FR-2057TW
16-channel Sink type Isolated High Current Output Module |
|
|
|
FR-2057TW |
|
|
|
|
|
|
 |
|
|
|
|
|
|
|
The FR-2053TA has 16-channel isolated Sink/Source input, while the FR-2057TW has 16-channel isolated sink output. The FR-2000 I/O module has an FRnet interface. The users can daisy chain several FR-2000 modules together. Via FRnet, the FR-2000 modules can extend the remote I/O control of PC, PAC and PLC easily. Further information about the networking of FR-2053TA/2057TW; refer to literature related to I-7188EF, I-8172, FRB-100/200/200U. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
- Built-in Wire-saving FRnet DI/DO control
- High-speed transmission reliability
- Simple synchronization mechanism
- No software overhead on protocol processing
- Supporting broadcasting (1:n data transmission)
- Duplicating output easily
- Fixed I/O scan-time and I/O synchronization
- DIN-Rail mountable
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Digital Output |
Output Channel |
16 |
Output Type |
Sink, Open-Collector (NPN) |
Load Voltage |
30VDC, Max |
Load Current |
250mA, Max |
Isolation Voltage |
3750Vrms |
Interface |
2-wire cabling |
Belden 9841 (2P twisted-pair cable),
When different cables are used, the transmission distance may be changed |
Transfer distance |
Max. 400m for speed 250Kbps
Max. 100m for speed 1Mbps(Default) |
LED Indicators |
Power, Communication Run, Communication Error, Terminal
resistor,Digital output |
Transfer speed |
250Kbps and 1Mbps(Default) |
Cyclic scan time |
2.88ms for speed 250Kbps
0.72ms for speed 1Mbps(Default) |
Connection |
Removable 20-pin Terminal Block |
Power |
Input Voltage Range |
+10 ~ +30VDC (Non-isolation) |
Power consumption |
2.4 W Max. |
Protection |
Power reverse polarity protection |
Frame Ground for EMS Protection |
Yes |
Connection |
5-Pin Removable Terminal Block |
Mechanical |
Casing |
Plastic (Flammability UL 94V-0) |
Flammability |
UL 94V-0 materials |
Dimensions |
32.5mm x 110mm x 102 mm (W x H x D) |
Installation |
DIN-Rail |
Mechanical |
Operating Temperature |
-25 ¢XC~ +75¢XC |
Storage Temperature |
-30 ~ +85¢XC |
Ambient Relative Humidity |
10 to 90% RH, non-condensing |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FR-2057TW |
16-channel Sink type Isolated High Current Output Module |
|
|
|
|
|
|
|
|
|
|