~ NEW ~ |
|
|
|
|
Model: ET-7017-10 |
Regular Ethernet Version |
|
Model: PET-7017-10 |
PoE Version |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The ET-7017-10/PET-7017-10 is a web-based Ethernet I/O module that features a built-in web server which allows remote configuration, I/O monitoring and I/O control simply by using a regular web browser. Remote control is as easy as surfing the Internet. In addition, the web HMI function means that programming or HTML skills are no longer required so creating dynamic and attractive web pages for I/O monitoring and I/O control purposes will be more fun for engineers in the future. The ET-7017-10/PET-7017-10 offers easy and safe access for users at anytime and from anywhere, and also supports the Modbus/TCP protocol that ensures perfect integration with SCADA software. Furthermore, the PET-7017-10 features ¡§PoE¡¨, meaning that not only is data transmitted through an Ethernet cable but also power making installation of the PET-7017-10 a piece of cake. Imagine no more unnecessary wires with only an Ethernet cable being required to take care of everything in the field.
The ET-7017-10 is a 16-bit, 10-channel differential or 20-channel single-ended analog inputs module that provides programmable input range on all analog channels (+/-150 mV, +/-500mV, +/-1 V, +/-5 V, +/-10 V, +/-20 mA, 0~20 mA and 4~20 mA). Each analog channel is allowed to configure an individual range and has 240 Vrms high overvoltage protection. Jumper selectable for voltage or current input. The sampling rate of ET-7017/PET-7017 is changeable; there are fast mode and normal mode for your consideration. ET-7017/PET-7017 also has qualification for 4 kV ESD protection as well as 3000 VDC intra-module isolation. |
|
|
|
|
|
|
|
|
|
back |
|
 |
|
|
|
|
|
|
- PoE and Regular Ethernet Options
- Built-In Web Server
- Web HMI
- Modbus/TCP, Modbus/UDP Protocol
- Communication Security
- Dual Watchdog
- Operating Temperature: -25 ~ +75 ¢XC
- I/O Pair Connection
- Built-In I/O
|
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis, Testing Equipment. |
|
|
|
|
|
|
|
|
|
back |
|
 |
|
|
|
|
|
|
Models |
ET-7017-10 |
PET-7017-10 |
Software |
Built-In Web Server |
Yes |
Web HMI |
Yes |
I/O Pair Connection |
Yes |
Communication |
Ethernet Port |
10/100 Base-TX with Auto MDI/MDI-X |
Protocol |
Modbus/TCP, Modbus/UDP |
Security |
ID, Password and IP Filter |
Dual Watchdog |
Yes, Module (0.8 second), Communication (Programmable) |
LED Indicators |
L1 (System Running) |
Yes |
L2 (Ethernet Link/Act) |
Yes |
L3 (Ethernet 10/100 M Speed) |
Yes |
PoE Power |
- |
Yes |
2 Way Isolaiton |
Ethernet |
1500 VDC |
- |
I/O |
2500 VDC |
2500 VDC |
EMS Protection |
ESD (IEC 61000-4-2) |
4 kV Contact for each terminal and 8 kV Air for random point |
EFT (IEC 61000-4-4) |
+/-4 kV for Power |
Power Requirements |
Reverse Polarity Protectionn |
Yes |
Powered from terminal block |
Yes, 10 ~ 30 VDC |
Yes, 12 ~ 48 VDC |
Powered from PoE |
- |
Yes, IEEE 802.3af, Class1 |
Consumption |
2.6 W |
3.8 W |
Mechanical |
Dimensions (W x L x D) |
72 mm x 123 mm x 35 mm |
Installation |
DIN-Rail or Wall mounting |
Environment |
Operating Temperature |
-25 ¢XC ~ +75 ¢XC |
Storage Temperature |
-30 ¢XC ~ +80 ¢XC |
Humidity |
10 ~ 90% RH, non-condensing |
|
|
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
Analog Input |
Input Channels |
10 differential or 20 single-ended (Note1),
software selectable |
Input Type |
+/-150 mV, +/-500 mV, +/-1V, +/-5V, +/-10V
+/-20 mA ,0 ~ 20 mA, 4 ~ 20 mA
(jumper selectable) |
Individual Channel Configuration |
Yes |
Resolution |
Normal Mode |
16-bit |
Fast Mode |
12-bit |
Sampling Rate |
Normal Mode |
10 Samples/Sec. (Total) |
Fast Mode |
60 Samples/Sec. (Total) |
Accuracy |
Normal Mode |
+/-0.1% |
Fast Mode |
+/-0.5% or better |
Zero Drift |
+/-20 £gV/¢XC |
Span Drift |
+/-25 ppm/¢XC |
Overvoltage Protection |
Differential |
240 Vrms |
Single-ended |
150 Vrms |
Input Impedance |
Voltage |
2 M£[ (Differential), 1 M£[ (Single-ended) |
Current |
125 £[ |
Common Mode Rejection |
86 dB Min. |
Normal Mode Rejection |
100 dB |
Note1: Differential mode can be used for voltage input and current input.
Single-Ended mode can be used for voltage input only. |
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
ET-7017-10 CR |
10/20-channel Analog Input Module with High Voltage Protection Module (RoHS) |
PET-7017-10 CR |
10/20-channel Analog Input Module with High Voltage Protection PoE Module (RoHS) |
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|
|
|
NS-205 CR |
Unmanaged 5-port Industrial Ethernet Switch; reguires 24 VDC Input (RoHS) |
NS-205PSE CR |
Unmanaged Ethernet switch with 4-PoE and
1 RJ45 uplink; reguires 48 VDC Input (RoHS) |
NS-205PSE-24V CR |
Unmanaged Ethernet switch with 4-PoE and
1 RJ45 uplink; reguires 24 VDC Input (RoHS) |
MDR-20-24 CR |
24V/1A, 24 W Power Supply with DIN-Rail Mounting (RoHS) |
DIN-KA52F-48 CR |
48V/0.52A, 25 W Power Supply with DIN-Rail Mounting (RoHS) |
|
|
|
|
|
|
|
|
|
back |
|
|
|
|
|
|