I-7018P

8-ch Thermocouple Input Module
I-7018P
I-7018P
I-7018P
I-7018P

Features

  • Additional Thermocouple Types, L and M
  • 8 Differential, or 6 Differential and 2 Single-ended Analog Inputs
  • Current, Voltage, and Thermocouple Inputs
  • High Resolution: 16-bit
  • Built-in Dual Watchdog
CE UKCA FCC RoHS WEEE

Introduction

The I-7018P is an Analog Input module that features current and voltage input, as well as thermocouple input. The I-7018BL is a thermocouple input module. Both of the modules provide 8-channel differential or 6-channel differential and 2-channel single ended input that can be selected via a jumper, and all channels can be configured for the same input type. Note that an optional external 125 Ω resistor is required for current input. The modules also feature 3000 VDC intra-module isolation as well as ±35 VDC overvoltage protection. The I-7018BL provides thermocouple open wire detection and the I-7018P provides support for two additional thermocouple types, L and M.

Applications


• Building Automation
• Factory Automation
• Machine Automation
• Remote Maintenance
• Remote Diagnosis
• Testing Equipment

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES I-7018P     CR DESCRIPTION8-ch Thermocouple Input Module using DCON Protocol (Blue Cover) (RoHS)
This combination include other products.

Similar Products

CPU Module
Watchdog Timer Module, Communication (Programmable)
Isolation
Intra-module Isolation 3000 VDC
EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power Line
ESD (IEC 61000-4-2) ±2 kV Contact for Each Terminal
Surge (IEC 61000-4-5) ±0.5 kV for Power Line
LED Indicators
Status 1 x Power and Communication
Analog Input
Channels 6 Differential and 2 Single-ended, or 8 Differential
Type Voltage
Current
Thermocouple
Sensor Type Thermocouple: J, K, T, E, R, S, B, N, C, L, M
Range Voltage: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V
Current: ±20 mA (requires an optional external 125 Ω resistor)
Resolution 16-bit
Accuracy ±0.1% of FSR
Sampling Rate 10 Hz
Input Impedance > 400 kΩ
Common Voltage Protection ±15 VDC
Overvoltage Protection ±80 VDC
COM Ports
Ports 1 x RS-485
Baud Rate 1200 ~ 115200 bps
Data Format (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1)
Protocol DCON
Power
Reverse Polarity Protection Yes
Input Range +10 ~ +30 VDC
Consumption 1.0 W
Mechanical
Dimensions (mm) 72 x 123 x 35 (W x L x H)
Installation DIN-Rail Mounting
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing

Specification Memo

Note:
For highly-accurate thermocouple measurement, ICP DAS recommends selecting the I-7018Z/I-7019Z module, which features automatic cold-junction compensation for each channel, ensuring consistent and stable temperature output.