Introduction

The ETS-7200 series is a web-based Ethernet I/O module equipped with a built-in web server (http/https) allows the user to configure module and control/monitor the status of digital I/O by simply using a regular web browser.

The ETS-7200 series offers easy and safe access for users from anytime and anywhere! In addition, it also supports Modbus security (TLS) protocol that makes improve the network security.
 

1. Industrial Cybersecurity

TLS/DTLS 1.2 support (RFC 5246) to introduce a more reliable industrial application, protect manufacturing data and equipment. An IP address filter is also included, which can be used to allow or deny connections with specific IP addresses.
 
 

2. Daisy-Chain Ethernet Cabling

The ETS-7200 Series has a built-in two-port Ethernet switch to implement daisy-chain topology. The cabling is much easier and total costs of cable and switch are significantly reduced.

 

3. LAN Bypass

LAN Bypass feature guarantees the Ethernet communication. It will automatically active to continue the network traffic if any one of the ETS-7200 looses its power.

 

4. Denial of Service (DoS) attacks protection

Improving DoS attacks protection. Detection, prevention and mitigation of DoS attacks that aim it.
   
 

5. Support for both Modbus/TCP and Modbus/UDP Protocols

The Modbus/TCP, Modbus/UDP slave function on the Ethernet port can be used to provide data to remote SCADA software.

 

6. Built-in I/O

Various I/O components are mixed with multiple channels in a single I/O module, which provides the most cost effective I/O usage and enhances performance of the I/O operations.

 

7. Dual Watchdog

The Dual Watchdog is consists of a Module Watchdog and a Communication Watchdog. The action of AO,DO are also associated to the Dual Watchdog.

Module Watchdog is a built-in hardware circuit to monitor the operation of the module and will reset the CPU if a failure occurs in the hardware or the software. Then the Power-on Value of AO,DO will be loaded.

Communication Watchdog is a software function to monitor the communication between the host and the I/O module. The timeout of the communication Watchdog is proprgrammable, when the I/O doesn't receive commands from the host for a while, the watchdog forces the AO,DO to pre-programmed Safe Value to prevent unpredicatable damage of the connected devices.

 

8. Highly Reliable Under Harsh Environment

  • Wide Operating Temperature Range: -25 ~ +75°C
  • Storage Temperature: -30 ~ +80°C
  • Humidity: 10 ~ 90% RH (Non-condensing)
 

9. I/O Pair Connection

This function is used to create a AI/DI to AO/DO pair through the Ethernet. Once the configuration is completed, the I/O module can poll the status of remote AI/DI devices and then use the Modbus TCP protocol to continuously write to a local AO/DO channels in the background. 


 

10. Power-on Value and Safe Value

Besides setting by the set AO,DO commands, the AO,DO can be set under two other conditions.

Power-on Value: The Power-on Value is loaded into the AO,DO under 3 conditions: Power-on, reset by Module Watchdog, reset by reset command.

Safe Value: When the Communication Watchdog is enabled and a Communication Watchdog timeout occurs, the “safe value” is loaded into the AO,DO.




 



 
Analog Input
Model AI DO
Channel Voltage & Current Input Sensor Input Channel Type Sink/Source
(NPN/PNP)
ETS-7217 8 ±150 mV, ±500 mV, ±1 V,
±5 V, ±10 V, ±20 mA,
0 ~ 20 mA, 4 ~ 20 mA
4 Open Collector Sink (NPN)
 



 
Multifunction I/O
Model AI AO DI/Counter DO
Channel Voltage & Current Input Sensor Input Channel Voltage & Current Output Channel Type Channel Type
ETS-7226 6 ±500 mV, ±1 V,
±5 V, ±10 V,
0 ~ 20 mA,
±20 mA, 4 ~ 20 mA
2 0 ~ 5 V, ±5 V,
0 ~ 10 V, ±10 V
0 ~ 20 mA,
4 ~ 20 mA
2 Dry (Source), Wet (Sink,Source) 2 Open Collector (Sink)
 



 
Digital I/O
Model DI DO
Channel Type Sink/Source
(NPN/PNP)
Channel Type Sink/Source
(NPN/PNP)
Max. Load
Current @ 25 °C
ETS-7255 8 Dry, Wet Sink (NPN) 8 Open Collector Source (PNP) 650 mA/channel
 



 
Relay Output & Digital Input
Model Relay Output DI
Channel Relay Type Max. Load
Current @ 25°C
Channel Type Sink/Source
(NPN/PNP)
ETS-7260 6 Power Relay Form A (SPST N.O.) 5.0 A/channel 6 Wet Sink/Source
(NPN/PNP)
ETS-7267 8 Power Relay Form A (SPST N.O.) 5.0 A/channel - - -
 



Product Lines Comparison Table

Comparison Item ET-2200 tET
tPET
ETA-7000
PETA-7000
ET-7000
PET-7000
ET-7200
PET-7200
Picture
Ethernet 2-Port Switch,
10/100 M
10/100 M 2-Port Switch,
10/100 M
PoE PET-2200 only tPET only PETA-7000 only PET-7000 only PET-7200 only
Protocol Modbus TCP/UDP, MQTT, and SNMP V2c (Note1) Modbus TCP/UDP, MQTT Modbus TCP/UDP
Web HMI Yes
Multi-client Yes (32) Yes (12)
IP Filter Yes (Accessible IP)
Latched DI Yes
DI as Counter (32-bit) 2.5 or 3 kHz 3.5 kHz (without filter) 3 kHz 100 or 500 Hz 100 Hz
I/O Pair-Connection Yes (Pull/Push Mode) Yes (Pull Mode)
PWM Yes (100 Hz max.) -
Frequency Measurement Yes (3 kHz max.) -
Dual Watchdog Yes (Module, Host)
Form Factor Slim Type Tiny Size Palm Size
Space Occupied on DIN-Rail 3.3 cm 5.2 cm 7.2 cm 7.6 cm
Note 1: The SNMP protocol is not available for all modules.