I-87017W-RMS
8-channel True RMS Input Module
 
~ NEW ~  
 
Model: I-87017W-RMS  
 
  • 8-channel True RMS Input
  • ±0.15% Factory Calibrated Accuracy
  • The RMS input range can be from +150 mVrms to +10 Vrms
  • Designed for Standard Operation with Frequencies of 45 Hz to 10 KHz
  • 0.15% Additional Error to Crest Factor of 3
  • Individual Channel Configurable
  • 4 kV ESD Protection
  • ±35 VDC Overvoltage Protection
  • 3000 VDC Intra-module Isolation
  • RoHS Compliant
  • Wide Operating Temperature Range: -25 to +75°C
 
The I-87017W-RMS is an 8-channel differential AC input module that is used to convert the AC input signals to their true RMS DC values. The RMS input range can be from +150 mVrms to +10 Vrms, and each channel can be configured individually. The I-87017W-RMS is a complete, high-accuracy, RMS-to-DC converter that computes the true RMS DC value of any complex waveform. It also features 4 kV ESD protection, 3000 VDC intra-module isolation and +/-35 VDC overvoltage protection.
 
  • Building Automation
  • Factory Automation
  • Machine Automation
  • Remote Maintenance
  • Remote Diagnosis
  • Testing Equipment
 
Analog Input
Channels 8
Wiring Differential
Range 0 ~ +10 Vrms, 0 ~ +5 Vrms, 0 ~ +1 Vrms,
0 ~ +500 mVrms, 0 ~ +150 mVrms
Resolution 16-bit
Accuracy Sinusoid
50/60 Hz ±0.15% of FSR
45 Hz to 10 kHz ±0.5% of FSR
Non-Sinusoid
Crest Factor = 1 to 2 ±0.2% of FSR
Crest Factor = 2 to 3 ±0.35% of FSR
DC
0 ~ +10 V/0 ~ +5 V/
0 ~ +1 V
±0.3% of FSR
0 ~ +500 mV, 0 ~ +150 mV ±0.7% of FSR
Sampling Rate 10 Hz (Total)
-3dB Bandwidth 15.7 Hz
Zero Drift ±20 μV/°C
Span Drift ±25 ppm/°C
Common Mode Rejection 86 dB
Normal Mode Rejection 100 dB
Input Impedance >2 MΩ
Individual Channel Configuration Yes
Overvoltage Protection ±35 VDC
 
Communication
Interface RS-485
Format N, 8, 1
Baud Rate 1200 to 115200 bps
Protocol DCON
Dual Watchdog Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicators/Display
System LED Indicator Yes, 1 as Power/Communication Indicator
I/O LED Indicator 16 as High/Low Alarm Signals
Isolation
Intra-module Isolation, Field-to-Logic 3000 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal
±8 kV Air for Random Point
Power
Power Consumption 1.0 W Max.
Mechanical
Dimensions (L x W x H) 115 mm x 30 mm x 102 mm
Environment
Operating Temperature -25 to +75°C
Storage Temperature -40 to +85°C
Humidity 10 to 95% RH, Non-condensing
 
I-87017W-RMS CR 8-channel True RMS Input Module (Gray Cover) (RoHS)
 
DN-843V-600V CR 3-channel 600 V Voltage Attenuator (RoHS)
DN-848VI-80V CR 8-channel 80 V Voltage Attenuator (RoHS)
DN-848VI-150V CR 8-channel 150 V Voltage Attenuator (RoHS)
DN-843I-CT-1 CR 3-channel 1 A Current Transformer (RoHS)
DN-843I-CT-50 CR 3-channel 50 A Current Transformer (RoHS)
SG-770 CR 7-channel Differential or 14-channel Single-ended Surge Protector (RoHS)
SG-3000 series Signal Conditioning Modules for Thermocouple, RTD, DC Voltage, DC Current and Power Input
 
TOP | HOME
 