Features

  • Protocol & Hierarchy : DP-V0 Slave
  • Transmission Rate Setting : detected automatically
  • Address Setting : 0~99 set by rotary switches
  • I/O modules Configuration : Configured by GSD file
  • Network Isolation Protection : High Speed iCoupler
  • DC Isolation Protection : 3000 VDC on PROFIBUS side
  • 4KV ESD Protection : Contact for each terminal
CE FCC RoHS WEEE

Introduction

The PROFI-5053 is specially designed for the slave device of PROFIBUS DP protocol. It supports up to 24-channel dry contact non-isolated digital input. Users can easily to choose and configure it by using the GSD file in any PROFIBUS Configurator.

Applications

  • Industrial Automation
  • Factory Automation
  • Process Automation
  • Etc…

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES PROFI-5053     CR DESCRIPTIONPROFIBUS Remote I/O Module (24-channels Dry Contact Non-Isolated Digital Input) (RoHS)
This combination include other products.

Similar Products

LED Indicators
Status PWR LED, RUN LED
Digital Input
Channels 24 Channels (Dry Contact), Non-Isolated.
Off Voltage Level: Close to IN.GND.
On Voltage Level: Open
PROFIBUS
Controller Profichip VPCLS2
Transceiver ADI ADM2486
Baud Rate 9.6 k, 19.2 k, 45.45 k, 93.75 k, 187.5 k, 500 k, 1.5 M, 3 M, 6 M, 12 M
Isolation 3000 VDC for DC-to-DC, 2500 Vrms for bus-to-logic
Protocol DP-V0
Power
Consumption 1 W
Mechanical
Dimensions (mm) 91 x 128 x 52 (W x L x H)
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75℃
Storage Temperature -30 ~ +80 ℃
Humidity 10 ~ 90% RH, Non-condensing