- 10-channel Differential or 20-channel Single-ended Inputs
- Jumper Selectable Voltage or Current Input
- 240 Vrms Overvoltage Protection
- High Resolution: 16-bits
- Supports Fast Mode and Normal Mode
- 4 kV ESD Protection
- 3000 VDC Intra-module Isolation
- Individual Channel Configuration
- Dual Watchdog
- RoHS Compliance
- Wide Operating Temperature Range: -25 to +75°C
|
|
|
| |
 |
The I-97017Z is an analog input module that includes 10 differential or 20
single-ended analog input channels. It provides a programmable input range on all analog inputs. (+/-150 mV, +/-500 mV, +/-1 V, +/-5 V,+/-10 V, +/-20 mA or 0 ~ +20 mA) Each analog input can be configured for an individual range that provides 240 Vrms high overvoltage protection and 50mA overcurrent protection at 110 VDC/VAC. Voltage and current inputs are jumper selectable. The sampling rate of the I-97017Z is adjustable and is available in either fast or normal mode. The module also features perchannel open wire detection for +4 ~ +20 mA inputs that provides 4 KV ESD protection as well as 3000 VDC intra-module isolation. |
|
| |
 |
- Industrial Automation
- Industrial Machinery
- Building Automation
- Food and Beverage Systems
- Semiconductor Fabrication
- Control Systems
|
| |
 |
| Analog Input |
| Channels |
10 Differential or 20 Single-ended (See Note 1), Jumper selectable |
| Range |
±150 mV, ±500 mV,
±1 VDC, ±5 VDC, ±10 VDC, ±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (jumper selectable) |
| Resolution |
16-bit |
| Accuracy |
Normal Mode |
±0.1% of FSR |
| Fast Mode |
±0.5% of FSR |
| Sampling Rate |
Normal Mode |
10 Hz (Total) |
| Fast Mode |
50 Hz (Total) |
| Band Width |
Normal Mode |
15.7 Hz |
| Fast Mode |
78.7 Hz |
| Zero Drift |
±20 μV/°C |
| Span Drift |
±25 ppm/°C |
| Common Mode Rejection |
86 dB |
| Normal Mode Rejection |
100 dB |
| Input Impedance |
Voltage |
Differential |
2 MΩ |
| Single-ended |
1 MΩ |
| Current |
125 Ω |
| Overvoltage Protection |
Differential |
240 Vrms |
| Single-ended |
150 Vrms |
| Individual Channel Configuration |
Yes |
| Overcurrent Protection |
50 mA Max. at 110 VDC/VAC Max. |
|
| Note 1: Differential mode can be used for either voltage input or current input. Single-Ended mode can only be used for voltage input. |
 |
| Communication |
| Interface |
RS-485 |
| Format |
N, 8, 1 |
| Baud Rate |
1200 to 115200 bps |
| Protocol |
DCON |
| Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Display |
| System LED Indictors |
Yes, 1 as Power/Communication Indicator |
| I/O LED Indicators |
- |
| Isolation |
| Intra-module Isolation, Field-to-Logic |
3000 VDC |
| EMS Protection |
| ESD (IEC 61000-4-2) |
±4 kV Contact for each Terminal |
| ±8 kV Air for Random Point |
| RS Immunity (IEC 61000-4-3) |
±4 kV for Power |
| Power |
| Power Consumption |
0.5 W Max. |
| Mechanical |
| Dimensions (W x L x H) |
31 mm x 134 mm x 144 mm |
| Environment |
| Operating Temperature |
-25 to +75°C |
| Storage Temperature |
-40 to +85°C |
| Humidity |
10 to 90% RH, non-condensing |
|
| |
 |