Features

  • Protocol & Hierarchy : DP-V0 & DP-V1 Slave
  • Transmission Rate Setting : detected automatically
  • Max Input Data Length : 240 Bytes
  • Max Output Data Length : 240 Bytes
  • Address Setting : 0~126 set by DIP switch or EEPROM
  • Supports Modbus Mode : Master/Slave
  • Supports Modbus Format : RTU/ASCII/TCP
  • Supports COM 1 Data Format : 7/8 data bits, No/Odd/Even parity, 1/2 stop bit
  • Network Isolation Protection : 2500 Vrms High Speed iCoupler
  • DC Isolation Protection : 3000 VDC on PROFIBUS side
CE FCC RoHS WEEE

Introduction

The GW-7553 Gateway is specially designed for the slave device of PROFIBUS DP protocol. It allows the PROFIBUS master to access the Modbus TCP devices. These Modbus devices may be a PLC, a sensor, the ICPDAS I-8KE4-MTCP module and so forth. In addition, the GW-7553 module built-in web server, the user can set the module by web browser. By using this module, users can put their Modbus TCP devices into PROFIBUS network very easily.

Applications

  • Industrial Automation
  • Factory Automation
  • Process Automation
  • Etc…

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES GW-7553-B     CR DESCRIPTIONPROFIBUS to Modbus TCP Gateway (Plastic Case) (RoHS)
This combination include other products.

Similar Products

CPU Module
CPU 80186, 80 MHz or compatible
EEPROM 16 KB
Flash 512 KB
SRAM 512 KB
Watchdog Timer Watchdog IC
CPU built-in
LED Indicators
Status PWR LED, RUN LED, ERR LED
Ethernet
Ports 10/100Base-TX Ethernet Controller (Auto-negotiating, Auto_MDIX)
COM Ports
Ports RS-232 (For updating firmware and configuration)
5-pin screwed terminal block (TxD, RxD, RTS, CTS, GND )
Baud Rate 2400, 4800, 9600, 19200, 38400, 57600, 115200
Parity None, Even, Odd
Data Bit 7, 8
Stop Bit 1, 2
PROFIBUS
Controller Profichip VPC3+C
Transceiver ADI ADM2486
Baud Rate 9.6 k, 19.2 k, 45.45 k, 93.75 k, 187.5 k, 500 k, 1.5 M, 3 M, 6 M, 12 M
Isolation 3000 VDC for DC-to-DC, 2500 Vrms for bus-to-logic
Protocol DP-V0 & DP-V1
Power
Consumption 2.5 W
Mechanical
Dimensions (mm) 72 x 33 x 119 (W x L x H)
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75℃
Storage Temperature -30 ~ +85 ℃
Humidity 5 ~ 95% RH, Non-condensing
  • Provide safe value setting
  • Provide network configuration
  • Show diagnostic messages and device information
  • Show communication log between GW-7553 and Modbus devices 
.

Modules Support 

Only the following Modbus commands are supported by the gateway. 
Code Name Description
01 Read Coil Status Read the ON/OFF status of discrete outputs in the slave
02 Read Input Status Read the ON/OFF status of discrete inputs in the slave
03 Read Holding Registers Read the binary contents of holding registers in the slave
04 Read Input Registers Read the binary contents of input registers in the slave
05 Force Single Coil Write a single output to either ON or OFF in the slave
06 Preset Single Register Write an integer value into a single register in the slave
15 Force Multi. Coils Write each coil in the sequence of coils to either ON or OFF in the slave
16 Preset Multi. Registers Write a block of contiguous registers in the slave