這個頁面上的內容需要較新版本的 Adobe Flash Player。

取得 Adobe Flash Player

home > product> solutions > remote i/o modules/units > I-8K & I-87K > I-87053W/I-87053PW/I-87053W-A2
 
I-87053W/I-87053PW/I-87053W-A2
16-channel Isolated Digital Input Module with 16-bit Counters
 
    ~ NEW~
Model: I-87053W Model: I-87053PW Model: I-87053W-A2
 
  • 16-channel Digital Inputs
  • Dry and Wet Contact, Selectable via Wire Connections
  • Photocouple Isolation
  • Long Distance Measurement
  • 4 kV ESD Protection
  • All Channels can be used as 16-bit Counters
  • 3750 VDC Intra-module Isolation
  • Dual Watchdog
  • Wide Operating Temperature Range: -25 ~ +75°C
 
The I-87053W, I-87053PW and I-87053W-A2 offer 16 channels for digital input, catering for both dry and wet contact, with an effective distance for dry contact of up to 500 meters. All channels feature photocouple isolation, and can also be used as 16-bit counters. The I-87053W series provides 16 LED indicators that can be used to monitor the DI channel status. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided to enhance noise immunity capabilities in industrial environments. ICP DAS recommends selecting either the "P" or "A2" version of the digital input module for industrial use.
 
  • Building Automation
  • Factory Automation
  • Machine Automation
  • Remote Maintenance
  • Remote Diagnosis
  • Testing Equipment
 
Model I-87053W I-87053PW I-87053W-A2
Digital Input
Channels 16
Type Dry, Wet
Sink /Source (NPN /PNP) Sink, Source
Dry Contact On Voltage Level Close to GND.
Off Voltage Level Open
Wet Contact On Voltage Level +3.5 VDC ~ +30 VDC +19 VDC ~ +30 VDC +19 VDC ~ +50 VDC
Off Voltage Level +1 VDC Max. +11 VDC Max. +11 VDC Max.
Input Impedance 3 kΩ, 1 W 3 kΩ, 1 W 10 kΩ, 1 W
Counters Channels 16
Max. Count 16-bit (65535)
Max. Input Frequency 100 Hz
Min. Pulse Width 5 ms
Channel-to-Channel Isolation -
Overvoltage Protection 50 VDC 50 VDC 100 VDC
Low Pass Filter Yes
Effective Distance for Dry Contact 500 m Max.
 
Model I-87053W I-87053PW I-87053W-A2
Communication
Interface RS-485
Format N, 8, 1
Baud Rate 1200 ~ 115200 bps
Protocol DCON
Dual Watchdog Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicators/Display
System LED Indicator 1 LED as Power/Communication Indicator
I/O LED Indicator 16 LEDs as High/Low Alarm Signals
Isolation
Intra-module Isolation, Field-to-Logic 3750 VDC
EMS Protection
ESD (IEC 61000-4-2) 4 kV Contact for Each Terminal
8 kV Air for Random Point
Power
Power Consumption 0.8 W Max.
Mechanical
Dimensions (W x L x H) 30 mm x 102 mm x 115 mm
Environment
Operating Temperature -25 ~ +75°C
Storage Temperature -40 ~ +85°C
Humidity 10 ~ 95% RH, Non-condensing
 
I-87053W-G CR 16-channel Isolated Digital Input Module with 16-bit Counters (Gray Cover) (RoHS)
I-87053PW-G CR 16-channel Isolated Digital Input Module with 16-bit Counters (Gray Cover) (RoHS)
I-87053W-A2-G CR 16-channel Isolated Digital Input Module with 16-bit Counters (Gray Cover) (RoHS)
 
SG-770 CR 7-channel Differential or 14-channel Single-ended Surge Protector (RoHS)
 
TOP | HOME
 