tM-P3R3/tM-PD3R3
3-channel Isolated Digital Input and
3-channel Relay Output Module |
|
|
|
~ NEW ~ |
|
 |
- Relay Outputs
- tM-P3R3
- Wet Contact Source- or Sink-type Digital Inputs
- tM-PD3R3
- Dry Contact Source-type Digital Inputs
- Photocoupler Isolation
- All Channels Can Be Used As 16-bit Counters
- Dual Watchdog
- Configurable Power-on Value Settings
- Configurable Safe Value Settings
- Cost-effective
- Wide Operating Temperature Range: -25 ~ +75°C
|
|
 |
 |
|
Model: tM-P3R3 |
Model: tM-PD3R3 |
|
|
|
 |
The tM-P3R3/tM-PD3R3 provides 3 channels for digital input and 3 channels for relay output, each of which features photocoupler isolation. All output channels are form A type relays, while input is based on sink- or souce-type using a wire connecion. All input channels can be used as 16-bit counters. There are options for
configuring power-on and safe digital output values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided. |
|
 |
- All Types of On/Off Control
- Industrial Automation
- Industrial Machinery
- Building Automation
- Food and Beverage Systems
- Semiconductor Fabrication
- Control Systems
|
|
 |
Model |
tM-P3R3 |
tM-PD3R3 |
Digital Input/Counter |
Input Channels |
3 |
Type |
Wet Contact (Sink, Source) |
Dry Contact (Source) |
Wet Contact |
On Voltage Level |
+3.5 VDC ~ 50 VDC |
- |
OFF Voltage Level |
+1 VDC Max. |
- |
Dry Contact |
ON Voltage Level |
- |
Close to GND |
OFF Voltage Level |
- |
Open |
Counters |
Max. Count |
65535 (16-bit) |
Max. Input Frequency |
100 Hz |
Min. Pulse Width |
5 ms |
Input Impedance |
10 kΩ, 0.5 W |
- |
Overvoltage Protection |
70 VDC |
- |
Relay Output |
Output Channels |
3 |
Type |
Power Relay, Form A (SPST N.O.) |
Operating Voltage Range |
250 VAC or 30 VDC |
Max. Load Current |
5 A |
Operating Time |
6 ms |
Release Time |
3 ms |
Electrical Life
(Resistive load) |
VDE |
5 A @250 VAC 30,000 ops (10 ops/minute) at 75°C |
5 A @30 VDC 70,000 ops (10 ops/minute) at 75°C |
UL |
5 A @250 VAC/30 VDC 6,000 ops |
3 A @250 VAC/30 VDC 100,000 ops |
Mechanical Life |
20,000,000 ops at no load (300 ops/minute) |
Power-on Value |
Yes, Programmable |
Safe Value |
Yes, Programmable |
|
|
 |
Model |
tM-P3R3 |
tM-PD3R3 |
Communication |
Interface |
RS-485 |
Format |
(N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1) |
Baud Rate |
1200 ~ 115200 bps |
Protocol |
DCON, Modbus/RTU, Modbus/ASCII |
Dual Watchdog |
Yes, Module (2.3 seconds), Communication (Programmable) |
LED Indicators |
Power |
1 LED as Power Indicator |
Isolation |
Intra-module Isolation,Field-to-Logic |
3750 VDC |
EMS Protection |
ESD (IEC 61000-4-2) |
±4 kV Contact for Each Terminal |
±8 kV Air for Random Point |
EFT (IEC 61000-4-4) |
±4 kV for Power |
Power Requirements |
Reverse Polarity Protection |
Yes |
Powered from Terminal Block |
Yes, 10 ~ 30 VDC |
Consumption |
0.8 W Max. |
0.9 W Max. |
Mechanical |
Dimensions (W x L x H) |
52 mm x 98 mm x 27 mm |
Installation |
DIN-Rail Mounting |
Environment |
Operating Temperature |
-25 °C ~ +75 °C |
Storage Temperature |
-30 °C ~ +75 °C |
Humidity |
10 ~ 95% RH, Non-condensing |
|
|
 |
tM-P3R3 CR |
3-channel Isolation Digital Input(Wet Contact) and 3-channel Relay Output Module(RoHS) |
tM-PD3R3 CR |
3-channel Isolation Digital Input(Dry Contact) and 3-channel Relay Output Module (RoHS) |
|
|
 |
tM-7561 CR |
Isolated USB to RS-485 Converter (RoHS) |
tM-7520U CR |
Isolated RS-232 to RS-485 Converter (RoHS) |
tM-7510U CR |
Isolated RS-485 Repeater (RoHS) |
MDR-20-24 CR |
24 W Single Output Industrial DIN Rail Power Supply (RoHS) |
|
|
|
|
|
|
|