I-87053W-AC1 offers 16 channels for AC digital input . All of its channels are not only with isolation but also able to be used as counters. I-87053W-AC1 has 16 LED indicators for channel status as well as qualification for 4 kV ESD protection and 3750 Vrms intra-module isolation. |
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
- Support AC Digital Inputs
- Photo Couple Isolation
- Long Distance Measurement
- Can Be Used As Counters
- 4 kV ESD Protection
- 3750 Vrms Intra-Module Isolation
- RoHS Compliance
- A Wide Range of Operating Temperature: -25 ¢XC~ 75 ¢XC
|
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
- Industry automation
- Industrial Machinery
- Building Automation
- Food & Beverage
- Semiconductor Fabrication
- Control system
|
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
Digital Input |
Input Channels |
16 |
Wet Contact |
On Voltage Level: 10 ~ 80 VAC |
Off Voltage Level: 3 VAC Max. |
AC Frequency |
47 ~ 400 Hz (> 45 Hz min) |
Input Impedance |
10 kOhm, 0.66 W |
Counters |
Channels: 16 |
Max. Counts : 16-bit (65535) |
Max. Input Frequency: 100 Hz |
Min. Pulse Width: 5 ms |
Intra-module Isolation, Field to Logic |
3750 Vrms |
ESD Protection |
4 kV (contact for each terminal) |
Watchdog |
Dual Watchdog |
Yes, Module(1.6 sec) and Communication(Programable) |
LED Display |
1 LED as Power/ Communication Indicator |
16 LEDs as Digital Input Indicators |
Power |
Power Consumption |
1.5 W max. |
Environment |
Operating Temperature |
-25 ~ 75 ¢XC |
Storage Temperature |
-30 ~ 75 ¢XC |
Humidity |
5 ~ 95% RH, non-condensing |
Dimensions |
30mm x 102mm x 115mm (W x L x H) Detail |
|
|
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
I-87053W-AC1-G CR |
16-channel AC Isolated Digital Input Module with 16-bit Counters (Gray Cover) (RoHS) |
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|