I-87005W
8-channel Thermistor Input and 8-channel Digital Output Module |
|
| |
| |
|
 |
|
| Model: I-87005W |
|
|
|
 |
- Thermistor Input
- Individual Channel Configuration
- Open Wire Detection
- 8-channel Digital Output for Alarm Output
- 3000 VDC Intra-module Isolation
- Overvoltage Protection for Thermistor Input
- User-defined Thermistor Types
- RoHS Compliant
- Wide Operating Temperature Range: -25 ~ +75°C
|
|
|
| |
 |
The I-87005W module is used for measuring temperature using a thermistor. The module supports a wide range of thermistors, and features individual channel configuration, which means that eight of the input channels can be individually configured for different kinds of thermistor. In addition, the I-87005W also provides 8 digital output channels that can be used for alarm output, and supports user-defined thermistor types, which can be added by specifying the Steinhart coefficients, if necessary. The inclusion of 3000 VDC intra-module isolation and overvoltage protection for the thermistors on the I-87005W ensures that the module operates at a higher reliability. |
|
| |
 |
- Temperature Measurement
- Environment Monitoring
- Tunnel Monitoring
- Building Monitoring
|
| |
 |
| Thermistor Input |
| Channels |
8 |
| Wiring |
2 Wires |
| Sensor Type |
Precon ST-A3, Fenwell U, YSI L100, YSI L300, YSI L1000, YSI B2252, YSI B3000, YSI B5000, YSI B6000, YSI B10000,
YSI H10000, YSI H30000, User-defined |
| Resolution |
16-bit |
| Accuracy |
±0.1% of FSR |
| Sampling Rate |
8 Hz (Total) |
| Zero Drift |
±0.5 μV/°C |
| Span Drift |
±25 ppm/°C |
| Common Mode Rejection |
113 dB |
| Normal Mode Rejection |
100 dB |
| Input Impedance |
>1 MΩ |
| Individual Channel Configuration |
Yes |
| Resistance Measurement |
200 kΩ |
| Open Wire Detection |
Yes |
| Overvoltage Protection |
120 VDC/110 VAC |
| Digital Output |
| Output Channels |
8 |
| Output Type |
Isolated Open-collector |
| Maximum Load Current |
700 mA/Channel |
| Load Voltage |
+5 ~ +50 VDC |
| Safe Value |
Yes |
| Power-on Value |
Yes |
|
| |
 |
| Communication |
| Interface |
RS-485 |
| Format |
N, 8, 1 |
| Baud Rate |
1200 ~ 115200 bps |
| Protocol |
DCON |
| Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Indicators/Display |
| System LED Indicator |
1 LED as Power/Communication Indicator |
| I/O LED Indicator |
16 LEDs as High/Low Alarm Signals |
| Isolation |
| Intra-module Isolation, Field-to-Logic |
3000 VDC |
| EMS Protection |
| ESD (IEC 61000-4-2) |
±4 kV Contact for each Terminal |
| ±8 kV Air for Random Point |
| Power |
| Power Consumption |
0.7 W Max. |
| Mechanical |
| Dimensions (W x L x H) |
30 mm x 95 mm x 114 mm |
| Environment |
| Operating Temperature |
-25 ~ +75°C |
| Storage Temperature |
-40 ~ +85°C |
| Humidity |
10 ~ 95% RH, Non-condensing |
|
| |
 |
| I-87005W-G CR |
8-channel Thermistor Input and 8-channel Digital Output Module (Gray Cover) (RoHS) |
|
| |
 |
| SG-770 CR |