting PC running Internet Explorer. |
I-7000 & I-87K
RS-485
Remote I/O |
One of COM2, COM3 supports I-7000 I/O modules, I-87K base + I-87K Serial I/O boards and
RU-87P1/2/4/8 + I-87K High Profile I/O boards as Remote I/O. Max. 255 pcs. of I-7000/87K Remote I/O modules for one controller. |
M-7000 Series Modbus I/O |
Max. 10 RS-485 ports COM2 ~ 3 & COM5 ~ COM14 if multi-serial port boards are plugged in) can support M-7000 series Modbus I/O. Each port can connect up to 32 M-7000 Modules.
(with optional I-7510 repeater connected can connect up to more than 32 M-7000 Modules) |
Modbus TCP/IP I/O |
Supports ICP DAS Ethernet I/O : I-8KE4-MTCP and I-8KE8-MTCP listed at oldweb.icpdas.com > FAQ > Software > ISaGRAF Ver.3 (English) FAQ-042.
If LAN1 is broken, it will switch to the 2nd Ethernet port (in optional I-8135W card) automatically to continuously work. (This need LAN1 & the 2nd Ethernet's IP are set in the same IP domain) |
FRnet I/O |
Support max 3 pcs. I-8172W boards in slot 0 ~ 2 to connect to FRnet I/O modules, like FR-2053,
FR-2057, FR-32R, FR-32P, at oldweb.icpdas.com > FAQ > Software > ISaGRAF Ver.3 (English) FAQ-048. Each I-8172W board can connect up to 256 DI plus 256 DO channels. |
Send Email |
Supports "mail_snd" and "mail_set" functions to send email with one attached file via Ethernet port. |
Ebus |
To exchange data between ICP DAS's ISaGRAF Ethernet controllers via Ethernet port.
(LAN1 Port only) |
SMS:
Short Message Service |
One of COM3 (or COM5 if multi-serial port board is plugged in) can link to a GSM Modem to support SMS. User can request data/control the controller by cellular phone. The controller can also send data & alarms to user's cellular phone. Optional GSM Modems: GTM-201-RS232 (850/900/1800/1900 GSM/GPRS External Modem) |
User-defined Protocol |
User can write his own protocol applied at COM2 ~ COM3 & COM5 ~ COM14 (if multi-serial port boards are plugged in) by Serial communication function blocks. |
MMICON/LCD |
COM3 or COM5 (if I-8112W/8114W is found) supports ICP DAS's MMICON. The MMICON is featured with a 240 x 64 dot LCD & a 4 x 4 Keyboard to display picture, string, integer, float, & input a char, string, integer & float. |
UDP Server & UDP Client
(Exchange Message &
Auto-Report) |
LAN1 or 2nd Ethernet port (in optional I-8135W card) support UDP Server and UDP/IP Client protocol to send/receive message to/from PC/HMI or other devices. For example, to automatically report data to InduSoft's RXTX driver. |
TCP Client
(Exchange Message &
Auto-Report) |
LAN1 or 2nd Ethernet port (in optional I-8135W card) support TCP Client protocol to send/receive message to/from PC/HMI or other devices which support TCP Server protocol. For example, to automatically report data to InduSoft's RXTX driver, or to connect a local camera. |
New Hot-Swap and
Redundant System |
Must enable the 2nd Ethernet port in the optional I-8135W card. This redundant system has setup two "Active IP" address point to the active VP-25W7/VP-23W7's LAN1 and 2nd Ethernet ports always. One or two or more PC/HMI/SCADA can communicate with this redundant system via one of the two given active IP.
So the PC/HMI/SCADA can access to the system easily without any notice about which VP-25W7/
VP-23W7 is currently active. Moreover, the new redundant system can integrate with the RU-87P4 and RU-87P8 expansion unit plus the I-87K high-profile I/O cards to support the hot-swap application.
If the I/O card is damaged, the maintenance person just takes one good-card with same model number to hot-swap the damaged one without stopping this redundant system. Please refer to oldweb.icpdas.com > FAQ > Software > ISaGRAF Ver.3 (English) FAQ-093. |
CAN/CANopen |
VP-25W7/VP-23W7 can use its COM3 or COM5 ~ COM14 resides at the I-8112iW/8114W/8114iW
RS-232 expansion board to connect one I-7530 : the RS-232 to CAN converter to support CAN and CANopen devices and sensors. One VP-25W7/VP-23W7 supports max. Ten RS-232 ports to connect max. Ten I-7530.
Please refer to oldweb.icpdas.com > FAQ > Software > ISaGRAF Ver.3 (English)
FAQ-086. |