*** tM-752n RevB / RevB2 only ***

This firmware is designed for "tM-752n RevB/RevB2" series only. 
Make sure there is a "RevB" or "RevB2" mark after the model name on the front cover.

Firmware B2.x : Supports hardware tM-752n RevB and RevB2.
Firmware B1.x : Supports hardware tM-752n RevB.
Firmware V1.x : Supports hardware tM-752n (not RevB and RevB2).

eSearch Utility : 
This is the software utility to update the firmware.
http://ftp.icpdas.com/pub/cd/tinymodules/napdos/software/esearch/windows/

tDS_Firmware_Update_xxx.pdf : 
This is the document describing how to update the firmware.
http://ftp.icpdas.com/pub/cd/tinymodules/napdos/tM-752N/Firmware/


===========================================
B2.0.1, Dec.29, 2022

Chg: Change-password is required if the current password is same as default.
     This rule does not apply to init-mode if troubleshooting is required.	

     Allow change password back to the same as factory default.
     So users can use a single password in site.
	  
Chg: For better protection, the non-isolated models may be discontinued in the future.
     Isolated version is actually shipped when ordering non-isolated models.

     Support isolated version without change the model name on web and eSearch Utility.
     For example: tM-7521_RevB isolated/non-isolated ==> all reports tM-7521_RevB

===========================================
B2.0.0, Mar.06, 2020

Add: Support tM-752n RevB2 series that are RS-485 direction controlled by MCU.
     Firmware B2.x supports tM-752n RevB and RevB2 series.

Add: Have a input box for baud rate	setting.
     So customer can try other non-standard baud rate using input box. 
	  
Fix: IP filter does not work correctly. 
     Change the IP filter to Accessible IP too.

Chg: Remove System Timeout (Network Watchdog).
     Add Serial Watchdog (TX/RX Idle) instead.

Fix: Command port checksum does not work correctly. 

Fix: Delimiter can be changed, but the new setting does not work. 

===========================================
B1.1.5, Apr.27, 2018

Fix: "Parameter Error" may be shown for web configuration. Fixed.

===========================================
B1.1.4, Apr.02, 2018

Fix: The fast-response data (i.e. TX/RX loopback) from slave deice may be 
     blocked and then send back on next request. This can cause data shift 
	  issue. Fixed.

===========================================
B1.1.3, Sep.10, 2016

Add: Supports tM-7521i, tM-7522i new model names.

===========================================
B1.1.2, Jul.19, 2016

Add: Supports CTS/RTS flow control for tM-7521 COM2.
     This function can be used for pending send/receive operations in short 
	  period of time. The master request is queued in TX buffer of the slave 
	  port when CTS off, and then dropped if message timeout.

===========================================
B1.1.1, Jun.24, 2016 

Add: Supports Char-Timeout function on master port for having a better 
     processing timing.

===========================================
B1.1.0, May.25, 2016

First version for RevB.

##