home > product> solutions > hmi & touch monitor> TouchPAD < I/O Expansion Boards(XV-Boards) > XV116i
 
XV116i
5-channel Isolated Digital Input and 6-channel Relay Output Module
 
 
~ Available soon ~
Model: XV116i
 
  • 5 Digital Input channels and 6 Relay Output channels
  • Sink- and Source-type Digital Input
  • All Digital Input Channels can be used as 16-bit Counters
  • 4 kV ESD Protection
  • 3750 VDC Intra-module Isolation
  • Configurable Power-on Value Settings
  • Configurable Safe Value Settings
  • Wide Operating Temperature Range: -25 ~ + 75°C
 
The XV116i provides 5 channels for digital input, as well as 6 Form A relay output channels. In addition, either sink- or source-type digital input can be selected via wire connections. All input channels can be used as 16-bit counters. The XV116i also provides options for configuring power-on and safe digital output values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided to enhance noise immunity capabilities in industrial environments.
 
  • Industrial Automation
  • Building Automation
  • Food and Beverage Systems
  • Control Systems
 
Digital Input/Counter
Input Channels 5
Type Dry Contact -
Wet Contact Sink/Source
On Voltage Level Dry Contact -
Wet Contact +3.5 ~ +50 VDC
Off Voltage Level Dry Contact -
Wet Contact +1 VDCMax.
Input Impedance 10 KΩ, 0.5 W
Counters Channels 5
Max. Count 16-bit (65535)
Max. Input Frequency 100 Hz
Min. Pulse Width 5 ms
Overvoltage Protection 70 VDC
Relay Output
Type Signal Relay Power Relay
Channels 2 (Channel 0,1) 4 (Channel 2 ~ 5)
Contact Material Silver Nickel, Gold-plated Silver Nickel Alloy
Contact Rating Max. Load Current 0.24 A @ 220 VAC
2 A @ 30 VDC
5 A @ 220 VAC
5 A @ 30 VDC
Min. Load Current 1 uA @ 100 uV 100 mA @ 5 VDC
Operate Time 3 ms (typical) 5 ms (typical)
Release Time 4 ms (typical) 2 ms (typical)
Mechanical Endurance 108 ops. 15*106 ops.
Electrical Endurance 2*105 ops. 1*105 ops.
Power-on Value Yes, Programmable
Safe Value Yes, Programmable
 
Communication
Interface RS-232/TTL
Format N, 8, 1
Baud Rate 1200 ~ 115200 bps
Protocol Modbus/RTU
Dual Watchdog Yes, Module (2.3 seconds), Communication(Programmable)
Isolation
Intra-module Isolation, Field-to-Logic 3750 VDC
EMS Protection
ESD (IEC 61000-4-2) +/-4kV Contact For Each Terminal
+/-8kV Air For Random Terminal
Power
Reverse Polarity Protection -
Powered from Terminal Block 5 VDC
Consumption 0.12 W Max.
Mechanical
Dimensions (W x L x H) 59 mm x 82 mm x 13 mm
Environment
Operating Temperature -25 ~ +75°C
Storage Temperature -40 ~ +85°C
Humidity 10 ~ 95% RH, Non-condensing
 
XV116i CR 5-channel Isolated Digital Input and 6-channel Relay Output Module with 16-bit Counters (RoHS)
 