F-8019
8-channel Isolated Thermocouple Input Redundant Module |
|
| |
| ~ NEW ~ |
 |
| Model: F-8019 |
|
|
 |
- 8 thermocouple input channels
- User defined up/down scale
- Open wire detection
- RoHS compliance
- 3000 VDC isolation from output to backplane
- 3000 VDC isolation from output to frame ground
- Redundancy
- Fast redundant switching time (<100us)
|
|
|
| |
 |
The F-8019 is a 16-bit, 8-channel thermocouple input module that features programmable input range on all channels. It measures millivolt input (±15mV, ±50mV, ±100mV, ±150mV, ±500mV), voltage input (±1V, ±2.5V, ±5V, ±10V) and thermocouple input (Type J, K, T, E, R, S, B, N, C). An external CJC is supported for accurate termperature measurement. Moreover, this module has ±0.05% accuracy for highly accurate application. Besides, the F-8019 provides 3000 VDC optical isolation between channels and backplane bus. If any high voltage or current damages these channels, this module won’t affect other component in iDCS-8000 system. |
| |
 |
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
|
|
| |
 |
| Feature |
| Redundant |
Yes (Switching time < 100us) |
| Over Voltage Protection |
Yes |
| Resolution |
Yes |
| Sampling Rate |
Yes |
| Accuracy |
1 RUN, 1 ACT, 1 DUX |
| Thermocouple Input |
| Number of channels |
8 |
| Type |
±15mV, ±50mV, ±100mV, ±150mV,
±500mV, ±1V, ±2.5V, ±5V, ±10V,
Type J, K, T, E, R, S, B, N, C |
| Temperature Range |
J |
-210 ~ +1200 °C |
| K |
-270 ~ +1372 °C |
| T |
-270 ~ +400 °C |
| E |
-270 ~ +1000 °C |
| R |
-50 ~ +1765 °C |
| S |
-50 ~ +1765 °C |
| B |
0 ~ +1820 °C |
| N |
-270 ~ +1300 °C |
| C |
0 ~ +2320 °C |
| Maximum Allowable Input Voltage |
120 VDC |
| Resolution |
16 bit |
| Sampling Rate |
8 Samples/sec (Total) |
| Accuracy |
±0.05% FSR |
| Zero Drift |
±0.5 μV/°C |
| Span Drift |
±20 ppm/°C |
| Common Mode Rejection |
106 dB |
| Normal Mode Rejection |
90 dB |
| Input Impedance |
10 MΩ |
| Data Range |
-2500 ~ 12500 |
| Isolation |
3000 VDC |
| Certification |
| EMC |
EN61000-6-2, EN61000-6-4, IEC/EN 61000-4-2, IEC/EN 61000-4-4 |
| General |
| Termination board |
DN-TC-M |
| Maximum power consumption |
1.3 W |
| Operating temperature |
-25°C ~ +75°C |
| Humidity |
5 ~ 95 % RH, Non-condensing |
| Weight |
300 g |
| Dimensions (W x L x H) |
30 mm x 85 mm x 115 mm |
|
| |
 |
| F-8019 CR |
8-channel Isolated Thermocouple Input Redundant Module (Gray Cover)(RoHS) |
|
| |
 |
| DN-37-A |
I/O Connector Block with DIN-Rail Mounting and 37-pin D-sub Connector (pitch: 5.08 mm) |
| DN-37-381-A |
I/O Connector Block with DIN-Rail Mounting and 37-pin D-sub Connector (pitch: 3.81 mm) |
| DN-TC-M |
Termination board for thermocouple input modules |
| CA-3710AM |
1m 37-pin Male-Female D-sub cable, 24AWG, UL-2464 |
| CA-3720AM |
2m 37-pin Male-Female D-sub cable, 24AWG, UL-2464 |
| CA-3730AM |
3m 37-pin Male-Female D-sub cable, 24AWG, UL-2464 |
| CA-3750AM |
5m 37-pin Male-Female D-sub cable, 24AWG, UL-2464 |
| CA-37100AM |
10m 37-pin Male-Female D-sub cable, 24AWG, UL-2464 |
| CA-3710D |
DB-37 Male-Male D-sub cable 1M, Cable for Daughter Board (180o) |
| CA-3720D |
DB-37 Male-Male D-sub cable 2M, Cable for Daughter Board (180o) |
|
| |
|
|
| |
|
|