I-87019RW
8-channel Universal Analog Input Module with High Overvoltage Protection |
|
| |
| |
|
 |
|
| Model: I-87019RW |
|
|
|
 |
- Current Input, Voltage Input and Thermocouple Input
- Wider Input Range for Voltage
- 240 Vrms Overvoltage Protection
- Individual Channel Configuration
- Jumper Setting for Current or Voltage Measuring
- Open Thermocouple Detection
- 4 kV ESD Protection
- 3000 VDC Intra-module Isolation
- RoHS Compliant
- Wide Operating Temperature Range: -25 ~ +75°C
|
|
|
| |
 |
I-87019RW features an extremely excellent protection mechanism where Overvoltage Protection is up to 240 Vrms. It has wider input range for voltage
compared to I-87018R. I-87019RW measures voltage from +/- 15 mV ~ +/- 10 V. Its input type also includes current and thermocouple. An intuitive design is kept in this model; choosing to measure current or voltage is simply by a jumper. An external resistor is no longer needed. Eight of its input channels can individually be configured with different kinds of analog input. What’s more, I-87019RW also got open thermocouple detection and many protection mechanisms. |
| |
 |
| Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment. |
| |
 |
| Analog Input |
| Channels |
8 |
| Wiring |
Differential |
| Sensor Type |
+/- 15 mV, +/- 50 mV, +/- 100 mV, +/- 150 mV, +/- 500 mV,
+/- 1 VDC , +/- 2.5 VDC , +/- 5 VDC ,+/- 10 VDC |
| -20 mA ~ +20 mA (Jumper Selectable) |
Thermocouple
(J, K, T, E, R, S, B, N, C, L, M, and LDIN43710) |
| Resolution |
16-bit |
| Accuracy |
+/- 0.1% of FSR |
| Sampling Rate |
8 Hz (Total) |
| -3dB Bandwidth |
15.7 Hz |
| Zero Drift |
+/- 20 μV/°C |
| Span Drift |
+/- 25 ppm/°C |
| Common Mode Rejection |
113 dB |
| Normal Mode Rejection |
100 dB |
| Input Impedance |
Voltage Input: >2 MΩ, Current Input: 125 Ω |
| Individual Channel Configurable |
Yes |
| Open Wire Detection |
Yes |
| Overvoltage Protection |
240 Vrms |
|
| |
 |
| Communication |
| Interface |
RS-485 |
| Format |
N, 8, 1 |
| Baud Rate |
1200 ~ 115200 bps |
| Protocol |
DCON |
| Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Indicators/Display |
| System LED Indicator |
1 LED as Power/Communication Indicator |
| I/O LED Indicator |
16 LEDs as High/Low Alarm Signals |
| Isolation |
| Intra-module Isolation, Field-to-Logic |
3000 VDC |
| EMS Protection |
| ESD (IEC 61000-4-2) |
4 kV Contact for each Terminal |
| 8 kV Air for Random Point |
| Power |
| Power Consumption |
1.1 W Max. |
| Mechanical |
| Dimensions (W x L x H) |
30 mm x 102 mm x 115 mm |
| Environment |
| Operating Temperature |
-25 ~ +75°C |
| Storage Temperature |
-40 ~ +85°C |
| Humidity |
10 ~ 95% RH, Non-condensing |
|
| |
 |
| I-87019RW-G CR |
8-channel Universal Analog Input Module with High Voltage Protection (Gray Cover) (RoHS) |
|
| |
 |
| SG-770 CR |
7-channel Differential or 14-channel Single-ended Surge Protector (RoHS) |
| SG-3000 series |
Signal Conditioning Modules for Thermocouple, RTD, DC Voltage, DC Current and Power Input |
|
| |
|
|
| |
|
|