MSM-508F Series
8-port Industrial Ethernet Layer 2 Managed Switch with 2-Fiber Port
|
|
|
|
|
 |
 |
Model: MSM-508FC-T/FCS-T Series |
Model: MSM-508FT-T Series |
|
|
 |
- Automatic MDI/MDI-X crossover for plug-and-play
- Each port supports both 10/100 Mbps speed auto negotiation
- Full duplex IEEE 802.3x and half duplex backpressure flow control
- Supports wide operating temperatures from -30 °C ~ +75 °C
- Built-in Cyber-Ring redundant technique
- Redundant Dual Power Inputs +12 VDC ~ +48 VDC
Power failure alarm by relay output
- Modbus remote monitoring
- Supports Modbus OPC Server
- Store-and-forward architecture
- Frame buffer memory: 1 Mbit
- 2048 MAC addresses
- 3.2 Gbps high performance memory bandwidth
- DIN-Rail Mounting
|
|
|
|
|
 |
The MSM-508F series is an 8-port Industrial Ethernet Layer 2 Managed Switch with 2-Fiber Port that secures data transmission by using fiber optic transmission to provide immunity from EMI/RFI interference. It is perfect solution for applications where transmission must be protected from electrical exposure, surges, lightning or chemical corrosion.
It can be managed through RS-232 port via serial console or Ethernet port using telnet or Web browser. In addition, the switch supports a lot of powerful managed functions, such as 802.1Q Tag-based VLAN, Portbased VLAN, 802.1p QoS (Quality of Service), Port Trunking, Spanning Tree, Cable Testing and Port Mirroring.
Built-in ICP DAS Cyber-Ring technique that enable multiple switches to be placed into a redundant ring. Typically it detects and recovers from a fiber or copper link failure within approximately 20 ms V for the majority of applications a seamless process. Modbus/TCP, Modbus/RTU and OPC supported, SCADA application can monitor status of Ethernet and fiber port with Modbus or OPC protocol.
MSM-508F provides two power inputs that can be connected simultaneously to live DC power sources. If one of the power
inputs fails, the other live source acts as a backup to automatically support the it's power needs. And the relay output facility
can deliver warning signal while power or network link failure. |
|
 |
Models |
MSM-508FC-T
MSM-508FCS-T Series |
MSM-508FT-T Series |
Technology |
Standards |
IEEE 802.3, 802.3u and 802.3x |
Processing Type |
Store & forward, wire speed switching |
MAC Addresses |
2048 |
Memory Bandwidth |
3.2 Gbps |
Frame Buffer Memory |
1 Mbit |
Flow Control |
IEEE 802.3x flow control, back pressure flow control |
Protocol |
VLAN, QoS, Port Trunk, SMTP, TELNET |
Ethernet Interface |
RJ-45 Ports |
10/100 Base-TX auto negotiation speed, F/H duplex mode, and auto MDI/MDI-X connection |
Fiber Optics Port |
2-port 100 Base-FX |
LED Indicators |
10/100M, Link/Act, Full duplex/Half duplex (Fiber Port) |
Ethernet Isolation |
1500 Vrms 1 minute |
Multi-mode |
Multi-mode Fiber Cables |
50/125, 62.5/125 or 100/140 μm |
Distance |
2 km, (62.5/125 μm recommended) for full duplex |
Wavelength |
1300 or 1310 nm |
Min. TX Output |
-20 dBm |
Max. TX Output |
-14 dBm |
RX Sensitivity |
-34 ~ -31 dBm |
Single-mode |
Single-mode Fiber Cables |
8.3/125, 8.7/125, 9/125 or 10/125 μm |
Distance |
30 km, (9/125 μm recommended) for full duplex |
Wavelength |
1300 or 1310 nm |
Min. TX Output |
-15 dBm |
Max. TX Output |
-8 dBm |
RX Sensitivity |
-36 ~ -31 dBm |
COM1 |
RS-232 (TxD, RxD and GND); Non-isolated |
COM2 |
RS-485 (D2+, D2-; self-tuner ASIC inside); Non-isolated |
Frame Ground for EMS Protection |
Yes |
Digital Input/Output |
Digital Input |
3-channel, Wet Contact, L: +11 VDC Max., H: +19 VDC ~ +30 VDC |
Digital Output |
3-channel, Open Collector, Sink/NPN, 30V/100 mA Max. |
Power |
Input Voltage Range |
+12 VDC ~ +48 VDC Redundant Dual Inputs (Non-isolated) |
Power Consumption |
0.3 A @ 24 VDC |
LED Indicator |
Yes |
Protection |
Power reverse polarity protection |
Frame Ground for EMS Protection |
Yes |
Connector |
20-Pin Removable Terminal Block |
Mechanical |
Casing |
Metal |
Environmental Rating |
IP30 Protection |
Dimensions (W x L x H) |
47 mm x 140 mm x 175 mm |
47 mm x 142 mm x 175 mm |
Installation |
DIN-Rail Mounting or Wall mounting |
Environment |
Operating Temperature |
-30 °C ~ +75 °C |
Storage Temperature |
-40 °C ~ +85 °C |
Ambient Relative Humidity |
10 ~ 90% RH, non-condensing |
Accessories |
Include Cable |
CA-090510 x 1 |
|
|
 |
MSM-508FT-T CR |
8-port Layer 2 Managed Switch with 2-Fiber Port, Multi-mode, ST Connector (RoHS) |
MSM-508FC-T CR |
8-port Layer 2 Managed Switch with 2-Fiber Port, Multi-mode, SC Connector (RoHS) |
MSM-508FCS-T CR |
8-port Layer 2 Managed Switch with 2-Fiber Port, Single-mode, SC Connector (RoHS) |
MSM-508FCS-60T CR |
8-port Layer 2 Managed Switch with 2-Fiber Port, Single-mode 60 km, SC Connector (RoHS) |
|
|
 |
CA-090510 |
9-Pin Female D-Sub & RJ-45 Cable, 1 M Cable |
MDR-20-24 |
24 V/1 A, 24 W Power Supply with DIN-Rail Mounting |
MDR-60-24 |
24V/2.5A, 60 W Power Supply with DIN-Rail Mounting |
DIN-KA52F |
24 V/1.04 A, 25 W Power Supply |
DR-120-24 |
24 V/5 A, 120 W Power Supply with DIN-Rail Mounting |
|
|
|
|
|
|
|