ETS-7260
Introduction
The ETS-7260 provides 6 wet contact digital input channels and 6 form A electromechanical relays, as well as the MQTT, Rest API, CoAP, LwM2M and Modbus protocols, which are supported for connecting with a variety of digital sensors in Industrial Internet of Things (IIoT) applications. It features optical isolation for 3000 VDC of transient overvoltage protection and doesn't have channel-to-channel isolation. Each input channel can be used as a 32-bit counter. The power-on value and safe value of relay are programmable. Note: When inductive loads are connected to the relays, a large counter electromotive force may occur when the relay actuates because of the energy stored in the load. These flyback voltages can severely damage the relay contacts and greatly shorten the relay life. Limit these flyback voltages at your inductive load by installing a flyback diode for DC loads or a metal oxide varistor for AC loads.
ETS-7260 provides an easy-to-use and intuitive web interface that allows users to implement IF-THEN-ELSE control logic with just a few clicks; no programming is required. The built-in IF-THEN-ELSE logic engine executes the automation logic in a stable and efficient manner. It also provides functions for mathematical operations.
ETS-7260 provides an easy-to-use and intuitive web interface that allows users to implement IF-THEN-ELSE control logic with just a few clicks; no programming is required. The built-in IF-THEN-ELSE logic engine executes the automation logic in a stable and efficient manner. It also provides functions for mathematical operations.
Applications
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment.
Ordering Information
| PRODUCT SERIES | DESCRIPTION | QNT. | INQUIRY |
|---|---|---|---|
This combination include other products.
Similar Products
| Software | |
|---|---|
| Function | • Web Interface for Configuration • IF-THEN-ELSE Logic operation • I/O channel monitoring and control • Timer operation • Schedule operation • Internal Register operation |
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
|---|---|
| 2-way Isolation | Ethernet: 1500 VDC I/O: 3000 VDC |
| EMS Protection | |
|---|---|
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| Surge (IEC 61000-4-5) | ±2 kV for Power Line |
| LED Indicators | |
|---|---|
| Status | Run, Ethernet, I/O |
| Digital Input/Counter | |
|---|---|
| Channels | 6 |
| Type | Wet Contact |
| Sink/Source (NPN/PNP) | Sink/Source |
| ON Voltage Level | +10 to +50 VDC |
| OFF Voltage Level | +4 VDC (max.) |
| Max. Counts | 4,294,967,295 (32-bit) |
| Frequency | 100 Hz |
| Min. Pulse Width | 5 ms |
| Input Impedance | 10 kΩ |
| Overvoltage Protection | +70 VDC |
| Relay Output | |
|---|---|
| Channels | 6 |
| Type | Power Relay, Form A (SPST N.O.) |
| Contact Rating | 5 A @ 250 VAC/24 VDC (Resistive Load) |
| Operate Time | 10 ms (max.) |
| Release Time | 5 ms (max.) |
| Electrical Endurance | 10^5 ops. |
| Mechanical Endurance | 2 × 10^7 ops. |
| Power on Value | Programmable |
| Safe Value | Programmable |
| Ethernet | |
|---|---|
| Ports | 2 x RJ-45, 10/100 Base-TX, Swtich Ports |
| LAN bypass | Yes |
| Access Control | ID, Password and IP Filter |
| Protocol | Modbus TCP, Modbus TCP/TLS, Modbus UDP, MQTT, Rest API, CoAP, LwM2M, SNMP, SMTP, SNTP, HTTP/HTTPS |
| Power | |
|---|---|
| Reverse Polarity Protection | Yes |
| Consumption | 3.9 W (max.) |
| Powered from PoE | Yes, IEEE 802.3af, Class 2 |
| Powered from Terminal Block | +12 to +48 VDC |
| Mechanical | |
|---|---|
| Dimensions (mm) | 76 x 120 x 38 (W x L x H) |
| Installation | DIN-Rail mounting |
| Environment | |
|---|---|
| Operating Temperature | -25 to +75°C |
| Storage Temperature | -30 to +80°C |
| Humidity | 10 to 90% RH, Non-condensing |