I-9064
Introduction
The I-9064 module provides 8 Form A Relay Output channels, and is an ideal solution for high-power applications. The I-9064 includes 8 LED indicators that can be used to monitor the status of the Relay Output channels, and options are available for configuring power-on and safe values. 4 kV ESD protection and 3000 VDC intra-module isolation are also provided to enhance the noise protection capabilities of the module in harsh industrial environments.
Applications
Ordering Information
| PRODUCT SERIES | DESCRIPTION | QNT. | INQUIRY |
|---|---|---|---|
This combination include other products.
Similar Products
| Isolation | |
|---|---|
| Intra-module Isolation | 3000 VDC |
| EMS Protection | |
|---|---|
| ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal ±8 kV Air for Random Point |
| LED Indicators | |
|---|---|
| Status | 1 x Power and Communication 8 x Power Relay |
| Relay Output | |
|---|---|
| Channels | 8 (Form A) |
| Type | Power Relay |
| Contact Material | Gold-plated Silver Cadmium Alloy |
| Contact Rating | 5A @ 250 VAC (Resistive Load) 5A @ 30 VDC (Resistive Load) |
| Operate Time | 6 ms (Max.) |
| Release Time | 3 ms (Max.) |
| Electrical Endurance | 1 × 105 ops. |
| Mechanical Endurance | 2 × 107 ops. |
| Power on Value | Yes |
| Safe Value | Yes |
| Power | |
|---|---|
| Consumption | 1 W Max. |
| Mechanical | |
|---|---|
| Dimensions (mm) | 31 x 134 x 144 (W x L x H) |
| Environment | |
|---|---|
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +85 °C |
| Humidity | 10 ~ 90 % RH, Non-condensing |