MP-1500R2
24 V/6.25 A, 150W Output Modularized Redundant Power for DCS system |
|
| |
| ~ Available soon ~ |
 |
| Model: MP-1500R2 |
|
 |
- Wide input voltage 90 to 264 VAC, 47 to 63Hz
- Internal EMI filter
- Input surge current and overload protection
- Overvoltage protection
- Built-in active PFC function, PF > 0.95
- Power lose detection
|
|
|
| |
 |
| Output |
| DC Voltage |
24VDC (with the range of 23.7 ~ 25.2 VDC) |
| Rated Current |
6.25A |
| Ripple & Noise |
240mVp-p |
| Voltage Tolerance |
5% |
| Line Regulation |
1% |
| Load Regulation |
5% |
| Setup/Rise Time |
3 second max. |
| Hold Up Time |
70ms, 110 VAC |
| 130ms, 230 VAC |
| Input |
| Voltage Range |
90 ~ 264 VAC |
| Frequency Range |
47 ~ 63 Hz |
| Power Factor |
> 0.95 |
| Efficiency |
78% |
| Inrush Current |
60A |
| Leakage Current |
1.5mA |
| Protection |
| Overload |
Overload at the output will not cause damage the power supply; the output will auto recovery at once after removing the circuit while setting at 110% to 150% of the maximum load. |
| Over Voltage |
Overvoltage protection is available on output, if the output voltage reaches an overvoltage condition shall be set at 112% to 132% for its protecting point and then the output will auto recovery at once after removing the abnormal circuit. |
| Function |
| Power lose detection |
When the Power system working, it’s open between terminal D and I.
When AC power failure, it’s short between terminal D and I.
When one of the power when an exception occurs, it’s short between terminal D and I. |
| Environmental |
| Working Temperature |
-20 ~ +35°C |
| Working Humidity |
5 ~ 95% RH, Non-condensing |
| Safety & EMC |
| Safety Standards |
C.S.A C22.2, EN60950-1 |
| Withstand Voltage |
I/P-O/P: 4KVDC, I/P-FG: 2KVDC |
| Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG:>50M Ohms / 500VDC |
| EMC Emission |
EN55022 (CISPR22) Class A, EN61000-3-2,-3 |
| EMC Immunity |
EN61000-4-2 ~ 6, EN61000-4-8, EN61000-4-11, EN55024 |
| Others |
| MTBF |
MTBF(theoretical) at 25°C ambient temp and half load, according to MIL-217F:100,000hrs above.
Lifetime > 8 year at 24 hours in function at load of 1.5A. |
| Dimension (W x H x D) |
65 x 437.2 x 229.4 mm |
|
| |
 |
| MP-1500R2 |
24 V/6.25 A, 150W Output Modularized Redundant Power for DCS system |
|
| |
|
|
| |
|
|