FR-2156T
8CH Discrete Digital Output Module of FRnet System |
|
|
|
 |
|
FR-2156T |
|
|
|
|
|
|
|
|
|
 |
|
|
|
|
|
|
|
The FR-2156T has 8-channels isolated photo-coupler output and the transfer speed is fixed at 1M bps. The default signal connector of FR-2156T is a 12-pin 0.15¡¨ screw terminal connector.
According to different applications, the users can choose suitable modules. The FR-2100 I/O module has a FRNet interface. The users can daisy chain several FR-2100 modules together. Via FRNet, the FR-2100 modules can extend the discrete I/O control of PC and PAC easily. For further information about the networking of FR-2100 series; please refer to literature related to I-7188EF, I-8172, FRB-200 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Built-in Wire-saving FRnet DI/DO control |
High-speed transmission reliability |
Simple synchronization mechanism |
No software overhead on protocol processing |
Supporting broadcasting (1:n data transmission) |
Duplicating output easily |
Fixed I/O scan-time and I/O synchronization |
DIN-Rail mountable |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Industrial Automation |
Remote I/O control |
Wire-saving application |
Built-in Wire-saving FRnet DI/DO control |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6P4C RJ-11 modular connector with Cat.3 cable (2P twisted-pair cable) for easy wiring( When different cables are used, the transmission distance may change). |
Power consumption |
2.0 W (Max.) |
Power requirement |
12-24 V DC |
Operating temperature |
-25¢XC to +65 ¢XC |
Operating humidity |
10% ~ 95% RH, non-condensing |
Storage temperature |
-30¢XC to +85¢XC |
Storage humidity |
5% ~ 95% RH, non-condensing |
Weight |
approximately 120g |
Dimensions |
99 mm x 32 mm x 83 mm |
Output Isolation |
1 KVdc |
Output type |
4.7 K Ohm |
Output points |
8 channels |
Sink Current |
300mA per channel max. |
Response Time |
Turn-On delay time: less than 0.15 ms |
Turn-Off delay time: less than 0.05 ms |
Output Protection |
Thermal shutdown with auto restart |
Overload protection |
Short circuit protection |
Over-voltage protection |
Current limitation. |
Transmission |
Transfer speed:1 M bps |
Cyclic scan time:0.72 ms |
Transfer distance:Max. 100 m |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FR-2156T |
8-channel isolated digital output with 12- pin screw terminal connector |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|