| Command |
$AA5 |
| Description |
Read the reset status from the specified I-8000 system. |
| Syntax |
$AA5[CHK](cr)
| $ |
a delimiter character |
| AA |
2-characters HEX module address for the specified I-8000 system
,Range from 01 to FFh |
| 5 |
Command for read the system status. |
| [CHK] |
2-characters of Checksum |
| (cr) |
Character Return(0x0D) for denote the end of command |
|
| Response |
| Valid Command |
!AAS[chk](cr)
|
| Invalid Command |
?AA[CHK](cr) |
Syntax error or communication error may get no response.
| ! |
delimiter for valid command |
| ? |
delimiter for invalid command |
| AA |
2-characters HEX module address |
| S |
represent the reset status for the I-8000 system. If S=1,
the system has been reset or first time power on, If S=0
the system has not been reset. |
| [CHK] |
2-characters of Checksum |
| (cr) |
Character Return(0x0D) for denote the end of response |
|
| Example |
| Command |
$015 |
| Response |
!011(cr) |
| Description |
The example reads the reset status from the I-8000 system
at address 01h, the system had been reset or first
time power on. |
| Note |
Execute this command will reset the status value. |
|
|
|
| Modules |
I-8410,I-8810,I-8430,I-8431,I-8830,I-8831,I-8KE4,I-8KE8
|
|